- Plan separate 1L+ and 2L+ load circuits and calculate each four-ampere group budget.
- Match five-pole M12 actuator cables and the specified M8 power and ET-Connection interfaces.
- Configure substitute values and diagnostic alarms for the required machine response.
- Preserve connector sealing and apply the ambient and high-altitude installation limits.
6ES7142-5AF00-0BA0 SIMATIC ET 200AL DQ 8x24VDC/2A Module
ET 200AL output module with eight M12 connections, two four-channel load groups and separate 1L+ and 2L+ supply circuits.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7142-5AF00-0BA0 |
| Product Type | Field digital output module |
| Core Function | Eight-channel current-sourcing load control |
| Application | Distributed machine I/O with ET-Connection |
Distributed actuator switching
Eight two-ampere outputs serve field actuators through individual M12 connections.
Two load groups
Two groups of four outputs separate the load circuits and their current budgets.
Parameterized fault response
Channel-specific substitute values and diagnostic alarms support the selected machine fault response.
Product Overview
6ES7142-5AF00-0BA0 provides eight current-sourcing digital outputs in an ET 200AL field installation.
The module distributes outputs across two load groups, combines M12 signal connections with M8 power and ET-Connection interfaces, and supports channel-specific substitute values.
Key Functions
Distributed actuator switching
Eight two-ampere outputs serve field actuators through individual M12 connections.
Two load groups
Two groups of four outputs separate the load circuits and their current budgets.
Parameterized fault response
Channel-specific substitute values and diagnostic alarms support the selected machine fault response.
Official Specifications
| Output channels and type | 8 current-sourcing outputs; 2 groups of 4 |
|---|---|
| Rated current per output | 2 A |
| Supply circuits and range | 1L+ and 2L+: 24 V DC; 20.4–28.8 V DC |
| No-load current | 40 mA from 1L+; 35 mA from 2L+ |
| Maximum supply current | 4 A from each of 1L+ and 2L+ |
| Typical power loss | 4 W |
| Maximum current per group | 4 A; maximum 2 channels per group for inductive loads |
| Short-circuit protection | Electronic per channel; typical threshold 2.8 A |
| Minimum on-state voltage | L+ minus 0.8 V |
| Maximum off-state residual current | 0.5 mA |
| Load resistance and lamp limit | 12 Ω to 4 kΩ; maximum 10 W lamp load |
| Switching-frequency limits | 100 Hz resistive; 0.1 Hz inductive, 0.25 Hz at 25°C; 1 Hz lamp |
| Maximum unshielded cable | 30 m |
| Substitute values | Parameterizable channel by channel |
| Signal connections | 8 M12, 5-pole |
| Power and ET-Connection | M8 4-pole power; shielded M8 4-pin ET-Connection |
| Enclosure protection | IP65/67 |
| Operating ambient | −30 to +55°C |
| Installation altitude | Up to 5000 m; additional restrictions above 2000 m |
| Dimensions and approximate weight | 45 × 159 × 40 mm (W × H × D); 192 g |
Frequently Asked Questions
Can every output of 6ES7142-5AF00-0BA0 supply two amperes at the same time?
Each four-channel group has a combined limit of four amperes, with at most two channels per group for inductive loads.
Which connectors distinguish signal and power wiring on 6ES7142-5AF00-0BA0?
Signal wiring uses five-pole M12 connectors while the supply uses four-pole M8 connectors.
Can I set a separate substitute value for each output of 6ES7142-5AF00-0BA0?
Substitute values are parameterizable channel by channel.
What is the inductive-load switching limit of 6ES7142-5AF00-0BA0 at twenty-five degrees Celsius?
The specified inductive-load switching limit is one-quarter hertz at twenty-five degrees Celsius.
Are the two load-voltage circuits of 6ES7142-5AF00-0BA0 isolated?
The module provides potential separation between its two load-voltage circuits.
Does 6ES7142-5AF00-0BA0 use the same M12 connector for ET-Connection as for actuator outputs?
ET-Connection uses a shielded four-pin M8 interface rather than the five-pole M12 actuator interface.
Can I apply the normal environmental assumptions above two thousand metres with 6ES7142-5AF00-0BA0?
Operation above two thousand metres requires the additional installation restrictions specified for the module.