Siemens 6ES7147-5JD00-0BA0 SIMATIC ET 200AL CM 4xIO-Link 4xM12
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Allocate 132 input bytes and 128 output bytes when using the full module data range.
- Keep sensor and additional-device currents within their separate total limits.
- Use the required GSD revision 5 or GSDML V2.3.1 where GSD engineering is used.
- Plan master backup and device parameter handling before replacing the module.
SIEMENS SIMATIC ET 200AL
6ES7147-5JD00-0BA0 SIMATIC ET 200AL CM 4xIO-Link 4xM12
Connect four IO-Link devices through M12 ports and integrate their process data, parameters and diagnostics into an ET 200AL station.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7147-5JD00-0BA0 |
| Product Type | IO-Link communication module |
| Core Function | Connect intelligent field devices |
| Application | ET 200AL distributed I/O stations |
Four field-device ports
Each M12 port supports IO-Link operation and configurable standard I/O modes.
Separate supply groups
1L+ powers the electronics and sensors, while 2L+ supplies the additional device circuit.
Device parameter storage
Parameter memory and master backup support device and module replacement.
Product Overview
6ES7147-5JD00-0BA0 expands an ET 200AL station with four IO-Link master ports for intelligent sensors and actuators. IO-Link V1.0 and V1.1 devices communicate at COM1, COM2 or COM3 speeds through the same field connection format.
The module exchanges up to 32 bytes of input and 32 bytes of output process data per port, stores device parameters and provides configurable diagnostics for the supply and field connections.
Key Functions
Integrate IO-Link process and diagnostic data
Four simultaneously controllable ports support IO-Link communications and configurable digital input or output operation.
Restore field-device parameters
Device parameter memory of 2 kbytes per port and the IO_LINK_MASTER function block support parameter backup for service tasks.
Build distributed field wiring
M12 field sockets and M8 supply and ET-Connection interfaces suit compact station wiring with an unshielded IO-Link cable length up to 20 m.
Official Specifications
| IO-Link Port Capacity | 4 simultaneously controllable ports; IO-Link V1.0 and V1.1 |
|---|---|
| Communication Speeds | 4.8 kbaud COM1; 38.4 kbaud COM2; 230 kbaud COM3 |
| Process Data per Port | 32 bytes input and 32 bytes output |
| Module Process-Data Size | 132 bytes input and 128 bytes output |
| Device Parameter Memory | 2 kbytes per port |
| Nominal Supply and Permitted Range | 1L+ and 2L+: 24 V DC, 20.4 to 28.8 V DC |
| No-Load Current | 40 mA |
| Maximum Supply Current | 4 A from 1L+ and 4 A from 2L+ |
| Sensor-Supply Current | Maximum 1.4 A total across all ports |
| Port B Additional Supply | Maximum 1.6 A total across all ports |
| Standard Digital Output Rating | Maximum 100 mA per configured DQ |
| Typical Power Dissipation | 2.6 W |
| Maximum IO-Link Cable Length | 20 m, unshielded |
| Field and Supply Connections | 5-pole M12 I/O; 4-pole M8 supply; shielded 4-pin M8 ET-Connection |
| Operating Ambient Temperature | −30 to +55 °C |
| Isolation Type-Test Voltage | 707 V DC |
| Housing Dimensions | 30 × 159 × 40 mm (W × H × D) |
| Approximate Weight | 145 g |
Frequently Asked Questions
Can 6ES7147-5JD00-0BA0 connect IO-Link V1.0 and V1.1 sensors in one station?
Yes, the master supports both protocol versions and provides four independently usable ports.
Does 6ES7147-5JD00-0BA0 support Separate supply groups for mobile equipment?
The maximum permitted unshielded cable length between the module and an IO-Link device is 20 m.
Can I configure a port of 6ES7147-5JD00-0BA0 as an ordinary digital output?
Yes, a port can operate in DQ mode with a maximum output current of 100 mA.
How much process data should I reserve per port on 6ES7147-5JD00-0BA0?
Each port supports up to 32 bytes of input and 32 bytes of output process data.
Which STEP 7 versions can configure 6ES7147-5JD00-0BA0?
Configuration is available from TIA Portal V13 SP1 or STEP 7 V5.5 SP4 Hotfix 3.
How can I back up the master configuration before replacing 6ES7147-5JD00-0BA0?
Use the IO_LINK_MASTER function block to back up the master parameters.
What supply limit applies when connecting Port B devices to 6ES7147-5JD00-0BA0?
The additional device supply for Port B connections is limited to a total current of 1.6 A across all ports.