Siemens 6ES7132-6GD51-0BA0 ET 200SP RQ CO 4-Channel Signal Relay Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use BaseUnit type A0 and the CC00 identification arrangement.
- Keep switched signals within the 24 V AC/DC contact rating.
- Apply the total-current limit for the selected orientation and cabinet temperature.
- Provide external output protection and do not parallel channels to increase current capacity.
6ES7132-6GD51-0BA0 ET 200SP RQ CO 4-Channel Signal Relay Module
A four-channel changeover-relay module for 24 V AC/DC signals up to 2 A per channel, with supply-voltage diagnostics and substitute-value output.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7132-6GD51-0BA0 |
| Product Type | Signal relay output module |
| Core Function | Galvanically isolated signal switching |
| Application | ET 200SP BaseUnit type A0 |
Four isolated changeover contacts
Each relay channel provides a changeover contact for low-voltage signal circuits with up to 2 A per channel.
Defined fault response
Configurable substitute values define the requested output behavior when the station applies a substitute state.
Supply and module diagnostics
The PWR and DIAG indicators support supply and module checks, while channel LEDs show output status.
Product Overview
6ES7132-6GD51-0BA0 switches low-voltage signals through four isolated changeover contacts in an ET 200SP station.
The module provides supply-voltage monitoring, channel status indication and configurable substitute values; the permitted combined output current depends on mounting orientation and ambient temperature.
Key Functions
Four isolated changeover contacts
Each relay channel provides a changeover contact for low-voltage signal circuits with up to 2 A per channel.
Defined fault response
Configurable substitute values define the requested output behavior when the station applies a substitute state.
Supply and module diagnostics
The PWR and DIAG indicators support supply and module checks, while channel LEDs show output status.
Official Specifications
| Relay arrangement | 4 isolated changeover contacts |
|---|---|
| Contact switching voltage | 24 V AC or 24 V DC, rated |
| Maximum channel current | 2 A |
| Minimum switching load | 1 mA at 5 V DC |
| Maximum switching frequency | 2 Hz with resistive load |
| Combined current, horizontal | 8 A up to 40 °C; 6 A up to 50 °C; 4 A up to 60 °C |
| Combined current, vertical | 8 A up to 30 °C; 6 A up to 40 °C; 4 A up to 50 °C |
| Module supply | 24 V DC; permitted 19.2–28.8 V DC |
| Rated module consumption | 50 mA |
| Typical power loss | 1.2 W |
| Relay endurance | Maximum 500,000 operating cycles |
| Output short-circuit protection | Not integrated |
| Maximum cable lengths | 1,000 m shielded; 200 m unshielded |
| Address space | 1 output byte; an additional input byte for QI information |
| Isolation test | 707 V DC, type test |
| Operating temperature | −30 to +60 °C horizontal; −30 to +50 °C vertical |
| Module width | 15 mm |
| Height and depth | 73 × 58 mm |
| Approximate weight | 30 g |
Frequently Asked Questions
Can 6ES7132-6GD51-0BA0 switch a 230 V AC signal?
The rated contact-switching voltage is 24 V AC or 24 V DC.
Which BaseUnit do I need beneath 6ES7132-6GD51-0BA0?
Use an ET 200SP BaseUnit of type A0 with the CC00 color-code arrangement.
Can I switch 2 A on all channels of 6ES7132-6GD51-0BA0 at 60 degrees Celsius?
At 60 °C in horizontal installation, the module’s total output current is limited to 4 A.
Can I parallel the outputs of 6ES7132-6GD51-0BA0 to increase current capacity?
Parallel outputs are not permitted for current uprating.
Does 6ES7132-6GD51-0BA0 detect a short circuit or broken load wire?
The module provides supply-voltage diagnostics but no short-circuit or wire-break diagnostics.
What PLC address space is needed for 6ES7132-6GD51-0BA0?
The module uses one output byte and an additional input byte when QI information is used.
Can I assign 6ES7132-6GD51-0BA0 to a safety shutdown function?
The module is not suitable for safety functions.