Siemens 6ES7321-1FF01-0AA0 S7-300 SM 321 Eight-Channel AC Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use rated 120/230 V AC field signals at 47–63 Hz.
- Maintain the paired channel-reference arrangement.
- Limit two-wire sensor quiescent current to 2 mA.
- Use a 20-pin front connector and preserve the required field wiring.
6ES7321-1FF01-0AA0 S7-300 SM 321 Eight-Channel AC Input Module
Eight AC input channels with a 20-pin front connector, paired isolation groups and a maximum 25 ms switching delay.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7321-1FF01-0AA0 |
| Product Type | AC digital input signal module |
| Core Function | Monitoring of mains-level switching signals |
| Application | SIMATIC S7-300 AC input installations |
AC field signals
The inputs are rated for 120/230 V AC at 47–63 Hz.
Paired references
The input isolation groups each contain two channels.
Input-state LEDs
Green indicators show the state of each input.
Product Overview
6ES7321-1FF01-0AA0 monitors eight AC field signals in a SIMATIC S7-300 station. The SM 321 uses IEC 61131 type-1 inputs and a 20-pin front connector for its rated 120/230 V AC wiring arrangement.
Each pair of input channels forms an isolation group, and optocouplers separate the inputs from the backplane. Switching delays can reach 25 ms, making the module suitable for ordinary AC contact monitoring rather than high-speed edge capture.
Key Functions
Acquire AC switching states
The module accepts rated 120/230 V AC inputs with a 47–63 Hz operating frequency.
Separate paired field circuits
Input channels are grouped in pairs, with optocoupler separation from the backplane.
Monitor normal AC contact operation
The maximum input delay is 25 ms for both switching-on and switching-off transitions.
Official Specifications
| Digital input channels | 8; IEC 61131 type 1 |
|---|---|
| Rated AC input | 120/230 V AC at 47–63 Hz |
| Logic voltage thresholds | Signal 0: 0–40 V; signal 1: 79–264 V |
| Typical signal-1 current | 6.5 mA at 120 V; 11 mA at 230 V |
| Maximum input delay | 25 ms on both transitions; not parameterizable |
| Simultaneously active inputs | 8 up to 60 °C horizontally or 40 °C vertically |
| Maximum two-wire sensor quiescent current | 2 mA |
| Maximum field-cable length | 1,000 m shielded; 600 m unshielded |
| Maximum 5 V backplane current | 29 mA |
| Typical power loss | 4.9 W |
| Isolation arrangement | Groups of 2 inputs; optocoupler separation from backplane |
| Insulation test voltage | 4,000 V DC |
| Required front connector | 20-pin |
| Indicators and alarms | Green input-state LEDs; no diagnostic or hardware-interrupt function |
| Dimensions and approximate weight | 40 × 125 × 120 mm (W × H × D); 240 g |
Frequently Asked Questions
Can a 24 V DC sensor drive an input of 6ES7321-1FF01-0AA0?
The module is intended for 120/230 V AC signals and its specified logic-1 voltage starts at 79 V.
Can all eight channels of 6ES7321-1FF01-0AA0 be active at 60 °C?
All eight inputs may be active up to 60 °C in the horizontal installation position.
How many channels share an isolation group on 6ES7321-1FF01-0AA0?
Each isolation group contains two input channels.
Can 6ES7321-1FF01-0AA0 reliably capture short pulses below its maximum input delay?
The input delay can reach 25 ms, so pulse timing must allow for that response.
Which front connector does 6ES7321-1FF01-0AA0 require?
Use the specified 20-pin front connector.
What off-state sensor current can 6ES7321-1FF01-0AA0 accept?
The maximum permissible quiescent current of a two-wire sensor is 2 mA.
Will 6ES7321-1FF01-0AA0 report a channel fault through an SF indicator?
The module provides green channel-state LEDs but no red SF group-error indicator or diagnostic function.