Siemens 6ES7331-7KB02-0AB0 S7-300 SM 331 Two-Channel Analog Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Provide the required 20-pin front connector and configure the selected measurement range.
- Use one channel for resistance measurement and choose the appropriate 2-wire, 3-wire or 4-wire arrangement.
- Select the integration time together with the required interference-rejection frequency.
- Keep general shielded analog wiring within 200 m and thermocouple or ±80 mV wiring within 50 m.
6ES7331-7KB02-0AB0 S7-300 SM 331 Two-Channel Analog Input Module
A configurable two-channel analog module for voltage, current, thermocouple and resistance measurements.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7331-7KB02-0AB0 |
| Product Type | Analog input module |
| Core Function | Digitizing analog measurements |
| Application | Process signal acquisition |
Acquire different signal types
The module accepts bipolar voltage ranges, current signals, selected thermocouples and Pt100 or Ni100 resistance sensors.
Match measurement timing
Selectable integration times of 2.5, 16.67, 20 and 100 ms support different noise-rejection settings.
Support fault response
Diagnostic alarms and a red SF indicator assist troubleshooting, while channel 0 supports limit-value interrupts.
Product Overview
6ES7331-7KB02-0AB0 interfaces analog process signals with an S7-300 controller using selectable measurement ranges and integration times.
Thermocouple compensation, resistance wiring options and diagnostic alarms support temperature and general analog measurement tasks.
Key Functions
Acquire different signal types
The module accepts bipolar voltage ranges, current signals, selected thermocouples and Pt100 or Ni100 resistance sensors.
Match measurement timing
Selectable integration times of 2.5, 16.67, 20 and 100 ms support different noise-rejection settings.
Support fault response
Diagnostic alarms and a red SF indicator assist troubleshooting, while channel 0 supports limit-value interrupts.
Official Specifications
| Analog Input Quantity | 2 channels; resistance measurement uses 1 channel |
|---|---|
| Resolution | 9, 12 or 14 bits, depending on configuration |
| Voltage Ranges | ±80 mV, ±250 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V, ±10 V and 1–5 V |
| Current Ranges | 0–20 mA, 4–20 mA, ±3.2 mA, ±10 mA and ±20 mA |
| Current Input Resistance | 25 Ω |
| Resistance Ranges | 0–150 Ω, 0–300 Ω and 0–600 Ω |
| Supported RTDs | Pt100 and Ni100 |
| Thermocouple Types | E, J, K and N |
| Resistance Measurement Current | 1.67 mA typical |
| Integration Times | 2.5, 16.67, 20 and 100 ms |
| Basic Conversion Times | 3, 17, 22 and 102 ms |
| Noise Rejection Frequencies | 400, 60, 50 and 10 Hz |
| Load Supply | 24 V DC; maximum 30 mA |
| Backplane Current | Maximum 50 mA at 5 V DC |
| Typical Power Loss | 1 W |
| Shielded Signal Cable Limit | 200 m; 50 m for ±80 mV and thermocouples |
| Resistance Wiring | 2-wire, 3-wire or 4-wire |
| Front Connector | 20 pins |
| Dimensions (W × H × D) | 40 × 125 × 120 mm |
| Approximate Weight | 250 g |
Frequently Asked Questions
Can 6ES7331-7KB02-0AB0 measure a 4–20 mA transmitter?
The current inputs support a 4–20 mA range and connection of two-wire or four-wire transmitters.
How many resistance sensors can I connect to 6ES7331-7KB02-0AB0?
Resistance measurement is available on one channel.
Can I connect a Pt1000 directly to 6ES7331-7KB02-0AB0?
The supported resistance-temperature sensors are Pt100 and Ni100.
Which cold-junction compensation methods can I use with 6ES7331-7KB02-0AB0?
Thermocouple operation supports internal compensation, external compensation and a configurable fixed comparison point.
What cable limit applies to a thermocouple on 6ES7331-7KB02-0AB0?
Keep shielded thermocouple and ±80 mV signal cables within 50 m.
Are the two channels of 6ES7331-7KB02-0AB0 electrically isolated from each other?
The channels are not isolated from one another, although they are isolated from the backplane bus.
Which channel can generate a limit-value interrupt on 6ES7331-7KB02-0AB0?
Limit-value interrupt operation is available on channel 0.