Siemens 6ES7194-4AJ00-0AA0 ET 200pro CM IM PN M12 7/8 Connection Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use with the ET 200pro IM 154-4 PN High Feature interface module.
- Prepare the two M12 PROFINET cable paths and the correctly gendered 7/8-inch power cables.
- Keep each incoming 1L+ and 2L+ circuit within the 8 A feed limit.
- Limit internal transfer to 5 A on 1L+ and 8 A on 2L+ for this connector.
- Account separately for station consumption and any supply forwarded to the next station.
6ES7194-4AJ00-0AA0 ET 200pro CM IM PN M12 7/8 Connection Module
A PROFINET connection module with two M12 network sockets and two 7/8-inch power connections for ET 200pro.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7194-4AJ00-0AA0 |
| Product Type | CM IM PN M12, 7/8 connection module |
| Core Function | Connects PROFINET and station power |
| Application | ET 200pro IM 154-4 PN High Feature |
PROFINET connections
Two M12 sockets provide the network feed and forwarding connections.
Power feed and forwarding
A 7/8-inch inlet and outlet carry the 1L+ and 2L+ supply circuits.
IM 154-4 PN attachment
The module plugs into the High Feature interface module and is secured with screws.
Product Overview
6ES7194-4AJ00-0AA0 provides the circular PROFINET and power connections for an ET 200pro IM 154-4 PN High Feature interface module.
Two M12 sockets provide the PROFINET feed and forwarding paths, while the two 7/8-inch connections carry the electronic/encoder and load supplies for the station and onward power distribution.
Key Functions
PROFINET network feed and forwarding
The two M12 sockets connect the PROFINET IO cable paths at the interface-module end of the ET 200pro station.
Separate 1L+ and 2L+ power circuits
The 7/8-inch power connections carry the electronics/encoder supply and load supply, with an incoming plug insert and an outgoing socket insert.
Station and cable identification
Four inscription labels identify the module connections, and the plug-and-screw attachment secures the connector directly to the interface module.
Official Specifications
| PROFINET Connections | 2 × M12 sockets for feed and forwarding |
|---|---|
| Power Connections | 2 × 7/8-inch connections for 1L+ and 2L+ |
| Power-feed Connector Insert | Pin insert |
| Power-forwarding Connector Insert | Socket insert |
| Maximum Supply Feed Current | 8 A each for 1L+ and 2L+ |
| Maximum Internal 1L+ Transfer | 5 A |
| Maximum Internal 2L+ Transfer | 8 A |
| Mechanical Attachment | Plug-in connection secured by screws |
| Inscription Labels | 4 |
| Dimensions (W × H × D) | 90 × 130 × 51 mm |
| Approximate Weight | 540 g |
Frequently Asked Questions
Which interface module accepts 6ES7194-4AJ00-0AA0?
The connector plugs into and screws onto the ET 200pro IM 154-4 PN High Feature interface module.
Can I loop PROFINET through the two M12 connections on 6ES7194-4AJ00-0AA0?
The two M12 sockets provide PROFINET feed and forwarding connections.
How do I identify the power inlet and outlet on 6ES7194-4AJ00-0AA0?
The incoming 7/8-inch connection has a pin insert and the forwarding connection has a socket insert.
Can the complete 8 A 1L+ feed of 6ES7194-4AJ00-0AA0 be used inside the station?
The internal 1L+ transfer is limited to 5 A, so the feed rating must be distinguished from the station’s internal current limit.
What internal 2L+ current limit applies to 6ES7194-4AJ00-0AA0?
The internal load-supply transfer is limited to 8 A for this connection module.
Does 6ES7194-4AJ00-0AA0 replace the PM-E direct-wiring connector for a separate load group?
This connector attaches to the PROFINET interface module, while a separate PM-E load group uses its matching power-module connector.
What labeling provision is available on 6ES7194-4AJ00-0AA0?
Four inscription labels are provided for identifying the connections.