Siemens 6ES7650-8EK70-0AA0 SIMATIC ET 200PA SMART 16DQ 24VDC/0.5A Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the module with the specified IM 650-8PH station interface.
- Check all four-channel potential groups and their total current against the mounting-temperature limits.
- Confirm the 40-pin connector and field-cable arrangement in the order.
- Configure diagnostic alarms and verify load-supply polarity before commissioning.
6ES7650-8EK70-0AA0 SIMATIC ET 200PA SMART 16DQ 24VDC/0.5A Output Module
Sixteen 24 V DC, 0.5 A outputs with channel diagnostics and a 40-pin front connection for ET 200PA SMART stations using IM 650-8PH.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7650-8EK70-0AA0 |
| Product Type | Digital output module |
| Core Function | Switching DC actuators with configurable diagnostics |
| Application | ET 200PA SMART stations with IM 650-8PH |
Actuator switching
Sixteen outputs switch suitable DC loads at a rated current of 0.5 A per channel.
Diagnostic visibility
Parameterized diagnostics support wire-break detection in both output states and reporting of short circuits or missing group load voltage.
Grouped load circuits
Four-channel potential groups support organized field wiring while retaining isolation from the backplane bus.
Product Overview
6ES7650-8EK70-0AA0 provides sixteen digital outputs for ET 200PA SMART process I/O, with configurable diagnostic reporting for wire breaks, short circuits and load-supply faults.
The outputs are arranged in groups of four, so load-current planning must consider both each channel rating and the total current permitted for each group.
Key Functions
Actuator switching
Sixteen outputs switch suitable DC loads at a rated current of 0.5 A per channel.
Diagnostic visibility
Parameterized diagnostics support wire-break detection in both output states and reporting of short circuits or missing group load voltage.
Grouped load circuits
Four-channel potential groups support organized field wiring while retaining isolation from the backplane bus.
Official Specifications
| Digital outputs | 16 |
|---|---|
| Rated load voltage | 24 V DC |
| Reverse-polarity protection | Not provided |
| Rated / permissible on-state current | 0.5 A / 5 mA–0.6 A per channel |
| Maximum output-group current | 2 A per group at up to 60 °C horizontal or 40 °C vertical mounting |
| Typical short-circuit response threshold | 1.4 A per channel |
| Maximum L+ / backplane current | 100 mA from L+; 100 mA from the 5 V backplane |
| Typical power loss | 6 W |
| Minimum on-state voltage | L+ minus 1.3 V |
| Maximum off-state leakage current | 0.7 mA |
| Typical switching delay | 3 ms on and 3 ms off |
| Maximum lamp load | 5 W |
| Permitted load resistance | 48 Ω–4 kΩ |
| Switching frequency | 100 Hz resistive; 2 Hz DC-13 inductive; 10 Hz lamp load |
| Maximum signal cable length | 1,000 m shielded; 600 m unshielded |
| Wire-break detection | Supported in both output state 0 and output state 1 |
| Potential groups | 4 channels per isolated group; isolated from backplane |
| Front connection | 1 × 40-pin connector |
| Dimensions (W × H × D) | 40 × 125 × 120 mm |
| Approximate weight | 300 g |
Frequently Asked Questions
Which station interface is required for 6ES7650-8EK70-0AA0?
The module is intended for ET 200PA SMART stations with an IM 650-8PH interface.
Can all four outputs in one group of 6ES7650-8EK70-0AA0 supply 0.5 A?
A four-output group permits a total of 2 A within the specified mounting and temperature conditions.
Does 6ES7650-8EK70-0AA0 protect against reversed load-supply polarity?
Reverse-polarity protection is not provided, so check the 24 V DC wiring before energizing the module.
Can 6ES7650-8EK70-0AA0 detect a broken wire while an output is off?
Wire-break diagnostics are supported in both output state 0 and output state 1.
May outputs on 6ES7650-8EK70-0AA0 be paralleled to raise load current?
Paralleling for increased current is not supported.
What front connector is required by 6ES7650-8EK70-0AA0?
The field connection uses one 40-pin front connector.
What must be considered when measuring an off output on 6ES7650-8EK70-0AA0?
Allow for the specified off-state leakage of up to 0.7 mA when interpreting a voltage measured across the connected load.