Siemens 6ES7650-8EK70-0AA0 SIMATIC ET 200PA SMART 16DQ 24VDC/0.5A Output Module
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Utere modulo cum specificato IM 650-8PH stationis interfacie.
- Verifica omnes quattuor canales potentialis gruppos et eorum totalem currentem contra limites temperaturae montandi.
- Confirma conectori 40-pin et dispositionem campi-cabli in ordine.
- Configura allarmes diagnosticos et verifica polaritatem oneris-supplendi antequam in operationem mittitur.
6ES7650-8EK70-0AA0 SIMATIC ET 200PA SMART 16DQ 24VDC/0.5A Output Module
Sixteen 24 V DC, 0.5 A outputs with channel diagnostics and a 40-pin front connection for ET 200PA SMART stations using IM 650-8PH.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7650-8EK70-0AA0 |
| Typus Producti | Modulus Exitus Digitalis |
| Functio principalis | Switching DC actuators with configurable diagnostics |
| Applicatio | ET 200PA SMART stations with IM 650-8PH |
Commutation d’actionneur
Sedecim interruptores de output idonei ad oneranda directa continua, cum currente nominali 0.5 A per canalum.
Visibilitas Diagnostica
Diagnosticum parametratum sublevat detectionem interruptionis fili in utroque statu output et notificatationem circuituum curtiorum vel absentiae tensionis in gruppo onerum.
Circuits de onus aggregati
Quattuor canales grupporum potentialium sublevant ordinatam connexionem in campo, dum isolatio a bus dorsalis retinetur.
Product Overview
6ES7650-8EK70-0AA0 Praebet sedecim outputs digitalis pro ET 200PA SMART process I/O, cum reportatione diagnosticorum configurabili pro interruptionibus filorum, circuitibus curtioribus et defectibus in supply onerum.
Outputs in gruppos quattuor dispositi sunt; ideo planificatio currentis oneris considerare debet tam ratingem per canalum quam currentem totalem permissum pro quolibet gruppo.
Key Functions
Commutation d’actionneur
Sedecim interruptores de output idonei ad oneranda directa continua, cum currente nominali 0.5 A per canalum.
Visibilitas Diagnostica
Diagnosticum parametratum sublevat detectionem interruptionis fili in utroque statu output et notificatationem circuituum curtiorum vel absentiae tensionis in gruppo onerum.
Circuits de onus aggregati
Quattuor canales grupporum potentialium sublevant ordinatam connexionem in campo, dum isolatio a bus dorsalis retinetur.
Official Specifications
| Emissiones Digitales | 16 |
|---|---|
| Tensio nominis oneris | 24 V DC |
| Protectio contra polaritatem inversam | Non praebita |
| Currentis in statu activo nominalis / permittenda | 0.5 A / 5 mA–0.6 A per canalum |
| Maximalis eliĝ-grupo kurento | 2 A per gruppus ad temperaturam usque ad 60 °C in positione horizontali aut 40 °C in positione verticali |
| Typical Short-Circuit Response Threshold | 1.4 A per channel |
| Maxima currentis L+ / bus dorsalis | 100 mA ab L+; 100 mA ab 5-V-Rückwand |
| Perditio potentiæ typica | 6 W |
| Minimum Tensionis in Statu Activato | L+ minus 1,3 V |
| Maxima Currentis Fugae in Statu Off | 0.7 mA |
| Typische Schaltdauer | 3 ms ein und 3 ms aus |
| Maxima onus lampadis | 5 w |
| Permitted Load Resistance | 48 Ω–4 kΩ |
| Commutatione Frequency | 100 Hz ohmsch; 2 Hz Gleichstrom-13 induktiv; 10 Hz Lampenlast |
| Longitudo maxima vitarum signali | 1 000 m scutum; 600 m non scutum |
| Detectio interrupti fili | Unterstützt in beiden Ausgangszuständen 0 und 1 |
| Grupos de potencial | 4 Kanäle pro isolierter Gruppe; isoliert von der Rückwand |
| Coniunctio anterior | 1 × 40-poliger Steckverbinder |
| Dimensiones (L × H × D) | 40 × 125 × 120 mm |
| Pondus Approximatum | 300 g |
Quaestiones Frequenter Rogatae
Welche Stations-Schnittstelle wird für 6ES7650-8EK70-0AA0 benötigt?
Modulus destinatus est pro stationibus ET 200PA SMART cum interfacie IM 650-8PH.
Possuntne omnes quattuor exsitus in uno gruppo 6ES7650-8EK70-0AA0 suppetere 0,5 A?
Unus quattuor-exsitus-gruppus permittit summam 2 A sub condicionibus specificatis montandi et temperaturae.
Num 6ES7650-8EK70-0AA0 protegit contra inversam polaritatem alimentationis oneris?
Protectio contra inversam polaritatem non praebetur; igitur ante activandam modulum inspicienda est connexio 24 V DC.
Num 6ES7650-8EK70-0AA0 potest detegere interruptum filum dum exsitus est ex?
Diagnostics interrupti fili supportantur in utroque statu exsitus: 0 et 1.
Num exsitus 6ES7650-8EK70-0AA0 paralleli fieri possunt ad augendam currentem oneris?
Parallelismus ad augendam currentem non suadetur.
Quis connectens anterior requiritur ab 6ES7650-8EK70-0AA0?
Conexio interrumpida campi utitur unum conectori frontali 40-pin.
Quid considerandum est dum mensuratur exire off in 6ES7650-8EK70-0AA0?
Admittendum est specificatum perditum statu off usque ad 0,7 mA dum interpretatur voltatio mensurata trans onerem connectum.