Siemens 6ES7235-0KD22-0XA0 S7-200 EM 235 Analog I/O Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Keep signal plus common-mode voltage within ±12 V.
- Use 0–20 mA for the current input or output range.
- Retain the 5 kΩ minimum voltage-output load or 500 Ω maximum current-output load.
- Provide the required external 24 V supply and backplane current.
6ES7235-0KD22-0XA0 S7-200 EM 235 Analog I/O Module
Four differential analog inputs and one analog output combine selectable voltage or current measurement with a bipolar voltage or unipolar current setpoint.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7235-0KD22-0XA0 |
| Product Type | Combined analog I/O module |
| Core Function | Analog measurement and setpoint output |
| Application | CPU 22x process-signal expansion |
Four differential inputs
Supports voltage ranges down to millivolt signals and a 0–20 mA current range.
One analog output
Provides ±10 V or 0–20 mA output operation.
Load matching
Voltage loads require at least 5 kΩ; current loads may be up to 500 Ω.
Product Overview
6ES7235-0KD22-0XA0 adds four differential analog inputs and one analog output to a SIMATIC S7-200 CPU 22x system. Selectable input ranges support both small voltage signals and standard process-current signals.
The output provides either a ±10 V voltage signal or a 0–20 mA current signal. Its voltage and current settling times differ, so both the load impedance and the required response should be considered when connecting a control element.
Key Functions
Measure differential process signals
Four differential channels support selectable unipolar and bipolar voltage ranges plus a 0–20 mA current range.
Generate a control setpoint
The single analog output supplies ±10 V into a load of at least 5 kΩ or 0–20 mA into a load up to 500 Ω.
Convert and scale analog values
Input conversion takes less than 0.25 ms, with unipolar data represented from 0 to 32000 and bipolar data from −32000 to +32000.
Official Specifications
| Analog channel arrangement | 4 differential inputs and 1 output |
|---|---|
| Unipolar voltage input ranges | 0–50 mV, 0–100 mV, 0–500 mV, 0–1 V, 0–5 V and 0–10 V |
| Bipolar voltage input ranges | ±25 mV, ±50 mV, ±100 mV, ±250 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V and ±10 V |
| Current input range | 0–20 mA |
| Input conversion resolution | 12 bits maximum; bipolar format uses 11 bits plus sign |
| Input conversion time | Less than 0.25 ms per channel |
| Input impedance | At least 2 MΩ for voltage; 250 Ω for current |
| Input destruction limits | 30 V maximum voltage; 32 mA maximum current |
| Permissible common-mode condition | Signal voltage plus common-mode voltage within ±12 V |
| Output ranges | ±10 V or 0–20 mA |
| Output resolution | 11 bits |
| Output load impedance | Voltage: at least 5 kΩ; current: no more than 500 Ω |
| Output settling time | 100 µs for voltage; 2 ms for current |
| Output accuracy | Typical ±0.5% of full scale at 25 °C; worst case ±2% over 0–55 °C |
| Analog data representation | Bipolar: −32000 to +32000; unipolar: 0–32000 |
| Supply-current requirements | 60 mA maximum from external 24 V DC; 30 mA maximum from the 5 V backplane |
| Electrical isolation | No field-to-logic isolation for analog inputs or outputs |
| Dimensions and weight | 71.2 × 80 × 62 mm (W × H × D); approximately 186 g |
Frequently Asked Questions
Can 6ES7235-0KD22-0XA0 measure a low-level ±50 mV signal?
The selectable bipolar voltage input ranges include ±50 mV.
Can I connect a thermocouple directly to 6ES7235-0KD22-0XA0 for temperature conversion?
The module supports voltage and current ranges but does not provide thermocouple or resistance-temperature measurement functions.
What input impedance should I use when sizing a current loop for 6ES7235-0KD22-0XA0?
The current input impedance is 250 Ω.
Will a 2 kΩ voltage-output load suit 6ES7235-0KD22-0XA0?
The voltage output requires a load impedance of at least 5 kΩ.
How quickly does the current output of 6ES7235-0KD22-0XA0 settle?
The current output settling time is 2 ms.
How should I scale a negative voltage reading from 6ES7235-0KD22-0XA0?
Bipolar analog values use the full-scale data range from −32000 to +32000.
Are the analog field circuits on 6ES7235-0KD22-0XA0 isolated from the controller logic?
The analog inputs and analog output do not have field-to-logic isolation.