6GK1502-3AA10 SIMATIC NET PROFIBUS OLM/P3 Optical Link Module
A three-channel OLM/P3 module for legacy PROFIBUS networks using plastic optical fiber, with electrical bus connections and a signaling contact.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6GK1502-3AA10 |
| Typus Producti | Plastic-fiber optical link module |
| Functio principalis | PROFIBUS electrical-to-optical network coupling |
| Applicatio | Legacy PROFIBUS plastic-fiber networks |
Plastic-fiber transmission
Optical network connections extend the PROFIBUS segment using the OLM/P3 plastic-fiber arrangement.
Electrical bus coupling
RS485 connections integrate the optical link with electrical PROFIBUS equipment.
Legacy version interoperability
Version 3 partners can operate with Version 2 equipment when their compatibility mode is correctly selected.
Product Overview
6GK1502-3AA10 couples electrical PROFIBUS communication to a plastic-fiber optical network.
The Version 2 OLM/P3 supports legacy transmission rates up to 1.5 Mbit/s and requires the corresponding Version 2 compatibility settings when linked with a Version 3 module.
Key Functions
Plastic-fiber transmission
Optical network connections extend the PROFIBUS segment using the OLM/P3 plastic-fiber arrangement.
Electrical bus coupling
RS485 connections integrate the optical link with electrical PROFIBUS equipment.
Legacy version interoperability
Version 3 partners can operate with Version 2 equipment when their compatibility mode is correctly selected.
Official Specifications
| OLM generation | Version 2 OLM/P3 |
|---|---|
| Dispositio canalium | 3 Canales |
| Mezzo ottico | Plastic optical fiber |
| Supported data-rate range | 9.6 kbit/s–1.5 Mbit/s; 45.45 kbit/s exclusus |
| Connectores electrici | Unum coniunctionis Sub-D novem-pinum et unum coniunctionis terminalis duorum-pinum |
| Supply and Signaling Connector | Blocus terminalis quinque-pinus |
| Isolatio interfaciei electricae | RS485 non est isolatus galvanice; nulla isolatio ab terra |
| Maxima connexio fibrae plasticae inter V2 et V2 | 80 m |
| Maxima connexio fibrae plasticae inter V2 et V3 | 72 m |
| Retardatio pervectionis | 1.5 tempora bit |
| Interfacs signali | Contactus Significativus |
| Conectores ópticos incluidos | 2 connexiones BFOC |
Quaestiones Frequenter Rogatae
Potest 6GK1502-3AA10 operare in rete PROFIBUS ad 12 Mbit/s?
Modulus Version 2 sustinet maximam velocitatem datorum ad 1.5 Mbit/s.
Sustinetne 6GK1502-3AA10 velocitatem PROFIBUS ad 45.45 kbit/s?
Velocitas transmissionis ad 45.45 kbit/s excluditur.
Quod medium opticum utitur 6GK1502-3AA10?
Arrangementum OLM/P3 utitur fibra optica plastica.
Quid est maxima distantia inter duos unitates Versionis 2 per fibras plasticas utentes 6GK1502-3AA10?
Maxima distantia inter unitates Versionis 2 per fibras plasticas est 80 m.
Potestne 6GK1502-3AA10 connexum habere cum modulo optico Versionis 3?
Constitue partnem Versionis 3 in modum compatibilitatis Versionis 2, ubi S7 aequale est 1, et observa limitem mixtae versionis pro fibris plasticis (72 m).
Estne interfacies electrica RS485 in 6GK1502-3AA10 galvanice isolata?
Interfacies RS485 non est galvanice isolata, et modulus nullam isolationem ab terra habet.
Quantum temporis transmissionis 6GK1502-3AA10 introducit?
Tempus transmittendi specificatum est 1,5 tempora bit.