Siemens SIMATIC S7-300 6ES7331-7PF01-0AB0 SM 331 RTD Analog Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Install in a compatible SIMATIC S7-300 rack or ET 200M station.
- Provide 24 V DC load voltage and verify the backplane-current budget.
- Select and wire the required 40-pin front connector.
- Match every channel to the exact RTD family or resistance range.
- Use three- or four-wire wiring when lead-resistance compensation is required.
Siemens · SIMATIC S7-300
6ES7331-7PF01-0AB0 SM 331 RTD Analog Input Module
Siemens 6ES7331-7PF01-0AB0 is the isolated SIMATIC S7-300 SM 331 eight-channel analog input module for resistance and RTD measurement in S7-300 and ET 200M systems.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7331-7PF01-0AB0 |
| Product Type | SIMATIC S7-300 SM 331 Analog Input Module |
| Core Function | Acquires resistance and resistance-temperature-detector signals |
| Application or Compatible Series | SIMATIC S7-300 and ET 200M systems |
Sensor Selection
Use supported Pt, Ni, LG-Ni or Cu10 resistance thermometers or one of the direct resistance ranges.
Wiring Layout
Choose two-, three- or four-wire resistance wiring and account for uncompensated leads in two-wire mode.
Panel Integration
Provide 24 V DC load voltage and select the required 40-pin front connector separately.
Product Overview
Siemens 6ES7331-7PF01-0AB0 is the isolated SIMATIC S7-300 SM 331 eight-channel analog input module for resistance and RTD measurement in S7-300 and ET 200M systems.
Parameterizable characteristic curves cover Pt100/200/500/1000, Ni100/120/200/500/1000, LG-Ni1000 and Cu10. Eight inputs support 0 to 150 Ω, 0 to 300 Ω and 0 to 600 Ω ranges with 16-bit conversion. Parameterizable diagnostics, diagnostic alarms and limit-value hardware interrupts support maintenance.
Key Functions
Broad RTD Linearization
Parameterizable characteristic curves cover Pt100/200/500/1000, Ni100/120/200/500/1000, LG-Ni1000 and Cu10.
Flexible Resistance Acquisition
Eight inputs support 0 to 150 Ω, 0 to 300 Ω and 0 to 600 Ω ranges with 16-bit conversion.
Channel Diagnostics and Alarms
Parameterizable diagnostics, diagnostic alarms and limit-value hardware interrupts support maintenance.
Official Specifications
| Rated Load Voltage | 24 V DC |
|---|---|
| Maximum Current from L+ Without Load | 240 mA |
| Maximum Current from 5 V Backplane Bus | 100 mA |
| Typical Power Loss | 4.6 W |
| Analog Input Count | 8 |
| Supported RTD Families | Pt100/200/500/1000; Ni100/120/200/500/1000; LG-Ni1000; Cu10 |
| Direct Resistance Ranges | 0 to 150 Ω, 0 to 300 Ω and 0 to 600 Ω |
| Maximum Shielded Cable Length | 200 m |
| Maximum Resolution with Overrange | 16-bit two’s complement |
| Basic Conversion Time | 10 ms per module with up to four channels; 80 ms per module with all eight channels |
| Interference-Frequency Suppression | 400, 60 or 50 Hz |
| Sensor Wiring Methods | Two-wire without resistance correction, three-wire and four-wire |
| Resistance Operational Error Limit | ±0.1% of input range |
| RTD Operational Error Limit | ±1 K |
| Resistance Basic Error Limit at 25 °C | ±0.05% of input range |
| RTD Basic Error Limit at 25 °C | ±0.5 K |
| Isolation Test Voltage | 500 V DC |
| Required Front Connector | 40-pin |
| Dimensions | 40 × 125 × 120 mm |
| Approximate Weight | 272 g |
Frequently Asked Questions
Which resistance sensors can I connect to 6ES7331-7PF01-0AB0?
Supported choices include Pt100/200/500/1000, Ni100/120/200/500/1000, LG-Ni1000 and Cu10 sensors.
Does 6ES7331-7PF01-0AB0 support two-, three- and four-wire resistance sensors?
All three methods are supported, but two-wire operation does not compensate lead resistance.
How should I select the direct resistance range for 6ES7331-7PF01-0AB0?
Parameterize the channel for the applicable 0 to 150 Ω, 0 to 300 Ω or 0 to 600 Ω range before commissioning.
What full-channel conversion time should I expect from 6ES7331-7PF01-0AB0?
With all eight channels enabled, the basic conversion time is 80 ms per module.
Which front connector fits 6ES7331-7PF01-0AB0?
The module requires a 40-pin front connector selected for the cabinet wiring method.
How long can the shielded RTD cable be for 6ES7331-7PF01-0AB0?
Shielded field wiring may be up to 200 m long.
What resistance-measurement accuracy should I allow for 6ES7331-7PF01-0AB0?
Allow ±0.05% basic error at 25 °C and ±0.1% operational error across the full temperature range.