Siemens 6ES7650-1AF51-2XX0 SIMATIC PCS 7 Eight-Channel Thermocouple MTA Terminal Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the supported SM 331 TC module and observe the E-Stand requirement for the 7PF10 version.
- Keep thermocouple polarity and shield connections consistent from the field device to the MTA.
- Provide 21.6–28.8 V DC and the specified 0.5 A module fuse.
- Set active channels to TC-EL external compensation and retain the Pt100 reference-junction connection.
SIEMENS SIMATIC PCS 7 ET 200M
6ES7650-1AF51-2XX0 SIMATIC PCS 7 Eight-Channel Thermocouple MTA Terminal Module
Eight-channel thermocouple terminal assembly with an integrated Pt100 reference-junction sensor, fused module supply and field-cable shield connections.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7650-1AF51-2XX0 |
| Product Type | Thermocouple marshalled termination assembly |
| Core Function | Field termination of thermocouple signals |
| Application | ET 200M thermocouple input systems |
Reference junction
Integrated Pt100 sensor is thermally coupled to the field terminals.
Serviceable supply
A removable L+/M power connector feeds the module through a fuse.
Shield management
Channel shield terminals and an earth-ground stud organize field-cable shields.
Product Overview
6ES7650-1AF51-2XX0 terminates eight thermocouple channels for an ET 200M thermocouple input module through a SIMATIC PCS 7 marshalled termination assembly.
An integrated Pt100 reference-junction sensor supports temperature compensation, while fixed field terminations reduce measurement errors and a green LED indicates available module power.
Key Functions
Eight-channel thermocouple termination
Each field channel provides TC+, TC− and shield connections, with signal connections routed to the I/O module through J1.
Integrated cold-junction sensing
The built-in Pt100 sensor is thermally coupled to the field terminals for reference-junction measurement.
Fused power distribution
Input power passes through the module power fuse, with a green indicator showing the presence of module power.
Official Specifications
| Thermocouple channel count | 8 |
|---|---|
| Integrated reference sensor | Pt100 RTD thermally coupled to the field terminals |
| Single-feed supply voltage | 21.6–28.8 V DC |
| Maximum current consumption | 0.243 A with all channels connected |
| Typical power dissipation | 1 W |
| Module supply fuse | 0.5 A; Bussmann GMA-0.5A |
| Power and field terminal conductor sizes | 24–14 AWG; 0.205–2.08 mm² |
| Supply connection | Removable screw-retained L+ and M connector |
| Field terminal arrangement | Fixed TC+, TC− and shield terminals for each channel |
| I/O connection | J1 connector |
| Power indication | Green module-power LED |
| Mounting rail | 35 mm deep top-hat DIN rail |
| Ambient temperature | −25 to +60 °C |
| Relative humidity | 5–95%; non-condensing |
| External compensation accuracy | ±0.3 °C or 0.6% of terminal temperature |
Frequently Asked Questions
Which ET 200M input modules can I connect to 6ES7650-1AF51-2XX0?
The assembly interfaces with 6ES7331-7PF10-0AB0 from E-Stand 4 and with 6ES7331-7PF11-0AB0.
Does 6ES7650-1AF51-2XX0 support Serviceable supply for mobile equipment?
A Pt100 reference-junction sensor is already built into the terminal assembly and thermally coupled to its field terminals.
Can I unplug the thermocouple terminal blocks on 6ES7650-1AF51-2XX0?
The thermocouple field connections are fixed to reduce measurement errors.
Which replacement module-power fuse belongs in 6ES7650-1AF51-2XX0?
The module supply uses a 0.5 A GMA-0.5A fuse, available from Siemens as spare part A5E01568885.
Where do I terminate cable shields on 6ES7650-1AF51-2XX0?
Each channel has a shield connection and the assembly has a shield ground stud for connection to earth.
Can I fit a power-monitor board to 6ES7650-1AF51-2XX0?
The power-monitor board option is not available on this thermocouple MTA.
Can I use 6ES7650-1AF51-2XX0 in a redundant thermocouple input pair?
Neither this MTA nor the connected eight-channel thermocouple module supports redundant operation.