- Use BaseUnit A0 with CC00 identification.
- Start the load group with a light-colored BaseUnit.
- Check each 0.5 A output and the orientation-dependent module current.
- Configure module-level diagnostics and the desired CPU STOP response.
- Allocate the additional input bytes if quality information is enabled.
6ES7132-6BH00-0BA0 SIMATIC ET 200SP DQ 16x24VDC/0.5A ST Output Module
Sixteen PNP outputs with 0.5 A per channel, temperature-dependent module current limits and configurable module diagnostics.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7132-6BH00-0BA0 |
| Product Type | Standard digital-output module |
| Core Function | Driving DC field actuators |
| Application | ET 200SP stations |
Sixteen PNP channels
Positive-switching outputs drive DC contactors, valves and indicator loads.
Temperature derating
The available module current depends on ambient temperature and mounting orientation.
BaseUnit A0
The output module uses A0 BaseUnits and CC00 color identification.
Product Overview
6ES7132-6BH00-0BA0 controls sixteen 24 V DC loads in an ET 200SP station. Each PNP channel is rated at 0.5 A, with a module total of up to 8 A under the stated installation conditions.
Configurable substitute values determine the response to CPU STOP. Module-level diagnostics cover supply voltage, wire break and short circuit, and optional quality information adds two bytes to the input address space.
Key Functions
Switch PNP loads
Sixteen positive-switching outputs provide 0.5 A per channel.
Set the STOP reaction
Channels can turn off, retain their last value or use configured substitute values.
Monitor module conditions
Configurable diagnostics and optional quality information support commissioning and fault evaluation.
Official Specifications
| Digital outputs | 16, PNP source outputs |
|---|---|
| Rated supply and permitted range | 24 V DC; 19.2–28.8 V DC |
| Maximum current without load | 60 mA |
| Typical power loss | 1 W |
| Output current per channel | 0.5 A |
| Horizontal module-current limits | 8 A up to 40 °C; 6 A up to 50 °C; 4 A up to 60 °C |
| Vertical module-current limits | 8 A up to 30 °C; 6 A up to 40 °C; 4 A up to 50 °C |
| Typical short-circuit response threshold | 0.7–1.3 A |
| Maximum lamp load | 5 W |
| Load resistance range | 48 Ω–12 kΩ |
| Maximum signal-0 residual current | 0.1 mA |
| Typical output delay with resistive load | 50 µs for 0→1; 100 µs for 1→0 |
| Maximum switching frequency | Resistive 100 Hz; inductive 2 Hz; lamp 10 Hz |
| Address-space allocation | 2 output bytes; an additional 2 input bytes for quality information |
| Maximum cable length | 1000 m shielded; 600 m unshielded |
| Diagnostic scope | Module-level supply-voltage, wire-break and short-circuit diagnostics |
| Local indicators | Green PWR and channel LEDs; green/red DIAG LED |
| Electrical isolation | Outputs separated from backplane; no separation between channels |
| Insulation type-test voltage | 707 V DC |
| Width and approximate weight | 15 mm; 28 g |
Frequently Asked Questions
May I install 6ES7132-6BH00-0BA0 on a BaseUnit type A1?
Use BaseUnit type A0 because an A1 fuse can be triggered and render its terminals unusable.
Where must the load group for 6ES7132-6BH00-0BA0 begin?
The load group must begin with a light-colored BaseUnit.
How much total current can 6ES7132-6BH00-0BA0 carry horizontally at 60 °C?
The module-current limit is 4 A in that installation condition.
Which responses to CPU STOP can I select for 6ES7132-6BH00-0BA0?
You can select turn off, keep last value or output a configured substitute value.
Why might a small indicator flicker when an output of 6ES7132-6BH00-0BA0 is off?
The low residual current associated with wire-break detection can cause indicator diodes to flicker.
Does the quality information of 6ES7132-6BH00-0BA0 identify each faulty output independently?
A fault on one channel sets the quality status of all channels to zero.
Will parameters written to 6ES7132-6BH00-0BA0 with WRREC remain after a restart?
The STEP 7 parameter settings become effective again after restart.