Siemens 6ES7193-7CA00-0AA0 ET 200iSP TM-EM/EM 60S Terminal Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use TM-EM/EM for its permitted digital or analog electronic modules, with two positions per terminal section.
- Select the separate TM-RM/RM base for relay electronics that require it.
- Keep blue-terminal and black-terminal station variants separate.
- Provide the corresponding enclosure for Zone 21 installation and apply the system’s certified intrinsically safe circuit design.
- Prepare field conductors and ferrules to the stated cross-sections, 11 mm stripping length and 0.5–0.7 N·m torque.
6ES7193-7CA00-0AA0 ET 200iSP TM-EM/EM 60S Terminal Module
A 60 mm screw-terminal module with two electronic-module positions and 32 field terminals for ET 200iSP stations.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7193-7CA00-0AA0 |
| Product Type | TM-EM/EM 60S terminal module |
| Core Function | Connects field wiring to electronic modules |
| Application | ET 200iSP distributed I/O stations |
Two module positions
Two electronic modules share one 60 mm terminal-module section.
Screw connections
Field wiring is connected through 32 terminals arranged as 8 × 4.
Prewired station base
The module can be wired before the electronic modules are fitted.
Product Overview
6ES7193-7CA00-0AA0 provides the screw-terminal field-wiring base for two ET 200iSP electronic modules, with separate power-bus and backplane-bus connections.
Its 60 mm wide body includes 32 field terminals and a spring contact to the mounting rail for interference discharge, allowing terminal prewiring before the I/O electronics are installed.
Key Functions
Two-slot electronic-module support
The terminal section accommodates two digital or analog I/O electronic modules and makes their field connections accessible at the front of the station.
Screw-terminal prewiring
Field conductors can be terminated before fitting the electronic modules, using 11 mm stripping length and the specified screw tightening torque.
Integrated power and backplane path
The terminal module carries the station power bus and backplane bus, while a spring contact provides interference discharge to the mounting rail.
Official Specifications
| Electronic-module Positions | 2 slots |
|---|---|
| Field Terminal Arrangement | 32 terminals, arranged as 8 × 4 |
| Connection Technology | Screw terminals |
| DC Input and Output Voltage Range | 20.4–28.8 V DC |
| Maximum DC Input and Output Current | 4 A |
| Solid and Unferruled Flexible Conductors | 0.14–2.5 mm² |
| Flexible Conductors with Ferrules | 0.14–1.5 mm² |
| Conductor Stripping Length | 11 mm |
| Terminal Tightening Torque | 0.5–0.7 N·m |
| Mounting Method | Rail mounting |
| Interference Discharge Connection | Spring contact to the mounting rail |
| ATEX Certificate | KEMA 04 ATEX 2242 |
| IECEx Certificate | IECEx KEM 05.0003 |
| Dimensions (W × H × D) | 60 × 190 × 52 mm |
| Approximate Weight | 275 g |
Frequently Asked Questions
Can I prewire 6ES7193-7CA00-0AA0 before the electronic modules are installed?
The terminal module can be prewired before its two electronic modules are fitted.
Which termination tool should I use on 6ES7193-7CA00-0AA0?
Use a screwdriver with a 3.5 mm blade to secure the screw-terminal field conductors.
How much insulation should I strip for 6ES7193-7CA00-0AA0?
Strip the conductor insulation to a length of 11 mm.
What changes when ferrules are fitted to conductors for 6ES7193-7CA00-0AA0?
The maximum cross-section is reduced from 2.5 mm² for unferruled conductors to 1.5 mm² for flexible conductors with ferrules.
Can I fit a 2DO relay UC60V/2A module to 6ES7193-7CA00-0AA0?
The relay electronics require the dedicated TM-RM/RM terminal module rather than the TM-EM/EM arrangement.
Can 6ES7193-7CA00-0AA0 be mixed with black-terminal modules in one ET 200iSP station?
Blue-terminal and black-terminal versions must not be combined within the same station.
What torque should I apply when wiring 6ES7193-7CA00-0AA0?
Tighten the screw terminals to 0.5–0.7 N·m.