Siemens 7KM9300-0AM00-0AA0 SENTRON PAC RS485 Expansion Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Match the PAC or COM host to the compatibility listing.
- Use the six-pole screw-terminal wiring arrangement.
- Coordinate baud rate and other serial parameters with the Modbus network.
- Use the compatible PAC4200 gateway arrangement when an Ethernet-to-RS485 connection is required.
7KM9300-0AM00-0AA0 SENTRON PAC RS485 Expansion Module
A host-powered RS485 expansion module for Modbus RTU communication, with four selectable baud rates and a six-pole screw-terminal connection.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 7KM9300-0AM00-0AA0 |
| Product Type | Plug-in serial communication module |
| Core Function | Transferring metering data over a serial network |
| Application | Compatible SENTRON meters and data concentrators |
Host-powered expansion
The compatible base device supplies the plug-in module.
Modbus RTU link
Selectable speeds range from 4.8 to 38.4 kbit/s.
Local commissioning
Parameters can be set at the device front or through parameterization software.
Product Overview
7KM9300-0AM00-0AA0 adds an RS485 communication interface to a compatible SENTRON measuring device or data concentrator. The plug-in module uses the Modbus RTU protocol and requires no separate auxiliary power supply.
A six-pole screw-terminal connection serves the serial wiring, while a module LED provides status indication. On a compatible PAC4200, the expansion module supports the gateway arrangement for simple RS485 devices through Ethernet Modbus TCP.
Key Functions
Exchange measured values
Modbus RTU carries the host measuring-device data through the RS485 interface.
Adapt the serial network speed
Four baud-rate settings cover 4.8, 9.6, 19.2 and 38.4 kbit/s.
Support host gateway operation
The PAC4200 gateway arrangement uses the RS485 expansion to reach simple serial devices through Ethernet.
Official Specifications
| Serial protocol | Modbus RTU |
|---|---|
| Selectable baud rates | 4.8, 9.6, 19.2 and 38.4 kbit/s |
| Field connection | 6-pole screw-terminal connection |
| Maximum insulation voltage | 500 V AC |
| Ingress protection | IP20 |
| UL 94 flammability class | V-0 |
| Pollution degree | 2 according to IEC 61131 |
| Housing dimensions | 18 × 90 × 73 mm (W × H × D) |
| Net weight | 41 g |
| Operating temperature | −5 to +55 °C |
| Storage temperature | −25 to +70 °C |
| Statistical MTBF | 222.3 years |
Frequently Asked Questions
Do I need an additional auxiliary power supply for 7KM9300-0AM00-0AA0?
The compatible base device supplies the expansion module, so no external auxiliary power is needed.
How can I configure the serial parameters of 7KM9300-0AM00-0AA0?
Parameters can be assigned at the front of the host device or with parameterization software.
Which baud-rate options can I select on 7KM9300-0AM00-0AA0?
The available speeds are 4.8, 9.6, 19.2 and 38.4 kbit/s.
Can 7KM9300-0AM00-0AA0 provide a direct Ethernet cable port?
The module provides RS485, while the compatible PAC4200 supplies the Ethernet Modbus TCP side of the gateway arrangement.
Which devices are listed for the plug-in 7KM9300-0AM00-0AA0 expansion?
The current compatibility listing includes PAC3220, PAC4200, PAC4220 and 3VA COM100/800.
How is the field cable connected to 7KM9300-0AM00-0AA0?
The serial cable connects through a six-pole screw-terminal arrangement.
Is there a local status indicator on 7KM9300-0AM00-0AA0?
A status LED is provided on the expansion module.