Siemens 6ES7288-1SR40-0AA0 SIMATIC S7-200 SMART CPU SR40 AC/DC/Relay Controller
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use STEP 7 Micro/WIN SMART and confirm the installed firmware for the required PROFINET role.
- Keep the AC controller supply separate from the 24 V DC input-signal wiring.
- Size relay loads and switching rates within the stated ratings.
- Budget the 300 mA sensor supply and the 1.4 A expansion-bus supply separately.
6ES7288-1SR40-0AA0 SIMATIC S7-200 SMART CPU SR40 AC/DC/Relay Controller
AC-powered CPU SR40 with 24 DC inputs, 16 relay outputs, separate 24 KB program and 16 KB data memory, Ethernet and RS 485 interfaces.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7288-1SR40-0AA0 |
| Product Type | Compact programmable controller |
| Core Function | Executing machine logic and managing local I/O |
| Application | Compact machine automation |
Integrated machine I/O
Twenty-four DC inputs and sixteen relay outputs support local switching and indication tasks.
Separate program and data storage
The CPU provides 24 KB for the user program and 16 KB for user data.
Network and serial communication
An RJ45 Ethernet interface and an RS 485 interface support connection to the wider control system.
Product Overview
6ES7288-1SR40-0AA0 combines an AC-powered controller with 24 integrated 24 V DC inputs and 16 relay outputs for compact machine-control installations.
STEP 7 Micro/WIN SMART supports the control program, while Ethernet and RS 485 provide communication paths and firmware-dependent PROFINET roles extend the network options.
Key Functions
Integrated machine I/O
Twenty-four DC inputs and sixteen relay outputs support local switching and indication tasks.
Separate program and data storage
The CPU provides 24 KB for the user program and 16 KB for user data.
Network and serial communication
An RJ45 Ethernet interface and an RS 485 interface support connection to the wider control system.
Official Specifications
| Controller supply | 85–264 V AC |
|---|---|
| Line frequency | 47–63 Hz |
| Input current | 190 mA rated at 240 V AC; 300 mA maximum at 120 V AC |
| Maximum power loss | 23 W |
| Integrated digital inputs | 24 inputs, 24 V DC, sourcing/sinking |
| Integrated digital outputs | 16 relay outputs |
| Resistive relay-load capacity | 2 A maximum |
| Relay switching response | 10 ms maximum on and off delay; 1 Hz maximum with resistive load |
| User memory | 24 KB program memory and 16 KB user-data memory |
| Sensor-power output | 24 V DC, 300 mA maximum |
| Expansion-bus supply | 5 V DC, 1.4 A maximum |
| Standard-input filtering | 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 12.8 ms, selectable in groups of four |
| Standard-input cable limits | 500 m shielded; 300 m unshielded |
| Output cable limits | 500 m shielded; 150 m unshielded |
| Ethernet interface | 1 RJ45, 10/100 Mbit/s, autonegotiation and autocrossing |
| Serial interface | 1 RS 485, up to 187.5 kbit/s |
| PROFINET roles | IO Controller from firmware V2.4, up to 8 IO Devices; I-Device from V2.5 |
| Real-time-clock backup | 7 days, battery-free hardware clock |
| Operating temperature | 0 to +55 °C horizontal; 0 to +45 °C vertical |
| Dimensions and approximate weight | 125 × 100 × 81 mm (W × H × D); 441.3 g |
Frequently Asked Questions
Can 6ES7288-1SR40-0AA0 use a 24 V DC supply at its controller-power terminals?
The controller-power supply is specified for 85–264 V AC.
Which engineering software should be used with 6ES7288-1SR40-0AA0?
Use STEP 7 Micro/WIN SMART to configure and program the CPU.
Are the outputs of 6ES7288-1SR40-0AA0 intended for rapid repetitive switching?
The relay-output switching limit with resistive loads is 1 Hz.
Which firmware is needed for PROFINET roles on 6ES7288-1SR40-0AA0?
The IO Controller role starts with firmware V2.4 and the I-Device role with V2.5.
How many PROFINET IO Devices can 6ES7288-1SR40-0AA0 control?
The maximum is eight connected IO Devices.
How much 24 V sensor current can 6ES7288-1SR40-0AA0 supply?
The integrated 24 V DC sensor-power output supplies up to 300 mA.
Does the 40 KB memory figure for 6ES7288-1SR40-0AA0 mean 40 KB of program storage?
The memory is divided into 24 KB for the program and 16 KB for user data.