Siemens 6ES7193-6BP20-0BA0 SIMATIC ET 200SP BU15-P16+A10+2B BaseUnit
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use a compatible I/O module with the required A0/A1 BaseUnit interface.
- Treat the ten AUX connections as a separate bus rather than I/O signal contacts.
- Keep AUX at no more than 24 V DC and 10 A and process terminals at no more than 2 A.
- Reserve 15 × 141 × 35 mm for the BaseUnit.
- Use the specified supply protection and suitable process and AUX color-coding labels.
- Apply installation-position temperature limits and altitude restrictions.
6ES7193-6BP20-0BA0 SIMATIC ET 200SP BU15-P16+A10+2B BaseUnit
A dark-colored push-in BaseUnit with sixteen process terminals, ten accessible AUX terminals and continued P1, P2 and AUX buses from the adjacent position.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7193-6BP20-0BA0 |
| Product Type | A0 BaseUnit with AUX terminals |
| Core Function | Continuing the potential group and providing auxiliary connections |
| Application | ET 200SP I/O modules requiring BU type A0 or A1 |
Ten AUX terminals
The auxiliary row provides a protective-conductor or separate potential connection.
Independent AUX bus
The AUX bus is not connected to the plugged I/O module.
141 mm height
The additional terminal row increases the base height to 141 mm.
Product Overview
6ES7193-6BP20-0BA0 provides the BU15-P16+A10+2B wiring base for ET 200SP, extending the existing potential group while making ten AUX terminal connections available.
The process signals follow the inserted I/O module, while the separate AUX bus can be used for a protective conductor or a potential within its 24 V DC and 10 A limits.
Key Functions
Expose the auxiliary connection row
Ten AUX terminals provide access to the auxiliary bus for a protective conductor or freely assigned potential up to 24 V DC.
Keep auxiliary and process wiring distinct
The AUX bus is not connected to the I/O module, and the installed module determines the assignment of the sixteen process terminals.
Continue the existing group across the station
P1, P2 and AUX connect to the neighboring BaseUnit on the left, preserving the potential group through the dark-colored base.
Official Specifications
| Rated DC Supply | 24 V DC |
|---|---|
| Maximum P1/P2 and AUX Bus Current | 10 A |
| Maximum Process-Terminal Current | 2 A |
| Process-Terminal Count | 16 |
| AUX-Terminal Count and Rating | 10 terminals; maximum 24 V DC and 10 A |
| Supply-Bus Terminals | 2 terminals connected to P1/P2 |
| Field-Terminal Construction | Push-in |
| AUX-to-I/O Connection | AUX bus not connected to the I/O module |
| Insulation Type-Test Voltage | 707 V DC |
| Conductor Cross-Section | 0.14–2.5 mm²; AWG 26–14 |
| Horizontal Operating Temperature | −30 to +60 °C |
| Vertical Operating Temperature | −30 to +50 °C |
| Maximum Installation Altitude | 5000 m; restrictions apply above 2000 m |
| Minimum Dew Point | −60 °C; suitable for dry-room applications |
| Color-Coding Labels | CC00–CC09 for process terminals; CC71–CC73 for AUX terminals |
| Dimensions (Width × Height × Depth) | 15 × 141 × 35 mm |
| Approximate Weight | 50 g |
Frequently Asked Questions
Can the AUX row of 6ES7193-6BP20-0BA0 supply a signal directly to the electronic module?
The AUX bus is separate from the I/O module and does not connect directly to its signal contacts.
Can I use the ten AUX points on 6ES7193-6BP20-0BA0 for a protective conductor?
The AUX terminals can be used for a protective-conductor connection or a potential up to 24 V DC.
Which AUX current limit applies when wiring 6ES7193-6BP20-0BA0?
Keep the auxiliary bus current within its 10 A maximum.
Will 6ES7193-6BP20-0BA0 fit the same 117 mm-high wiring space as a base without AUX terminals?
This AUX-terminal version is 141 mm high, so it needs additional vertical space.
Which identification labels fit the AUX row of 6ES7193-6BP20-0BA0?
The AUX terminal row uses color-coding labels CC71 to CC73.
Can 6ES7193-6BP20-0BA0 be used to isolate a new potential group from the preceding position?
This dark-colored base continues P1, P2 and AUX from the BaseUnit to its left.
Which supply-line protection is required for 6ES7193-6BP20-0BA0?
Use a 24 V DC, 10 A miniature circuit breaker with type B or C tripping characteristic.