Siemens · SIMATIC S7-400
6ES7412-1XF04-0AB0 CPU 412-1 Central Processing Unit
Siemens 6ES7412-1XF04-0AB0 is the SIMATIC S7-400 CPU 412-1 with separate 72 KB code and data work memory, MPI/PROFIBUS DP communication and fast instruction processing.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7412-1XF04-0AB0 |
| Product Type | Standard S7-400 programmable controller CPU |
| Core Function | Executes medium-scale machine and process automation programs |
| Application or Compatible Series | SIMATIC S7-400 central and expansion rack systems |
Firmware Match
Confirm the installed firmware level and the STEP 7 hardware catalog entry before exchange.
Memory Transfer
Back up the project and match the flash or RAM memory card used by the application.
Bus Parameters
Preserve MPI or PROFIBUS DP addresses, baud rates, node configuration and termination.
Product Overview
Siemens 6ES7412-1XF04-0AB0 is the SIMATIC S7-400 CPU 412-1 with separate 72 KB code and data work memory, MPI/PROFIBUS DP communication and fast instruction processing.
Separate code and data work areas support structured S7-400 applications. The onboard interface handles programming, HMI and PROFIBUS communication tasks. Bit, word and integer operations execute in approximately one tenth of a microsecond.
Key Functions
Balanced Work Memory
Separate code and data work areas support structured S7-400 applications.
Integrated MPI/DP
The onboard interface handles programming, HMI and PROFIBUS communication tasks.
Fast Instruction Processing
Bit, word and integer operations execute in approximately one tenth of a microsecond.
Official Specifications
| Firmware Version | V4.0.0 |
|---|---|
| Integrated Work Memory | 72 KB for code and 72 KB for data |
| Integrated Load Memory | 256 KB RAM |
| Memory Card Expansion | Up to 64 MB with a FLASH card or up to 64 MB with a RAM card |
| Battery-Backed Data | All working and load memory retained with the backup battery |
| Execution Time for Bit, Word and Integer Operations | 0.1 µs |
| Floating-Point Operation Time | 0.3 µs |
| S7 Counters | 2,048 counters; retention configurable from Z0 to Z2047, preset Z0 to Z7; count range 1 to 999 |
| S7 Timers | 2,048 timers; no preset retentive timers; time range 10 ms to 9,990 s |
| Marker Memory and Retention | 4 KB; adjustable from MB0 to MB4095, preset MB0 to MB15; 1 clock-memory byte |
| Data Blocks | Up to 511 blocks with DB0 reserved; maximum block size 64 KB |
| Local Data | Up to 8 KB configurable; 4 KB preset |
| Program Blocks | Up to 256 function blocks and 256 functions; size limited by work memory |
| Block Nesting Depth | 24 per priority class plus 2 additional levels inside an error OB |
| I/O Address Area | 4 KB inputs and 4 KB outputs; up to 2 KB each through the integrated MPI/DP interface |
| Process Image | Up to 4 KB inputs and 4 KB outputs, configurable; 128 bytes each preset; up to 15 partial process images |
| Channel Capacity | Up to 32,768 digital input/output channels and 2,048 analog input/output channels |
| Maximum Consistent Data | 244 bytes |
Frequently Asked Questions
Which memory card types can I use with 6ES7412-1XF04-0AB0?
Use a compatible S7-400 flash or RAM card sized for the archived program and load memory.
What should I compare before exchanging 6ES7412-1XF04-0AB0?
Compare firmware, memory card, rack slot, interface settings, project hardware configuration and backup state.
How much integrated work memory does 6ES7412-1XF04-0AB0 provide?
It provides seventy-two kilobytes for code and a separate seventy-two kilobytes for data.
Can 6ES7412-1XF04-0AB0 connect to a PROFIBUS network?
Yes, the integrated MPI/DP interface can be configured for the supported PROFIBUS application.
Why might 6ES7412-1XF04-0AB0 remain in STOP after replacement?
A firmware, memory-card, hardware-configuration or bus-parameter mismatch can prevent a successful startup.
What I/O address capacity is available on 6ES7412-1XF04-0AB0?
The total address area is four kilobytes for inputs and four kilobytes for outputs.
How should I commission 6ES7412-1XF04-0AB0 in an existing rack?
Load the verified project, check diagnostics, confirm all bus nodes and test controlled outputs before returning to production.
Compatibility & Ordering Notes
Compatibility Checklist
- Match the exact CPU 412-1 hardware and firmware entry in the archived STEP 7 project.
- Retain the approved flash or RAM memory card and verify that the complete application fits.
- Restore MPI or PROFIBUS parameters, rack allocation, process images and diagnostic organization blocks.