Siemens 6SL3244-0BE17-5UA0 SINAMICS G120 PM240 0.75 kW Power Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Select the matching G120 Control Unit and the required overload configuration.
- Account for the line-reactor choice when sizing the mains circuit.
- Provide the cooling airflow and cabinet protection required by the frame A module.
- Match motor cable, power conductors and the M4 protective-earth connection to the installation.
6SL3244-0BE17-5UA0 SINAMICS G120 PM240 0.75 kW Power Module
Unfiltered PM240 power stage with a 380–480 V three-phase input, 0.75 kW rating and 2.2 A rated output current.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6SL3244-0BE17-5UA0 |
| Product Type | Drive power module |
| Core Function | Motor power conversion |
| Application | Compatible G120 control-unit systems |
Three-phase motor power stage
The module delivers a 0.75 kW rating and 2.2 A rated output for the specified low- and high-overload duties.
Defined overload profiles
Low-overload and high-overload ratings provide different short-term current profiles within a 300-second cycle.
Cabinet drive integration
The unfiltered frame A module uses internal air cooling and separate line, motor and braking-resistor connections.
Product Overview
6SL3244-0BE17-5UA0 provides a PM240 power stage for a SINAMICS G120 drive assembled with a compatible Control Unit.
The frame A module supports low-overload and high-overload duty profiles, screw-terminal power wiring and the stated motor-cable lengths in an internally air-cooled IP20 housing.
Key Functions
Three-phase motor power stage
The module delivers a 0.75 kW rating and 2.2 A rated output for the specified low- and high-overload duties.
Defined overload profiles
Low-overload and high-overload ratings provide different short-term current profiles within a 300-second cycle.
Cabinet drive integration
The unfiltered frame A module uses internal air cooling and separate line, motor and braking-resistor connections.
Official Specifications
| Mains input | 3-phase 380–480 V AC, ±10% |
|---|---|
| Input frequency | 47–63 Hz |
| Input current with line reactor | 2.30 A rated |
| Input current without line reactor | 2.60 A rated |
| LO and HO power rating | 0.75 kW / 1 hp |
| LO and HO rated output current | 2.20 A |
| Maximum output current | 4.40 A |
| Pulse frequency | 4 kHz |
| Output frequency limits | 0–200 Hz for vector control; 0–550 Hz for V/f control |
| Low-overload profile | 110% for 57 s and 150% for 3 s within a 300 s cycle |
| High-overload profile | 150% for 57 s and 200% for 3 s within a 300 s cycle |
| Efficiency | 97% |
| Power loss | 0.10 kW |
| Integrated EMC filter | Unfiltered |
| Cooling and airflow | Internal air cooling; 0.005 m³/s |
| Operating temperature | 0 to +40°C LO; 0 to +50°C HO |
| Maximum installation altitude | 1000 m |
| Motor cable limits | 50 m shielded; 100 m unshielded |
| Power conductors | 1.00–2.50 mm² screw terminals; M4 protective-earth housing connection |
| Housing and dimensions | IP20 / UL open type; FSA; 73 × 173 × 145 mm; 1.10 kg |
Frequently Asked Questions
Does 6SL3244-0BE17-5UA0 include an integrated EMC filter?
The power module is the unfiltered version.
Which mains supply should I select for 6SL3244-0BE17-5UA0?
Use a three-phase 380–480 V AC supply within the ±10% tolerance.
Does fitting a line reactor change the rated input current of 6SL3244-0BE17-5UA0?
The rated input current is 2.30 A with a line reactor or 2.60 A without one.
Can 6SL3244-0BE17-5UA0 deliver 200% current for a short acceleration duty?
The high-overload profile permits 200% output current for three seconds in the stated 300-second cycle.
How does the control mode affect the output-frequency limit of 6SL3244-0BE17-5UA0?
The limit is 200 Hz for vector control or 550 Hz for V/f control.
How far can I place the motor from 6SL3244-0BE17-5UA0?
The specified motor-cable limits are fifty meters shielded or one hundred meters unshielded.
What cabinet temperature limit applies to the overload configuration of 6SL3244-0BE17-5UA0?
The stated operating ceiling is +40°C for low-overload duty or +50°C for high-overload duty.