Siemens 7MF1567-3CB10-1AA1 SITRANS P220 0–16 bar Pressure Transmitter
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use a 0–10 V controller channel with at least 10 kΩ receiving resistance.
- Match the G½ EN837-1 process connection and the medium to the stainless-steel wetted parts.
- Provide 12–33 V DC and wire the three-wire voltage-output circuit.
- Use the specified Form A connector to complete the IP65 assembly; this configuration is not the Ex-protected version.
7MF1567-3CB10-1AA1 SITRANS P220 0–16 bar Pressure Transmitter
A fully welded stainless-steel P220 transmitter for 0–16 bar gauge pressure, with 0–10 V three-wire output and a G½ male process connection.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 7MF1567-3CB10-1AA1 |
| Product Type | Welded pressure transmitter |
| Core Function | Convert process pressure to an analog signal |
| Application | Gauge-pressure measurement of liquids and gases |
Welded pressure measurement
The stainless-steel diaphragm transfers process pressure to a piezoresistive measuring cell in a fully welded construction.
Voltage-output integration
A linearly rising 0–10 V signal connects to a receiving input with a load resistance of at least 10 kΩ.
Industrial process connection
The G½ male process connection follows EN837-1 and the electrical connection uses the Form A plug with M16 cable entry.
Product Overview
7MF1567-3CB10-1AA1 measures gauge pressure over a 0–16 bar range using a stainless-steel piezoresistive measuring cell.
This configuration provides a 0–10 V three-wire output, a 12–33 V DC supply range and a DIN EN175301-803-A electrical connector with an M16 cable entry.
Key Functions
Welded pressure measurement
The stainless-steel diaphragm transfers process pressure to a piezoresistive measuring cell in a fully welded construction.
Voltage-output integration
A linearly rising 0–10 V signal connects to a receiving input with a load resistance of at least 10 kΩ.
Industrial process connection
The G½ male process connection follows EN837-1 and the electrical connection uses the Form A plug with M16 cable entry.
Official Specifications
| Calibrated measuring range | 0–16 bar gauge |
|---|---|
| Overload limits | −1 to +40 bar |
| Burst pressure | 96 bar |
| Output and wiring | 0–10 V DC, three-wire |
| Supply voltage | 12–33 V DC |
| Minimum output load resistance | 10 kΩ |
| Supply current at 10 kΩ load | Less than 7 mA |
| Typical and maximum measuring error | 0.25% and 0.5% of span, including hysteresis and reproducibility |
| Step response T99 | Less than 5 ms |
| Long-term stability | 0.25% of span per year |
| Process-temperature range | −40 to +120 °C |
| Ambient-temperature range | −25 to +85 °C |
| Storage-temperature range | −50 to +100 °C |
| Measuring-cell material | Stainless steel 1.4016 |
| Process-connection and housing material | Stainless steel 1.4404 (316L) |
| Process thread | G½ male to EN837-1 |
| Electrical connection | DIN EN175301-803-A Form A, M16 cable entry |
| Ingress protection | IP65 with the specified Form A connector |
| Explosion-protection configuration | Without explosion protection |
| Approximate mass | 0.090 kg |
Frequently Asked Questions
Can I connect 7MF1567-3CB10-1AA1 to a 4–20 mA analog input?
This version provides a three-wire 0–10 V voltage signal and requires a compatible voltage input.
Does 7MF1567-3CB10-1AA1 measure absolute pressure?
The selected measuring range is 0–16 bar gauge pressure.
Which DC supply should I use for 7MF1567-3CB10-1AA1?
Provide a DC supply between 12 and 33 V.
What input impedance is needed by the controller connected to 7MF1567-3CB10-1AA1?
The receiving load resistance must be at least 10 kΩ.
Which process adapter mates with 7MF1567-3CB10-1AA1?
Use a matching connection for the G½ male thread to EN837-1.
Can I use 7MF1567-3CB10-1AA1 as the Ex-protected version in a hazardous installation?
This order configuration is supplied without explosion protection.
Can 7MF1567-3CB10-1AA1 follow a fast pressure step?
The specified T99 step response is less than 5 ms.