Siemens 7KM2111-1BA00-3AA0 SENTRON PAC3200 Three-Phase Power Monitoring Device
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Keep auxiliary DC power separate from the measured voltage circuit requirements.
- Select and configure the correct current-transformer secondary rating.
- Use the built-in Modbus TCP interface or the appropriate optional communication module for the project.
- Install vertically in a suitable indoor panel and observe environmental and altitude limits.
7KM2111-1BA00-3AA0 SENTRON PAC3200 Three-Phase Power Monitoring Device
A DC-powered LCD meter with transformer current inputs, Modbus TCP and a programmable switching or pulse output.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 7KM2111-1BA00-3AA0 |
| Product Type | Panel power monitoring instrument |
| Core Function | Measuring electrical power and energy |
| Application | Stationary indoor electrical panels |
Multivariable electrical measurement
RMS voltage and true-RMS current measurement accompany active and reactive power and energy functions.
Ethernet measurement access
The integrated Ethernet port supports Modbus TCP for the measured electrical values.
Configurable field signaling
One digital input and one switching or pulse output support the local monitoring arrangement.
Product Overview
7KM2111-1BA00-3AA0 measures voltage, current, power, frequency and energy in a three-phase electrical installation.
The extra-low-voltage DC supply is separate from the voltage measurement circuits, and the integrated Ethernet connection exposes measurements through Modbus TCP.
Key Functions
Multivariable electrical measurement
RMS voltage and true-RMS current measurement accompany active and reactive power and energy functions.
Ethernet measurement access
The integrated Ethernet port supports Modbus TCP for the measured electrical values.
Configurable field signaling
One digital input and one switching or pulse output support the local monitoring arrangement.
Official Specifications
| Auxiliary supply | 22–65 V DC, ±10% |
|---|---|
| Measurement frequency | 45–65 Hz with automatic line-frequency detection |
| Voltage measurement method | RMS; sinusoidal or distorted waveform |
| Current measurement method | True RMS |
| Nominal voltage inputs | 500 V line-to-line; 289 V line-to-neutral |
| Voltage measuring ranges | 70–600 V line-to-line; 40–346 V line-to-neutral |
| Rated current inputs | 1 A or 5 A AC; 10–120% relative measurement range |
| Measurement categories | CAT III for voltage and current; CAT II for digital signals |
| Measurement error limits | Voltage ±0.3%; current ±0.2% |
| Active energy accuracy | Class 0.5 to IEC 61557-12; class 0.5s to IEC 62053-22 |
| Reactive energy accuracy | Class 2 to IEC 61557-12 or IEC 62053-23 |
| Ethernet data interface | One 10 Mbit/s port with Modbus TCP |
| Digital I/O | One digital input and one digital output |
| Digital-output limits | 30 V DC maximum; 27 mA maximum high-state current; short-circuit proof |
| Pulse-output timing | 30–500 ms pulse duration; maximum switching frequency 17 Hz |
| Display and controls | 72 × 54 mm LCD with four keys |
| Front protection | IP65 |
| Operating environment | −10 to +55 °C; maximum 95% RH at 25 °C without condensation |
| Installation altitude | Up to 2,000 m |
| Dimensions and installation depth | 96 × 96 × 56 mm; installation depth 51 mm |
Frequently Asked Questions
Can I power 7KM2111-1BA00-3AA0 directly from a 230 V AC auxiliary supply?
This variant uses an extra-low-voltage DC supply rated 22–65 V DC with the stated tolerance.
Can I use either 1 A or 5 A current-transformer secondaries with 7KM2111-1BA00-3AA0?
The current inputs provide rated measurement choices of 1 A and 5 A AC.
Which protocol is available through the built-in network port of 7KM2111-1BA00-3AA0?
The integrated Ethernet interface supports Modbus TCP.
Does 7KM2111-1BA00-3AA0 measure distorted current waveforms?
The current measurement uses the true-RMS method.
Can the digital output of 7KM2111-1BA00-3AA0 produce energy pulses?
The digital output can be used as either a switching output or a pulse output.
Can I use 7KM2111-1BA00-3AA0 as an outdoor freestanding instrument?
The instrument is intended for stationary panel installation in closed indoor rooms.
Does the front IP65 rating of 7KM2111-1BA00-3AA0 remove the need for a suitable panel enclosure?
The stated IP65 protection applies to the front of the installed meter.