Siemens SIMATIC ET 200S 6ES7134-4GB52-0AB0 2AI High-Speed Current Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Match the complete order number and photographed product revision.
- Use an ET 200S terminal arrangement for a 15 mm electronic module.
- Confirm that each field device is a two-wire current transmitter within the permitted range and 670 Ω load limit.
- Use shielded signal wiring no longer than 200 m.
- Account for the absence of galvanic separation between the two input channels.
- For technology functions, use IM 151-1 High Feature 6ES7151-1BA01-0AB0 or 6ES7151-1BA02-0AB0.
- Do not use product revisions through E03 centrally with an IM 151-8 PN/DP CPU.
Siemens · SIMATIC ET 200S
6ES7134-4GB52-0AB0 2AI I 2WIRE HS Analog Input Module
Siemens 6ES7134-4GB52-0AB0 is a high-speed ET 200S analog electronic module for two independent two-wire current transmitters using the 0 to 20 mA or 4 to 20 mA range.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7134-4GB52-0AB0 |
| Product Type | High-Speed Analog Input Electronic Module |
| Core Function | Converts two-wire transmitter currents into fast digital process values |
| Application or Compatible Series | SIMATIC ET 200S distributed I/O stations |
Exact Signal Match
Confirm that both field devices are two-wire current transmitters using either the 0 to 20 mA or 4 to 20 mA range.
Timing and Filtering
Select the smoothing level according to the required response because the available time constants span one to 32 module cycles.
Interface and Revision Check
Verify the interface-module order number and electronic-module revision before enabling technology or isochronous functions.
Product Overview
Siemens 6ES7134-4GB52-0AB0 is a high-speed ET 200S analog electronic module for two independent two-wire current transmitters using the 0 to 20 mA or 4 to 20 mA range.
Two current-loop channels use successive-approximation conversion for rapid process acquisition. Four filtering levels stabilize the measured values with defined time constants. The module provides readable diagnostics and a parameterizable process interrupt with a capable interface module.
Key Functions
High-Speed Current Acquisition
Two current-loop channels use successive-approximation conversion for rapid process acquisition.
Selectable Digital Smoothing
Four filtering levels stabilize the measured values with defined time constants.
Diagnostics and Process Alarm
The module provides readable diagnostics and a parameterizable process interrupt with a capable interface module.
Official Specifications
| Input Ranges | 0 to 20 mA and 4 to 20 mA |
|---|---|
| Input Resistance | 106 Ω |
| Measuring Principle | Successive-approximation register conversion |
| Conversion Time | 15 µs per channel |
| All-Channel Module Cycle | 0.25 ms maximum |
| Encoded Resolution | 15-bit analog resolution; 16 bits maximum when the sign is included |
| Digital Smoothing | None, weak, medium or strong with time constants of 1, 4, 16 or 32 module cycles |
| Transmitter Supply | Two outputs, 24 V with +5% / -10% tolerance and 45 mA rated per channel |
| Two-Wire Transmitter Load | 670 Ω maximum |
| Maximum Shielded Cable Length | 200 m |
| Address Space | 4 bytes |
| Parameter Data Length | 12 bytes |
| Current from L+ | 225 mA maximum with sensor supply |
| Current from 3.3 V Backplane Bus | 10 mA maximum |
| Typical Power Loss | 2.5 W |
| Crosstalk Between Inputs | Greater than 50 dB |
| Operational Error Limit | ±0.3% of input range over the full temperature range |
| Basic Error Limit | ±0.2% of input range at 25 °C |
| Temperature, Linearity and Repeatability Errors | ±0.01%/K, ±0.03% and ±0.1% at steady state and 25 °C |
| Galvanic Isolation | Channels isolated from the backplane bus and L+ but not isolated from each other; tested at 500 V DC |
Frequently Asked Questions
Which current ranges can 6ES7134-4GB52-0AB0 measure?
It accepts 0 to 20 mA and 4 to 20 mA signals from two-wire transmitters.
What conversion speed does 6ES7134-4GB52-0AB0 provide?
Each channel converts in 15 µs, and the complete module cycle is rated at up to 0.25 ms.
Can 6ES7134-4GB52-0AB0 be used for isochronous technology functions with any ET 200S interface?
Use IM 151-1 High Feature 6ES7151-1BA01-0AB0 or 6ES7151-1BA02-0AB0 for the verified technology-function configuration.
What is the maximum signal-cable length for 6ES7134-4GB52-0AB0?
A shielded signal cable may be up to 200 m long.
Are the two input channels of 6ES7134-4GB52-0AB0 isolated from one another?
The channels are isolated from the backplane and load supply but are not galvanically isolated from each other.
Which diagnostic condition can 6ES7134-4GB52-0AB0 detect on a 4 to 20 mA loop?
The diagnostic set includes an open-circuit indication for the 4 to 20 mA range.
What must be checked before installing 6ES7134-4GB52-0AB0 behind an IM 151-8 PN/DP CPU?
Product revisions through E03 must not be used centrally with that CPU because Siemens identifies possible disruptive responses.