Siemens 6ES7322-1BH01-0AA0 S7-300 SM 322 16-Channel DC Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the 20-pin front connector of the output station.
- Apply the group-current derating for the actual orientation and temperature.
- Do not parallel outputs to increase rated load current.
- Use external checks for faults that the module does not diagnose.
6ES7322-1BH01-0AA0 S7-300 SM 322 16-Channel DC Output Module
Sixteen 0.5 A outputs with electronic short-circuit protection, two eight-channel groups and temperature-dependent group-current limits.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7322-1BH01-0AA0 |
| Product Type | Digital output signal module |
| Core Function | Switching of machine actuator circuits |
| Application | SIMATIC S7-300 output stations |
Group current budget
Each group permits 4 A at 40 °C horizontally, falling to 3 A at 60 °C.
Electronic protection
Short-circuit protection has a typical response threshold of 1 A.
Load-dependent switching
Maximum rates are 100 Hz for resistive loads, 0.5 Hz for inductive loads and 10 Hz for lamps.
Product Overview
6ES7322-1BH01-0AA0 controls 16 digital actuator circuits in a SIMATIC S7-300 station. Each channel has a rated output current of 0.5 A, while the eight-channel groups have separate aggregate-current limits that depend on mounting position and temperature.
The module provides electronic short-circuit protection and green output-state LEDs, but it does not provide fault diagnostics for short circuit, wire break or missing load voltage. External commissioning checks remain necessary even when an output is protected.
Key Functions
Switch distributed DC loads
Sixteen outputs operate from a rated 24 V DC load supply and provide up to 0.5 A rated current per channel.
Apply group-current derating
A group permits 4 A at 40 °C horizontally, 3 A at 60 °C horizontally or 2 A at 40 °C vertically.
Protect the switching channels
Electronic short-circuit protection operates at a typical 1 A response threshold.
Official Specifications
| Digital outputs | 16 |
|---|---|
| Load supply | 24 V DC rated; permissible range 20.4–28.8 V |
| Channel output current | 0.5 A rated; permissible signal-1 range 5–600 mA |
| Maximum current per eight-channel group | Horizontal: 4 A up to 40 °C or 3 A up to 60 °C; vertical: 2 A up to 40 °C |
| Minimum signal-1 output voltage | Load voltage L+ minus 0.8 V |
| Maximum signal-0 residual current | 0.5 mA |
| Maximum resistive-load switching delay | 100 µs on; 500 µs off |
| Short-circuit protection | Electronic; typical response threshold 1 A |
| Inductive shutdown-voltage limitation | L+ minus 53 V |
| Maximum lamp load | 5 W |
| Load-resistance range | 48 Ω to 4 kΩ |
| Maximum switching frequency | Resistive: 100 Hz; inductive: 0.5 Hz; lamp: 10 Hz |
| Maximum internal currents | 80 mA from load voltage without load; 80 mA from the 5 V backplane |
| Typical power loss | 4.9 W |
| Maximum cable length | 1,000 m shielded; 600 m unshielded |
| Isolation arrangement | Groups of 8 outputs; optocoupler separation from the backplane |
| Insulation test voltage | 500 V DC |
| Required front connector | 20-pin |
| Indicators and diagnostics | Green output-state LEDs; no diagnostic alarm, wire-break, short-circuit or missing-load-voltage diagnosis |
| Dimensions and approximate weight | 40 × 125 × 120 mm (W × H × D); 190 g |
Frequently Asked Questions
How much group current can 6ES7322-1BH01-0AA0 supply at 60 °C horizontally?
The maximum current per eight-channel group is 3 A in that condition.
Can I raise the current rating of 6ES7322-1BH01-0AA0 by paralleling two outputs?
Parallel switching is not permitted for increasing the output-current rating.
Does electronic short-circuit protection on 6ES7322-1BH01-0AA0 also generate a fault diagnosis?
The module has electronic short-circuit protection but no short-circuit diagnostic function.
How often can 6ES7322-1BH01-0AA0 switch an inductive actuator?
The maximum inductive-load switching frequency is 0.5 Hz.
What is the highest permitted lamp load on one output of 6ES7322-1BH01-0AA0?
The maximum lamp load is 5 W.
Which connector is needed to transfer field wiring to 6ES7322-1BH01-0AA0?
The module requires a 20-pin front connector.
Can I keep a 4 A group load on 6ES7322-1BH01-0AA0 after changing to vertical mounting?
At 40 °C in the vertical position, the group-current limit is 2 A.