Siemens 6ES7241-1CH31-0XB0 SIMATIC S7-1200 CM 1241 RS422/485 Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the female nine-pin D-sub interface pinout for the selected electrical mode.
- Provide external line termination.
- Match baud rate, parity and stop bits to the partner device.
- Include 240 mA in the CPU 5 V power budget.
- Choose cable length for the operating baud rate.
6ES7241-1CH31-0XB0 SIMATIC S7-1200 CM 1241 RS422/485 Module
A CM 1241 module with an RS422/485 port, a female nine-pin D-sub connector and configurable serial parameters.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7241-1CH31-0XB0 |
| Product Type | Serial communication module |
| Core Function | Exchanging serial device data |
| Application | Compatible S7-1200 CPU configurations |
Two electrical modes
The port operates as RS422 or RS485.
Flexible character format
Baud rate, parity and stop bits can be configured.
Isolated serial connection
The port isolation is tested at 500 V AC for one minute.
Product Overview
6ES7241-1CH31-0XB0 adds an RS422/485 communication port to a compatible S7-1200 controller. The nine-pin female D-sub interface supports the serial connection and Freeport application.
The module is supplied from the CPU 5 V bus. Configurable internal bias options do not remove the requirement for external line termination, and the maximum shielded cable length depends on the baud rate.
Key Functions
Connect the serial device
The port supports RS422 and RS485 electrical operation through the nine-pin female D-sub connector.
Set the serial frame
Configurable speed, parity and stop bits adapt the port to the partner device.
Coordinate transmission
RS422 supports XON/XOFF flow control and the RTS output indicates active transmission.
Official Specifications
| Port electrical modes | RS422 or RS485 |
|---|---|
| Connector | 9-pin D-sub female |
| Selectable baud rates | 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800 or 115200 bit/s; default 9600 bit/s |
| Parity settings | None, even, odd, mark or space; default none |
| Stop bits | 1 or 2; default 1 |
| Common-mode voltage | −7 to +12 V for 1 s; 3 V RMS continuous |
| Minimum differential transmit voltage | 2 V at 100 Ω load; 1.5 V at 54 Ω load |
| Optional internal bias | 10 kΩ to +5 V on B/pin 3 and 10 kΩ to ground on A/pin 8 |
| Minimum receiver input impedance | 5.4 kΩ including termination |
| Receiver threshold and hysteresis | ±0.2 V minimum threshold; 60 mV typical hysteresis |
| Isolation test | 500 V AC for 1 minute, serial signals to chassis ground and CPU logic common |
| Maximum shielded cable length | 1000 m, depending on baud rate |
| Flow control | XON/XOFF in RS422 mode |
| Wait-time range | 0–65535 ms |
| 5 V bus consumption | 240 mA |
| Power dissipation | 1.2 W |
| Dimensions | 30 × 100 × 75 mm (W × H × D) |
| Approximate weight | 155 g |
Frequently Asked Questions
Does the internal bias of 6ES7241-1CH31-0XB0 remove the need for line termination?
External termination is required even when an internal bias option is selected.
Which pins of 6ES7241-1CH31-0XB0 are used only for RS422 transmission?
Pins 2 and 9 carry the dedicated RS422 transmit signals and are not used for RS485.
What serial settings does 6ES7241-1CH31-0XB0 use by default?
The default settings are 9600 bit/s, no parity and one stop bit.
Can I use XON/XOFF flow control with 6ES7241-1CH31-0XB0?
XON/XOFF flow control is supported in RS422 mode.
Is the 1000 m cable limit of 6ES7241-1CH31-0XB0 valid at every baud rate?
The maximum shielded cable length is 1000 m and depends on the selected baud rate.
How is 6ES7241-1CH31-0XB0 powered by the controller?
The module draws 240 mA from the CPU 5 V DC bus.
What does the RTS output of 6ES7241-1CH31-0XB0 indicate?
The TTL-level RTS signal is active during transmission and inactive at other times.