- Use the module’s GSD in the PROFIBUS master configuration.
- Set a unique address between 0 and 99.
- Keep the bus segment within the length allowed for its baud rate.
- Supply 24 V DC within the permissible range and calculate the expansion-bus load.
- Match the V-memory offset and data lengths to the application program.
6ES7277-0AA22-0XA0 SIMATIC S7-200 EM 277 PROFIBUS DP Slave Module
An EM 277 communication module with automatic baud-rate detection, rotary address selection and isolated RS485 fieldbus access.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7277-0AA22-0XA0 |
| Product Type | PLC communication expansion module |
| Core Function | Exchanges PLC data with a fieldbus master |
| Application | S7-200 PROFIBUS DP and MPI networks |
PROFIBUS integration
Connects the S7-200 as a DP slave.
MPI access
Supports programming and operator-panel communication.
Local diagnostics
Power, bus-fault, CPU-error and data-exchange LEDs support commissioning.
Product Overview
6ES7277-0AA22-0XA0 adds a PROFIBUS DP slave and MPI slave interface to a compatible S7-200 controller.
The module exchanges process data through CPU V-memory buffers, detects the bus rate automatically and provides dedicated network status indications for setup and maintenance.
Key Functions
Cyclic fieldbus data transfer
The DP master configures the input and output buffer sizes and the V-memory offset used for the exchange.
Automatic line-speed selection
The RS485 port recognizes network rates from 9.6 kbit/s to 12 Mbit/s without a manual baud-rate setting.
Programming and HMI connections
Six MPI connections include one reserved programming connection and one reserved operator-panel connection.
Official Specifications
| External supply range | 24 V DC nominal; 20.4–28.8 V DC |
|---|---|
| External supply current | 30–180 mA depending on interface loading |
| Backplane-bus current | 150 mA maximum at 5 V DC |
| RS485 interface | 1 port |
| Transmission speeds | 9.6–500 kbit/s and 1–12 Mbit/s in the supported standard steps |
| Station address setting | 0–99 by rotary switches |
| Maximum stations per segment | 32 |
| Maximum stations per network | 126, including up to 99 EM 277 stations |
| MPI connection capacity | 6 total; 1 reserved for PG and 1 for OP |
| Maximum segment length at ≤93.75 kbit/s | 1200 m |
| Maximum segment length at 187.5 kbit/s | 1000 m |
| Maximum segment length at 500 kbit/s | 400 m |
| Maximum segment length at 1–1.5 Mbit/s | 200 m |
| Maximum segment length at 3–12 Mbit/s | 100 m |
| 5 V interface output | 90 mA maximum |
| 24 V interface output | 120 mA maximum |
| Typical power loss | 2.5 W |
| Isolation test | 500 V AC between external signals and control logic |
| Dimensions (W × H × D) | 71.2 × 80 × 62 mm |
| Approximate weight | 175 g |
Frequently Asked Questions
Can 6ES7277-0AA22-0XA0 act as the PROFIBUS master?
The module operates as a PROFIBUS DP slave or MPI slave and requires a separate master for DP operation.
Do I need to set the baud rate on 6ES7277-0AA22-0XA0?
The module automatically detects the supported fieldbus transmission rate.
How do I choose the network address for 6ES7277-0AA22-0XA0?
Set the station address from 0 to 99 using the module’s rotary switches.
Where does 6ES7277-0AA22-0XA0 exchange data with the CPU program?
The DP exchange uses configured input and output buffers in the S7-200 CPU’s V memory.
Can I connect both a programming device and an HMI through 6ES7277-0AA22-0XA0?
The six MPI connections include reserved connections for a programming device and an operator panel.
How long can a 12 Mbit/s segment connected to 6ES7277-0AA22-0XA0 be?
At rates from 3 to 12 Mbit/s, keep the segment within 100 m.
Can I change the DP buffer size by writing special memory from 6ES7277-0AA22-0XA0?
Configure the buffer sizes and V-memory location through the DP master configuration rather than writing the special-memory reporting fields.