Overview
SIMATIC S7-300

6ES7321-1FH00-0AA0 S7-300 SM 321 16 DI 120/230 V AC

An SM 321 with sixteen 120/230 V AC inputs, isolated in groups of four, using one 20-pin front connector.

At a Glance

Brand Siemens
Model 6ES7321-1FH00-0AA0
Product Type Digital input module
Core Function Acquires AC field signals
Application S7-300 I/O racks

Sixteen AC inputs

The input circuit accepts 120/230 V AC signals at 47–63 Hz with IEC 61131 type 1 characteristics.

Grouped input isolation

The sixteen channels are isolated in groups of four, with optocoupler isolation from the backplane bus.

Direct channel indication

Green input-status LEDs show the input states without a group-error SF indicator or module diagnostic alarms.

Product Overview

6ES7321-1FH00-0AA0 acquires sixteen AC input signals through the SM 321 input arrangement.

The module uses optocoupler separation from the backplane, groups its inputs in sets of four and provides green input-status indication, with a fixed input delay rather than configurable interrupt or diagnostic functions.

Ordering focus: Match 120/230 V AC signals, maintain the same phase for all load voltages and select the required 20-pin front connector.
Key Functions

Sixteen AC inputs

The input circuit accepts 120/230 V AC signals at 47–63 Hz with IEC 61131 type 1 characteristics.

Grouped input isolation

The sixteen channels are isolated in groups of four, with optocoupler isolation from the backplane bus.

Direct channel indication

Green input-status LEDs show the input states without a group-error SF indicator or module diagnostic alarms.

Official Specifications
Input channels 16
Input voltage and frequency 120/230 V AC, 47–63 Hz
Input characteristic IEC 61131 type 1
Logic thresholds Logic 0: 0–40 V; logic 1: 79–264 V
Typical input current 6.5 mA at 120 V/60 Hz; 16 mA at 230 V/50 Hz
Input delay 25 ms; not parameterizable
Maximum input cable lengths 1000 m shielded; 600 m unshielded
Two-wire sensor quiescent current Maximum 2 mA
Backplane current Maximum 29 mA at 5 V DC
Typical power loss 4.9 W
Input isolation Groups of four; optocoupler isolation from the backplane
Isolation test voltage 4000 V DC
Simultaneously active inputs All 16 up to 60 °C horizontal or 40 °C vertical
Input indication Green input-status LEDs
Interrupts and diagnostics No hardware interrupt, diagnostic alarm or diagnostic function
Front connection One 20-pin front connector
Dimensions 40 × 125 × 120 mm
Approximate weight 240 g
Frequently Asked Questions

Can I use different supply phases across the input groups of 6ES7321-1FH00-0AA0?

All load voltages must have the same phase.

Can I change the input-filter delay on 6ES7321-1FH00-0AA0?

The input delay is fixed at 25 ms and is not parameterizable.

Which front connector should I order for 6ES7321-1FH00-0AA0?

The module requires a 20-pin front connector.

Can 6ES7321-1FH00-0AA0 accept a two-wire sensor with 3 mA off-state current?

The permitted two-wire-sensor quiescent current is at most 2 mA.

Will 6ES7321-1FH00-0AA0 generate a hardware interrupt when an input changes?

The module does not provide hardware interrupts.

Is every channel on 6ES7321-1FH00-0AA0 isolated separately?

The input channels are isolated in groups of four rather than individually.

Can all channels on 6ES7321-1FH00-0AA0 remain active at 60 degrees Celsius?

All sixteen inputs may be active up to 60 °C in horizontal installation, while vertical installation is limited to 40 °C for that condition.

Compatibility & Ordering Notes
Before ordering 6ES7321-1FH00-0AA0: Match 120/230 V AC signals, maintain the same phase for all load voltages and select the required 20-pin front connector.

Before installation

  • Use the 120/230 V AC input variant for the intended field signals.
  • Keep every load voltage on the same phase.
  • Select the required 20-pin front connector and respect the grouped-isolation arrangement.
  • Account for the fixed 25 ms input delay and the absence of module interrupt and diagnostic functions.
Hot Selling Models
6RA3101-5DL00
DZF-32-40-APA
5SY6602-7
6FC5247-0AA02-0AA0
PSU300S 6EP1436-2BA10
01754 01754000
3LD1704-0TH51
40/0.03-4 604208
1461100 16DX
3031940
KBW-1 03100051 1-450-95-109-5
FBG31C-01 8222932.15
WAGO 757-303
110095 11-2015-BBOA
5SY4106-7 5ST3010

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop

Evolo Automation is not an authorized distributor unless otherwise specified, representative, or affiliate of the manufacturer of this product. All trademarks and documents are the property of their respective owners and are provided for identification and informational.