Overview
Siemens • SIMATIC ET 200iSP
6ES7134-7SD00-0AB0 SIMATIC ET 200iSP 4 AI TC Analog Input Module
The SIMATIC ET 200iSP 4 AI TC module provides four intrinsically safe analog inputs for thermocouple and voltage measurement with configurable linearization and diagnostics.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7134-7SD00-0AB0 |
| Product Type | Four-channel intrinsically safe thermocouple input module |
| Core Function | Measures thermocouple and voltage signals in hazardous-area process systems |
| Application or Compatible Series | ET 200iSP installations requiring intrinsically safe temperature measurement |
Exact Identification
Match 6ES7134-7SD00-0AB0 character by character and confirm the complete SIMATIC ET 200iSP 4 AI TC Analog Input Module designation.
Interface Arrangement
Confirm the installed supply, ports, field connections and required accessories before wiring the replacement.
Configuration Check
Preserve the approved engineering project, network parameters and application data used by the installed system.
Product Overview
The SIMATIC ET 200iSP 4 AI TC module provides four intrinsically safe analog inputs for thermocouple and voltage measurement with configurable linearization and diagnostics.
Four channels acquire thermocouple or voltage signals in the ET 200iSP station. Configured linearization supports common E, N, J, K, L, S, R, B, T and U thermocouples. Intrinsically safe circuits support the certified Ex installation when all associated conditions are met.
Key Functions
Four Temperature Inputs
Four channels acquire thermocouple or voltage signals in the ET 200iSP station.
Broad Thermocouple Support
Configured linearization supports common E, N, J, K, L, S, R, B, T and U thermocouples.
Hazardous-Area Capability
Intrinsically safe circuits support the certified Ex installation when all associated conditions are met.
Official Specifications
| Analog Inputs | 4 |
|---|---|
| Supported Sensors | Thermocouples and voltage signals |
| Thermocouple Types | E, N, J, K, L, S, R, B, T and U |
| Characteristic Linearization | Provided |
| Diagnostic Alarm | Parameterizable |
| Limit Alarm | Parameterizable |
| Wire-Break Detection | R greater than 1.7 kohm |
| Open-Circuit Voltage Uo | 5.9 V maximum |
| Short-Circuit Current Io | 15 mA maximum |
| Output Power Po | 23 mW maximum |
| External Capacitance Co, IIC | 43 uF maximum |
| External Inductance Lo, IIC | 100 mH maximum |
| Channel-to-Power-Bus Isolation | Provided |
| Channel-to-Backplane Isolation | Provided |
| Degree of Protection | IP30 |
| Electrical Connection | Screw or spring terminal |
| Dimensions W x H x D | 30 x 129 x 136.5 mm |
| Approximate Weight | 230 g |
| ATEX Certificate | KEMA 04 ATEX 1246 |
| IECEx Certificate | IECEx KEM 05.0008 |
Frequently Asked Questions
How many thermocouples can connect to 6ES7134-7SD00-0AB0?
The module provides four analog input channels for thermocouple or voltage measurement.
Which thermocouple types are supported by 6ES7134-7SD00-0AB0?
Configure the required E, N, J, K, L, S, R, B, T or U characteristic.
Can 6ES7134-7SD00-0AB0 be installed in an intrinsically safe circuit?
Yes; the complete loop, enclosure and associated apparatus must comply with the certified Ex parameters.
How does 6ES7134-7SD00-0AB0 detect an open sensor circuit?
Wire-break diagnostics operate when the configured circuit resistance exceeds the stated threshold.
What should be checked before changing 6ES7134-7SD00-0AB0?
Verify the Ex documentation, terminal assignment, thermocouple type, compensation method, barriers and grounding.
Can limit alarms be configured on 6ES7134-7SD00-0AB0?
Yes; parameterizable limit alarms are available for the measured channels.
What must be tested after installing 6ES7134-7SD00-0AB0?
Validate all four channels with known temperature signals and confirm compensation, diagnostics, alarms and intrinsic-safety records.
Compatibility & Ordering Notes
Compatibility Checklist
- Use only within the certified ET 200iSP and Ex installation design.
- Match thermocouple type, polarity and compensation settings per channel.
- Verify Uo, Io, Po, Co and Lo against every connected intrinsically safe loop.