Siemens 6GK1502-3AA10 SIMATIC NET PROFIBUS OLM/P3 Optical Link Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Identify the OLM generation on both ends of each optical link.
- Use plastic optical fiber and the appropriate BFOC termination for the installation.
- Set a supported legacy data rate and observe the correct same-version or mixed-version link length.
- Review reference-earth connections because the electrical RS485 interface is not isolated.
6GK1502-3AA10 SIMATIC NET PROFIBUS OLM/P3 Optical Link Module
A three-channel OLM/P3 module for legacy PROFIBUS networks using plastic optical fiber, with electrical bus connections and a signaling contact.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6GK1502-3AA10 |
| Product Type | Plastic-fiber optical link module |
| Core Function | PROFIBUS electrical-to-optical network coupling |
| Application | Legacy PROFIBUS plastic-fiber networks |
Plastic-fiber transmission
Optical network connections extend the PROFIBUS segment using the OLM/P3 plastic-fiber arrangement.
Electrical bus coupling
RS485 connections integrate the optical link with electrical PROFIBUS equipment.
Legacy version interoperability
Version 3 partners can operate with Version 2 equipment when their compatibility mode is correctly selected.
Product Overview
6GK1502-3AA10 couples electrical PROFIBUS communication to a plastic-fiber optical network.
The Version 2 OLM/P3 supports legacy transmission rates up to 1.5 Mbit/s and requires the corresponding Version 2 compatibility settings when linked with a Version 3 module.
Key Functions
Plastic-fiber transmission
Optical network connections extend the PROFIBUS segment using the OLM/P3 plastic-fiber arrangement.
Electrical bus coupling
RS485 connections integrate the optical link with electrical PROFIBUS equipment.
Legacy version interoperability
Version 3 partners can operate with Version 2 equipment when their compatibility mode is correctly selected.
Official Specifications
| OLM generation | Version 2 OLM/P3 |
|---|---|
| Channel arrangement | 3 channels |
| Optical medium | Plastic optical fiber |
| Supported data-rate range | 9.6 kbit/s–1.5 Mbit/s; 45.45 kbit/s excluded |
| Electrical connectors | One 9-pin Sub-D connection and one two-pin terminal connection |
| Supply and signaling connector | Five-pin screw terminal block |
| Electrical-interface isolation | RS485 is not galvanically isolated; no isolation from earth |
| Maximum V2-to-V2 plastic-fiber link | 80 m |
| Maximum V2-to-V3 plastic-fiber link | 72 m |
| Throughput delay | 1.5 bit times |
| Signaling interface | Signaling contact |
| Included optical connectors | 2 BFOC connectors |
Frequently Asked Questions
Can 6GK1502-3AA10 operate on a 12 Mbit/s PROFIBUS network?
The Version 2 module supports a maximum data rate of 1.5 Mbit/s.
Does 6GK1502-3AA10 support the 45.45 kbit/s PROFIBUS rate?
The 45.45 kbit/s transmission rate is excluded.
Which optical medium is used by 6GK1502-3AA10?
The OLM/P3 arrangement uses plastic optical fiber.
What is the maximum plastic-fiber distance between two Version 2 units using 6GK1502-3AA10?
The maximum Version 2 to Version 2 plastic-fiber link is 80 m.
Can 6GK1502-3AA10 connect to a Version 3 optical link module?
Set the Version 3 partner to Version 2 compatibility mode with S7 equal to 1 and observe the 72 m mixed-version plastic-fiber limit.
Is the electrical RS485 interface on 6GK1502-3AA10 galvanically isolated?
The RS485 interface is not galvanically isolated, and the module has no isolation from earth.
How much transmission delay does 6GK1502-3AA10 introduce?
The specified throughput delay is 1.5 bit times.