Siemens 6ES7422-1BH10-0AA0 SIMATIC S7-400 SM422 16DO 24VDC/2A Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Apply the supply behavior of the exact 1BH10 revision when replacing a module.
- Provide both eight-output group supplies during commissioning.
- Calculate current for adjacent pairs 0/1, 2/3 and onward through 14/15.
- Do not use parallel outputs to increase current, and check the load type and switching rate.
6ES7422-1BH10-0AA0 SIMATIC S7-400 SM422 16DO 24VDC/2A Output Module
SM422 with sixteen 24 V DC, 2 A outputs, isolation in two groups of eight and paired-channel supply-current limits.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7422-1BH10-0AA0 |
| Product Type | Digital output module |
| Core Function | Switching DC field loads from the S7-400 |
| Application | S7-400 central and expansion I/O racks |
Sixteen DC load channels
Provides a 2 A rated current per output for suitable 24 V DC loads.
Paired-current planning
Each adjacent channel pair permits 3 A total up to 40 °C or 2 A total up to 60 °C.
Direct channel indication
Green channel LEDs continue to indicate system state even when the front connector is not inserted.
Product Overview
6ES7422-1BH10-0AA0 switches sixteen DC loads in an S7-400 rack, with the channels electrically separated into two groups of eight.
This 1BH10 version requires load voltage to be applied to both eight-output groups during commissioning, and loss of one group supply can switch off all outputs, making the supply arrangement important during replacement.
Key Functions
Sixteen DC load channels
Provides a 2 A rated current per output for suitable 24 V DC loads.
Paired-current planning
Each adjacent channel pair permits 3 A total up to 40 °C or 2 A total up to 60 °C.
Direct channel indication
Green channel LEDs continue to indicate system state even when the front connector is not inserted.
Official Specifications
| Digital outputs | 16 |
|---|---|
| Rated electronics and load voltage | 24 V DC |
| Rated output current | 2 A per channel |
| Paired-channel aggregate current | 3 A up to 40 °C; 2 A up to 60 °C per adjacent channel pair |
| Channel grouping and isolation | 2 groups of 8; isolated from the backplane |
| Maximum current consumption | 160 mA from backplane; 30 mA from L+ without load |
| Typical power dissipation | 5 W |
| Minimum on-state output voltage | L+ minus 0.5 V |
| Maximum off-state leakage | 0.5 mA |
| Maximum resistive-load delay | 1 ms for either switching transition |
| Load-resistance range | 12 Ω–4 kΩ |
| Maximum lamp load | 10 W |
| Switching frequency | 100 Hz resistive; 0.2 Hz inductive at 1 A or 0.1 Hz at 2 A; 10 Hz lamp load |
| Short-circuit protection | Electronically cyclic; response threshold 2.8–6 A |
| Maximum signal-cable length | 1,000 m shielded; 600 m unshielded |
| Permissible potential difference | 75 V DC or 60 V AC between separate circuits |
| Insulation test voltage | 500 V DC |
| Status and diagnostics | Green LED per channel; no interrupts or diagnostic functions |
| Dimensions (W × H × D) | 25 × 290 × 210 mm |
| Approximate weight | 600 g |
Frequently Asked Questions
Must both eight-output groups be supplied when commissioning 6ES7422-1BH10-0AA0?
Apply rated load voltage at least once to each eight-output group during commissioning.
Can loss of one group supply on 6ES7422-1BH10-0AA0 affect the other outputs?
Loss of a group load supply can switch off all outputs, including those in the other group.
Does the eight-channel isolation group define the current budget for 6ES7422-1BH10-0AA0?
The aggregate-current limit applies to adjacent two-channel supply pairs, with 3 A permitted up to 40 °C or 2 A up to 60 °C.
May two outputs on 6ES7422-1BH10-0AA0 be paralleled to raise current capacity?
Paralleling outputs to increase load capability is not permitted.
What can restore an output of 6ES7422-1BH10-0AA0 after short-circuit protection operates?
Change the output signal, interrupt the module load voltage or briefly disconnect the load when reclosing under full load does not occur.
Do the channel LEDs on 6ES7422-1BH10-0AA0 still operate without the front connector?
The channel-status LEDs continue to indicate system state when the front connector is absent.
Can 6ES7422-1BH10-0AA0 report channel diagnostic alarms?
This module has no diagnostic functions or interrupts.