Siemens 6ES7194-1AA01-0XA0 ET 200X PROFIBUS and Power Connection Plug
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Match the ET 200X or ASM 450/452 socket and its PROFIBUS or power-connection duty.
- Allow three plugs per ASM where the complete ASM connection set is required.
- Use cables with 4–10 mm outside diameter and the permitted conductor cross-sections.
- Prepare 45 mm sheath stripping and 6 mm core stripping lengths.
- Clamp the sheath correctly in the M16 gland and fully latch the insert in the protective shell.
- Close unused station connections with the appropriate protective cover.
6ES7194-1AA01-0XA0 ET 200X PROFIBUS and Power Connection Plug
An IP65 connection-plug assembly with a six-pin insert and metric M16 cable glands for compatible PROFIBUS DP and 24 V supply connections.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7194-1AA01-0XA0 |
| Product Type | Field connection plug assembly |
| Core Function | Terminates PROFIBUS DP and supply wiring at compatible station connections |
| Application | ET 200X station and ASM 450/452 field connections |
Six-pin connection insert
The connector insert is wired for the assigned bus or power connection.
Metric cable entries
The assembly includes two M16 cable glands with matching lock nuts.
Field-service assembly
The wired connector snaps into its protective shell using locking hooks.
Product Overview
6ES7194-1AA01-0XA0 provides the field connector assembly used for compatible ET 200X PROFIBUS DP, electronics/sensor supply and load-voltage connections.
The protective shell contains a six-pin connector insert with metric cable-entry hardware; it is also assigned as the PROFIBUS and 24 V power connection plug for the ASM 450/452 identification interfaces.
Key Functions
PROFIBUS and supply termination
The six-pin insert is wired to the assigned PROFIBUS DP or 24 V supply connection rather than using a universal pin assignment for every socket.
Sealed cable entry
M16 cable glands clamp the cable sheath at the protective shell and support the specified assembled protection.
Maintainable connector construction
The wired insert snaps into the shell, while the locking hooks can be released to remove the insert during service.
Official Specifications
| Connector insert | Six pins |
|---|---|
| Cable-entry hardware | Two M16 cable glands and two lock nuts |
| Protection degree | IP65 |
| Approximate weight | 10 g |
| Permitted cable outside diameter | 4–10 mm |
| Flexible conductor with ferrule | 0.25–1.5 mm² |
| Flexible conductor without ferrule | 0.25–2.5 mm² |
| Conductors per terminal | One core, or two cores totalling up to 1.5 mm² in a common ferrule |
| Core stripping length | 6 mm |
| Cable sheath stripping length | 45 mm |
| Ferrules without insulating collar | DIN 46228 Form A, up to 7 mm long |
| Ferrules with insulating collar | DIN 46228 Form E, up to 8 mm long |
Frequently Asked Questions
How many pieces of 6ES7194-1AA01-0XA0 are required for an ASM 450 installation?
Three connection plugs are required per ASM, rather than treating one plug as the complete station connection set.
Which cable entries are included with 6ES7194-1AA01-0XA0?
The connector assembly includes two M16 cable glands and two lock nuts.
What cable outside diameter can be clamped in 6ES7194-1AA01-0XA0?
The permissible cable outside diameter is 4–10 mm.
How much insulation should be stripped before wiring 6ES7194-1AA01-0XA0?
Strip 6 mm from each core and 45 mm from the cable sheath.
Which flexible conductor sizes can be used with ferrules in 6ES7194-1AA01-0XA0?
Flexible conductors with wire-end ferrules may have a cross-section of 0.25–1.5 mm².
Can PROFIBUS and supply connectors using 6ES7194-1AA01-0XA0 be wired with the same pin assignment?
Use the pin assignment for the actual station socket, because PROFIBUS and supply or load-voltage connections have different wiring duties.
How is the wired insert removed from the protective shell of 6ES7194-1AA01-0XA0?
Release the two locking hooks with a pointed implement and withdraw the connector insert from the shell.