Siemens 6ES7138-4FA05-0AB0 SIMATIC ET 200S 4/8 F-DI PROFIsafe Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Configure the correct PROFIsafe module and F-parameters in the compatible station.
- Select the single-channel or two-channel evaluation required by the safety application.
- Match sensor-supply loads and configured delays to the connected sensors.
- Apply the achievable safety classification to the complete engineered safety function.
6ES7138-4FA05-0AB0 SIMATIC ET 200S 4/8 F-DI PROFIsafe Module
24 V DC F-DI module with eight single-channel or four two-channel inputs, two protected sensor supplies and configurable input delay.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7138-4FA05-0AB0 |
| Product Type | Fail-safe digital input module |
| Core Function | Acquisition of safety-related sensor signals |
| Application | ET 200S PROFIsafe stations |
Selectable input architecture
Eight single-channel inputs or four two-channel inputs support the specified sensor evaluation arrangement.
Protected sensor supplies
Two sensor-supply outputs provide a 300 mA rating with electronic short-circuit protection.
PROFIsafe integration
The module supports safety-related station operation and readable short-circuit diagnostics.
Product Overview
6ES7138-4FA05-0AB0 acquires safety-related digital signals in an ET 200S PROFIsafe station.
The thirty-millimeter module supports single-channel or two-channel evaluation, protected sensor supplies and diagnostic alarms, with use in a PROFINET configuration supported through an IM 151-3 HF interface.
Key Functions
Selectable input architecture
Eight single-channel inputs or four two-channel inputs support the specified sensor evaluation arrangement.
Protected sensor supplies
Two sensor-supply outputs provide a 300 mA rating with electronic short-circuit protection.
PROFIsafe integration
The module supports safety-related station operation and readable short-circuit diagnostics.
Official Specifications
| Input architecture | 8 single-channel inputs or 4 two-channel inputs |
|---|---|
| Nominal supply and input voltage | 24 V DC |
| Input characteristic | IEC 61131 Type 1 |
| Typical high-state input current | 3.7 mA |
| Configurable input delay | 0.3–17 ms for rising and falling transitions |
| Sensor-supply output count | 2 |
| Sensor-supply current rating | 300 mA |
| Sensor-supply voltage | At least L+ minus 1.5 V |
| Electronic protection threshold | 0.7–1.8 A |
| Typical power loss | 4 W |
| Address space | 6 input bytes and 4 output bytes |
| Maximum sensor cable | 500 m shielded or unshielded |
| Input isolation | From the backplane; no channel-to-channel or input-to-L+ isolation |
| Safety integrity by architecture | Up to SIL 2 single-channel or SIL 3 two-channel, IEC 61508 |
| Performance level | Up to PL e, ISO 13849-1 |
| Safety category | Up to Category 4, EN 954 |
| Diagnostic display | Red SF group-fault LED and green input-status LEDs |
| Dimensions and weight | 30 × 81 × 52 mm (W × H × D); approximately 78 g |
Frequently Asked Questions
How many two-channel sensor circuits can I evaluate with 6ES7138-4FA05-0AB0?
The module supports four two-channel input circuits.
Does single-channel operation of 6ES7138-4FA05-0AB0 have the same SIL limit as two-channel operation?
The stated maximum is SIL 2 for single-channel use and SIL 3 for two-channel use.
Can I use 6ES7138-4FA05-0AB0 in a PROFINET station?
The module supports a PROFINET configuration with an IM 151-3 HF interface.
Can I adjust the input delay of 6ES7138-4FA05-0AB0 for the sensor application?
Rising and falling input delays are configurable between 0.3 and 17 ms.
How many sensor-supply outputs are available on 6ES7138-4FA05-0AB0?
The module provides two protected sensor-supply outputs.
What cable-length limit should I apply to sensors connected to 6ES7138-4FA05-0AB0?
The specified maximum is 500 m for shielded or unshielded sensor cables.
Can the controller read short-circuit diagnostics from 6ES7138-4FA05-0AB0?
The module provides readable short-circuit diagnostic information and diagnostic alarms.