Overview
- Use the mounting rail intended for module replacement during operation.
- Install active bus bases only with power removed.
- Keep the station on one rack and within the maximum 12 I/O assemblies to the right of the IM 650.
- Use a backplane bus cover for each unused slot and a bus module cover at the final base.
- Order the backplane bus cover separately where required.
- For intrinsically safe configurations, preserve the specified Ex partition between the relevant areas.
6ES7650-8PC00-1AA0 ET 200PA SMART Coated BM 2x40 Active Bus Module
A conformally coated BM 2x40 base for two 40 mm I/O modules, supporting the ET 200PA SMART module insertion and removal arrangement.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7650-8PC00-1AA0 |
| Product Type | Coated active I/O bus module |
| Core Function | Maintains the backplane connection during I/O module replacement |
| Application | ET 200PA SMART process I/O stations |
Coated construction
The coating is specified for ISA-S71.04 severity levels G1, G2 and G3.
Two I/O positions
The base accepts two I/O modules with a width of 40 mm each.
Continuous backplane path
Other modules remain reachable when an I/O position is unoccupied.
Product Overview
6ES7650-8PC00-1AA0 carries two 40 mm wide I/O modules on the active backplane of an ET 200PA SMART station.
This coated variant supports the insertion and removal arrangement while maintaining the backplane path to the other modules, and its conformal coating is specified for ISA-S71.04 severity levels G1, G2 and G3.
Key Functions
Carry the paired I/O modules
The module provides the mounting positions for two 40 mm wide I/O assemblies.
Preserve communication to the remaining rack
The active bus arrangement keeps the other backplane modules accessible when a module is absent.
Add conformal coating for the specified environment
The coated construction is assigned to ISA-S71.04 G1, G2 and G3 severity levels.
Official Specifications
| I/O mounting capacity | Two positions for 40 mm wide I/O modules |
|---|---|
| Conformal-coating classification | ISA-S71.04 severity levels G1, G2 and G3 |
| Dimensions (W × H × D) | 97 × 92 × 30 mm |
| Approximate weight | 140 g |
| Permissible ambient temperature, horizontal assembly | 0 to 60 °C |
| Permissible ambient temperature, vertical assembly | 0 to 40 °C |
| Degree of protection, ET 200PA SMART assembly | IP20 |
| Mechanical locking | Inter-module latches and a mounting-rail lock |
Frequently Asked Questions
How does the -1AA0 version of 6ES7650-8PC00-1AA0 differ from the standard bus base?
This version has conformal coating for ISA-S71.04 severity levels G1, G2 and G3.
Where is 6ES7650-8PC00-1AA0 positioned relative to the first active bus module?
The I/O bus base is fitted to the right of the PS/IM or IM/IM base and slid left until the module connectors make contact.
Can 6ES7650-8PC00-1AA0 be used as the mounting base for an IM 650?
This base carries two 40 mm I/O modules, while the IM 650 uses the dedicated PS/IM or IM/IM bus base.
Does 6ES7650-8PC00-1AA0 itself have to be installed with the rack de-energized?
Active bus modules must be installed in a de-energized state.
What secures 6ES7650-8PC00-1AA0 to the rail after the I/O modules are fitted?
Tightening the mounted module screws also fixes the bus base to the mounting rail.
Does coating eliminate the need to cover an empty slot on 6ES7650-8PC00-1AA0?
An unoccupied slot still requires a backplane bus cover, and the final bus module requires its end cover.
Will the remaining rack become unreachable when one I/O module is removed from 6ES7650-8PC00-1AA0?
The active backplane keeps the other modules accessible when a module is missing.