Siemens 6ES7961-1AA00-0AC0 SIMATIC M7 IF 961-DIO Digital I/O Submodule
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Install the submodule in a supported M7 programmable or expansion-module position.
- Use the slot-dependent base address and the correct input, output and interrupt-register offsets.
- Match signal-cable length to shielding and the selected common input delay.
- Provide the required field supply, maintain the specified isolation groups and keep each output within its load rating.
6ES7961-1AA00-0AC0 SIMATIC M7 IF 961-DIO Digital I/O Submodule
A compact digital interface with eight inputs, eight outputs, edge-triggered interrupts and a front sub-D connection.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7961-1AA00-0AC0 |
| Product Type | Digital I/O interface submodule |
| Core Function | Discrete signal acquisition and switching |
| Application | Compatible M7 programmable and expansion modules |
Selectable input filtering
The input-delay setting applies a common delay of approximately 750 µs or 3 ms to the input channels.
Edge-triggered events
Rising and falling input edges can generate interrupts through configurable registers.
Protected DC switching
The digital outputs have electronic short-circuit protection and grouped electrical isolation.
Product Overview
6ES7961-1AA00-0AC0 adds discrete field-signal connections to a compatible M7 carrier module.
Selectable input filtering and edge interrupts support event-driven signal handling, while electronically protected outputs switch small DC loads.
Key Functions
Selectable input filtering
The input-delay setting applies a common delay of approximately 750 µs or 3 ms to the input channels.
Edge-triggered events
Rising and falling input edges can generate interrupts through configurable registers.
Protected DC switching
The digital outputs have electronic short-circuit protection and grouped electrical isolation.
Official Specifications
| Onboard channels | 8 digital inputs and 8 digital outputs |
|---|---|
| Nominal field supply | 24 V DC; permissible load-supply range 20.4–28.8 V |
| Input signal levels | High: 13–30 V DC; low: −30 to +5 V DC |
| Signal-one input current | 4–8.5 mA |
| Common input-delay selection | Approximately 750 µs or 3 ms |
| Input isolation grouping | 2 inputs per isolated group |
| Output isolation grouping | 4 outputs per isolated group |
| Output current | 0.1 A nominal; permissible on-state range 5–100 mA |
| On-state output voltage | L+ minus 1.5 V |
| Maximum lamp load | 2.4 W |
| Maximum switching frequency | 500 Hz for resistive or lamp loads; 2 Hz for a 0.1 A inductive load |
| Input interrupt organization | 1 combined interrupt from up to 8 sources |
| Front connection | 25-pin sub-D socket |
| Maximum signal cable | 1,000 m shielded; unshielded 200 m at 750 µs or 600 m at 3 ms input delay |
| Carrier supply loading | 30 mA referenced to 24 V in M7-300; 85 mA referenced to 5 V in M7-400 |
| Power loss | 2.4 W |
| Isolation test | 500 V DC |
| Dimensions and weight | 18.2 × 67 × 97 mm (W × H × D); 0.065 kg |
Frequently Asked Questions
Can 6ES7961-1AA00-0AC0 generate an event when an input changes state?
Input interrupts can be configured for rising edges, falling edges or both.
Can I set a different input filter on every channel of 6ES7961-1AA00-0AC0?
The selected delay of approximately 750 µs or 3 ms applies in common to all input channels.
How are the field inputs on 6ES7961-1AA00-0AC0 electrically grouped?
The eight inputs are isolated in groups of two.
Can I parallel the outputs of 6ES7961-1AA00-0AC0 for a larger load?
Parallel wiring of two outputs is not permitted.
Which connector carries the field signals on 6ES7961-1AA00-0AC0?
The front connection is a 25-pin sub-D socket.
Does 6ES7961-1AA00-0AC0 provide a separate diagnostic function?
The submodule has no diagnostic function.
Can 6ES7961-1AA00-0AC0 use a 500 m unshielded input cable?
The unshielded-cable limit is 600 m with the 3 ms input delay and 200 m with the 750 µs delay.