Overview
SIMATIC S7-400

6ES7412-1XF03-0AB0 SIMATIC S7-400 CPU 412-1 Processor

A CPU 412-1 with separate program and data work-memory areas and an integrated MPI/PROFIBUS DP interface.

At a Glance

Brand Siemens
Model 6ES7412-1XF03-0AB0
Product Type Central processing unit
Core Function Cyclic and interrupt-driven control
Application Modular S7-400 automation systems

Separated work-memory areas

The processor provides independent 48 kB program and 48 kB data areas.

Integrated MPI/DP communication

The isolated RS485 interface supports MPI and PROFIBUS DP master or device operation.

Expandable modular system

Rack expansion and supported multicomputing configurations accommodate larger S7-400 installations.

Product Overview

6ES7412-1XF03-0AB0 executes the control program and manages local or distributed I/O in an S7-400 installation.

Its integrated communications interface can serve MPI and PROFIBUS applications, while memory-card expansion, battery backup and a diagnostic buffer support project deployment and maintenance.

Ordering focus: Match the existing CPU order number, program-memory requirement, rack configuration and PROFIBUS role.
Key Functions

Separated work-memory areas

The processor provides independent 48 kB program and 48 kB data areas.

Integrated MPI/DP communication

The isolated RS485 interface supports MPI and PROFIBUS DP master or device operation.

Expandable modular system

Rack expansion and supported multicomputing configurations accommodate larger S7-400 installations.

Official Specifications
Work-memory organization 48 kB program plus 48 kB data; non-expandable
Load-memory capacity 256 kB integrated RAM; memory-card expansion to 64 MB RAM or FEPROM
Bit, word and fixed-point execution 0.2 µs typical
Floating-point execution 0.6 µs typical
S7 counters and timers 256 counters and 256 timers
Timer setting range 10 ms–9,990 s
Flag memory 4 kB
I/O address space 4 kB inputs and 4 kB outputs
Process image 128 bytes each input/output by default; adjustable to 4 kB each at the expense of code RAM
Digital channel capacity 32,768 inputs and 32,768 outputs
Analog channel capacity 2,048 inputs and 2,048 outputs
Integrated bus interface Isolated RS485 MPI/PROFIBUS DP; up to 12 Mbit/s
DP master station capacity Up to 32 DP devices
DP user data per device Up to 244 input bytes and 244 output bytes
Communication connections 16 overall, including reserved PG and OP resources
Rack expansion Up to 21 expansion units, including 6 with communication bus
Diagnostic buffer Up to 200 entries
5 V backplane current 1.5 A typical; 1.6 A maximum
Typical power loss 7.5 W
Dimensions and weight 25 × 290 × 219 mm (W × H × D); approximately 720 g
Frequently Asked Questions

Can I increase the working RAM inside 6ES7412-1XF03-0AB0?

The integrated program and data work-memory areas are not expandable.

Which memory-card capacity can 6ES7412-1XF03-0AB0 use for load memory?

Load memory can be expanded with a RAM or FEPROM card up to 64 MB.

Does 6ES7412-1XF03-0AB0 retain all RAM data without a backup battery?

Backup of all data requires a backup battery.

Can 6ES7412-1XF03-0AB0 take part in a multicomputing rack?

Multicomputing supports up to four CPUs when a UR1 or UR2 rack is used.

How many PROFIBUS DP devices can the integrated master of 6ES7412-1XF03-0AB0 operate?

The integrated DP master supports up to 32 DP devices.

What communication rate can the integrated MPI/DP interface of 6ES7412-1XF03-0AB0 reach?

The integrated interface supports a maximum rate of 12 Mbit/s.

How many events can I review in the diagnostic buffer of 6ES7412-1XF03-0AB0?

The diagnostic buffer holds up to 200 entries.

Compatibility & Ordering Notes
Before ordering 6ES7412-1XF03-0AB0: Match the existing CPU order number, program-memory requirement, rack configuration and PROFIBUS role.

Before installation

  • Check the project work-memory use against the separate code and data limits.
  • Select the memory-card type and capacity for the required load-memory and retention strategy.
  • Match the MPI/PROFIBUS role, station count and cyclic-data allocation to the project.
  • Include CPU backplane current, rack compatibility and the intended backup arrangement in the hardware design.
Hot Selling Models
BSE 400 S112130
E50740A
3TG1010-0AL2
M71X15G4GGA
QIUNT-PS-3x400-500AC/24DC/10
6SE6400-3CC00-2AD3
3RV1031-4AB10
A1S35B
GB2CB09
KIB-M12PS/002-KL2T
BCS018PO1CS4
DFM-100-PA
efector200 OT5203
SLR01
8/U-10B/MST8

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop

Evolo Automation is not an authorized distributor unless otherwise specified, representative, or affiliate of the manufacturer of this product. All trademarks and documents are the property of their respective owners and are provided for identification and informational.