- Select the thermocouple characteristic or millivolt range to match the connected sensor.
- Use the designated AT terminal module for internal compensation or separate external compensating boxes.
- Include active-channel count, filtering and wire-break diagnostics in the update-time calculation.
- Use shielded signal wiring and retain the correct ET 200S power-module arrangement.
6ES7134-4NB01-0AB0 SIMATIC ET 200S Two-Channel Thermocouple High Feature Module
A narrow 2AI TC High Feature module with internal or external cold-junction compensation, integrating conversion and selectable smoothing.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7134-4NB01-0AB0 |
| Product Type | Thermocouple analog input module |
| Core Function | Converting temperature-sensor signals |
| Application | Modular ET 200S I/O stations |
Selectable thermocouple acquisition
Ten thermocouple types and a bipolar millivolt range support different field sensors.
Cold-junction compensation
Internal compensation uses the designated AT terminal modules, while external compensation uses one compensating box per channel.
Configurable measurement filtering
Four smoothing stages trade response time for the selected level of digital filtering.
Product Overview
6ES7134-4NB01-0AB0 acquires thermocouple or low-level voltage measurements in an ET 200S station.
Configurable sensor linearization, temperature units and digital smoothing adapt the two-channel module to the field measurement, while diagnostic functions cover sensor wire breaks and range violations.
Key Functions
Selectable thermocouple acquisition
Ten thermocouple types and a bipolar millivolt range support different field sensors.
Cold-junction compensation
Internal compensation uses the designated AT terminal modules, while external compensation uses one compensating box per channel.
Configurable measurement filtering
Four smoothing stages trade response time for the selected level of digital filtering.
Official Specifications
| Analog input count | 2 |
|---|---|
| Input voltage range | −80 to +80 mV |
| Thermocouple types | B, C, E, J, K, L, N, R, S and T |
| Input resistance | 1 MΩ for the voltage and thermocouple ranges |
| Conversion resolution | 15 bits plus sign; 16 bits including sign with overrange |
| Integrating conversion | 16.7 or 20 ms integration for 60 or 50 Hz interference suppression |
| Basic conversion time | 66 or 80 ms per channel; wire-break testing adds conversion time |
| Module cycle time | Number of active channels multiplied by the basic conversion time |
| Digital smoothing | None: 1× cycle; low: 4×; medium: 32×; high: 64× |
| Temperature engineering units | Celsius or Fahrenheit |
| Supply | 24 V DC from the power module |
| Maximum current demand | 30 mA from L+ and 10 mA from the 3.3 V backplane |
| Typical dissipation | 0.6 W |
| Input address space | 4 bytes |
| Maximum shielded signal cable | 50 m |
| Voltage error limits | ±0.05% basic at 25 °C; ±0.1% operational over the temperature range |
| Diagnostics | Thermocouple wire break, group error and overflow/underflow; red SF indicator |
| Input isolation | Channels isolated from the backplane and L+; no channel-to-channel isolation |
| Isolation test voltage | 500 V DC |
| Dimensions and approximate mass | 15 × 81 × 52 mm (W × H × D); 40 g |
Frequently Asked Questions
Which terminal modules enable internal cold-junction compensation for 6ES7134-4NB01-0AB0?
Use a TM-E15S24-AT or TM-E15C24-AT terminal module for internal compensation.
Can I share one external compensating box between both channels of 6ES7134-4NB01-0AB0?
External cold-junction compensation requires one compensating box per channel.
Can 6ES7134-4NB01-0AB0 measure a low-level voltage instead of a thermocouple?
The module includes a −80 to +80 mV input range.
Can I display temperatures from 6ES7134-4NB01-0AB0 in Fahrenheit?
The temperature engineering unit can be configured as Celsius or Fahrenheit.
How much response delay does the high smoothing setting add on 6ES7134-4NB01-0AB0?
The high smoothing setting corresponds to 64 times the module cycle time.
Are the two sensor channels of 6ES7134-4NB01-0AB0 isolated from one another?
The channels are not isolated from each other, although they are isolated from the backplane and load supply.
How far may I run a shielded thermocouple cable to 6ES7134-4NB01-0AB0?
The specified maximum shielded signal-cable length is 50 m.