Siemens 6ES7151-7AA10-0AB0 SIMATIC ET 200S IM151-7 CPU Interface Controller
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Fit a compatible MMC and keep the program within the fixed CPU work-memory capacity.
- Use the integrated interface in its supported MPI or DP slave role.
- Place the optional 6ES7138-4HA00-0AB0 master module directly to the right of the CPU when required.
- Use STEP 7 V5.1 SP6 or higher for the CPU, or V5.2 SP1 or higher with the master module.
6ES7151-7AA10-0AB0 SIMATIC ET 200S IM151-7 CPU Interface Controller
An IM151-7 CPU with fixed work memory, MMC load memory and an optional separate interface for PROFIBUS master operation.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7151-7AA10-0AB0 |
| Product Type | Distributed station CPU |
| Core Function | Executing local station control |
| Application | ET 200S programmable I/O stations |
Local programmable control
The CPU executes logic, word and arithmetic operations for its ET 200S station.
Separate bus-role expansion
A DP master module can be fitted beside the CPU in addition to the integrated DP slave interface.
Battery-free program storage
A compatible MMC supplies load memory and maintenance-free retention.
Product Overview
6ES7151-7AA10-0AB0 executes local ET 200S control logic while exchanging data through its integrated PROFIBUS slave interface.
Maintenance-free MMC storage replaces a backup battery, and the optional DP master module adds a second bus role without increasing the fixed CPU work memory.
Key Functions
Local programmable control
The CPU executes logic, word and arithmetic operations for its ET 200S station.
Separate bus-role expansion
A DP master module can be fitted beside the CPU in addition to the integrated DP slave interface.
Battery-free program storage
A compatible MMC supplies load memory and maintenance-free retention.
Official Specifications
| CPU supply | 24 V DC; permissible range 20.4–28.8 V |
|---|---|
| Maximum 1L+ current | 250 mA; 280 mA with DP master module |
| Backplane output current | Maximum 700 mA at 5 V DC |
| Typical dissipation | 3.3 W |
| Integrated work memory | 48 kB, not expandable |
| MMC load memory | Up to 8 MB; minimum ten-year data retention after programming |
| Typical bit operation | 0.1 µs |
| Typical word operation | 0.2 µs |
| Typical fixed-point arithmetic | 2 µs |
| Typical floating-point arithmetic | 6 µs |
| Counter and timer resources | 256 S7 counters and 256 S7 timers |
| Flag memory | 256 bytes |
| Process image | 128 input bytes and 128 output bytes; not adjustable |
| Block capacity | 1,024 FC, FB and DB elements in total; block size up to 16 kB |
| Integrated serial interface | Isolated RS485, 9-pin D-sub female; MPI or DP slave up to 12 Mbit/s |
| DP slave transfer memory | 244 input bytes and 244 output bytes; up to 32 address areas |
| CPU communication connections | 12 total across the CPU |
| Real-time clock | Typical six-week reserve at 40 °C; maximum deviation 10 s per day |
| Isolation test level | 500 V DC |
| CPU dimensions and approximate mass | 60 × 119.5 × 75 mm; 200 g |
Frequently Asked Questions
Can a larger MMC increase the work memory of 6ES7151-7AA10-0AB0?
The integrated 48 kB work memory is fixed even when a larger supported MMC is fitted.
Can the integrated bus connector of 6ES7151-7AA10-0AB0 operate as a DP master?
The integrated interface is a DP slave and master operation requires the separate DP master module.
Where is the optional master interface installed beside 6ES7151-7AA10-0AB0?
The DP master module is installed immediately to the right of the CPU at its X2 interface.
Does 6ES7151-7AA10-0AB0 need a backup battery to retain its stored program?
Program retention is maintained by the MMC without a backup battery.
Which STEP 7 release is needed when 6ES7151-7AA10-0AB0 uses the DP master module?
That configuration requires STEP 7 V5.2 SP1 or higher.
How many DP devices can the optional master arrangement of 6ES7151-7AA10-0AB0 serve?
The external master interface supports up to 32 DP devices per station.
Do two interfaces on 6ES7151-7AA10-0AB0 each provide twelve communication connections?
The twelve-connection limit applies to the CPU as a whole rather than separately to each interface.