Siemens 6ES7193-6BP60-0DA0 SIMATIC ET 200SP 2BU15-P16+A0+2DB Double BaseUnit
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use I/O modules requiring BaseUnit type A0 or A1 in the two positions.
- Keep the light side as the new-group infeed and the dark side as its continuation.
- Sum module and external-load consumption within the 10 A group limit.
- Limit individual process terminals to 2 A.
- Use the specified 24 V DC, 10 A type B or C supply protection.
- For the manufacturer-listed replacement arrangement, use one 0DA0 and one 0BA0 single BaseUnit.
6ES7193-6BP60-0DA0 SIMATIC ET 200SP 2BU15-P16+A0+2DB Double BaseUnit
A two-position A0 BaseUnit combining a light infeed side and dark continuation side, with two sets of sixteen process terminals and no external AUX terminal access.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7193-6BP60-0DA0 |
| Product Type | Light-dark double BaseUnit |
| Core Function | Starting and extending one potential group across two positions |
| Application | ET 200SP modules requiring BaseUnit type A0 or A1 |
One group across two positions
The light side starts the potential group and the dark side continues it.
Two 15 mm module slots
The double base provides a combined 30 mm width.
Shared current budget
Module consumption and connected loads together must remain within 10 A.
Product Overview
6ES7193-6BP60-0DA0 combines a light-colored infeed BaseUnit and a dark-colored continuation BaseUnit in one two-position ET 200SP assembly.
Its light side interrupts P1, P2 and AUX from the preceding position to start a new potential group, while the dark side connects those buses onward within the double base.
Key Functions
Start a new group at the light side
The light side interrupts the voltage and AUX buses to the left and provides the new group’s 24 V DC infeed.
Continue the group through the second position
The dark side joins its P1, P2 and AUX buses to the light side, so both installed I/O modules share the same potential group.
Provide push-in wiring for both I/O modules
Each position has sixteen process terminals assigned by its I/O module and its own L+/M terminal pair, with no external AUX access.
Official Specifications
| Rated Supply Voltage | 24 V DC |
|---|---|
| Maximum P1/P2 Bus Current | 10 A |
| Maximum Process-Terminal Current | 2 A |
| Module Positions | 2 positions, each 15 mm wide |
| Process-Terminal Arrangement | 2 × 16 terminals |
| Supply-Terminal Arrangement | L+ and M present for each position |
| Terminal Construction | Push-in |
| External AUX and Add-On Terminals | No external AUX or add-on terminal access |
| Integrated Mains Filter | Provided on the infeed arrangement |
| Insulation Type-Test Voltage | 707 V DC |
| Conductor Cross-Section | 0.14–2.5 mm²; AWG 26–14 |
| Baseline Horizontal Operating Temperature | 0 to +60 °C |
| Baseline Vertical Operating Temperature | 0 to +50 °C |
| Standard Installation Altitude | Up to 2000 m above sea level |
| Process Color-Coding Range | CC00 to CC09 |
| Dimensions (Width × Height × Depth) | 30 × 117 × 35 mm |
| Approximate Weight | 80 g |
Frequently Asked Questions
Can I use the two positions of 6ES7193-6BP60-0DA0 as two independent potential groups?
The light side starts one group and the dark side continues that same group.
Does 6ES7193-6BP60-0DA0 keep the supply buses connected to the BaseUnit on its left?
The light side interrupts P1, P2 and AUX to the preceding BaseUnit or interface module.
How do I calculate the 10 A load budget for 6ES7193-6BP60-0DA0?
Add the consumption of every I/O module in the potential group to the demand of all external loads supplied by that group.
Can I connect an AUX field wire directly to 6ES7193-6BP60-0DA0?
The AUX bus is carried internally but has no external terminal access on this version.
Which individual bases make up the arrangement of 6ES7193-6BP60-0DA0?
The arrangement combines a 6ES7193-6BP00-0DA0 light BaseUnit with a 6ES7193-6BP00-0BA0 dark BaseUnit.
Which protective device should feed the supply lines of 6ES7193-6BP60-0DA0?
Use a 24 V DC, 10 A miniature circuit breaker with type B or C tripping characteristic.
How much horizontal rail space do I need for 6ES7193-6BP60-0DA0?
The complete double BaseUnit occupies 30 mm of width for its two module positions.