Siemens 6ES7132-6BD20-0BA0 ET 200SP DQ 4x24VDC/2A ST Digital Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Select BaseUnit type A0 and CC02 color identification for this module.
- Provide AUX connections or potential distributors for the required three- or four-wire actuators.
- Keep each output within 2 A and observe the total-current limits for temperature and orientation.
- Allocate the additional input byte when quality information is enabled.
- Use module-level diagnostics for wire-break and short-circuit reporting; channel diagnostic LEDs are not provided.
6ES7132-6BD20-0BA0 ET 200SP DQ 4x24VDC/2A ST Digital Output Module
A four-channel, current-sourcing 24 V DC output module with 2 A per channel, module diagnostics and BaseUnit type A0 compatibility.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7132-6BD20-0BA0 |
| Product Type | Standard digital output module |
| Core Function | Switches DC actuator signals |
| Application | ET 200SP distributed I/O stations |
Four sourcing channels
PNP outputs switch 24 V DC loads at up to 2 A per channel.
Module diagnostics
Supply, short-circuit and wire-break diagnostics assist commissioning.
A0 BaseUnit
The module uses a type A0 BaseUnit and the CC02 identification color code.
Product Overview
6ES7132-6BD20-0BA0 provides four current-sourcing digital outputs for 24 V DC actuators in a SIMATIC ET 200SP station.
The standard module supports diagnostic alarms and optional quality information, while its permitted total output current depends on the installation orientation and ambient temperature.
Key Functions
PNP actuator switching
Four outputs provide up to 2 A per channel for DC loads, with electronic short-circuit protection and a maximum resistive-load switching frequency of 100 Hz.
Diagnostics and quality information
Module diagnostics cover load-voltage monitoring, short circuit and wire break, and an enabled QI input byte reports the validity of the output channels.
Flexible field-wiring arrangements
Type A0 BaseUnits support one- and two-wire actuators, while AUX terminals or potential distributors provide the additional connections needed for three- and four-wire arrangements.
Official Specifications
| Digital Output Arrangement | 4 PNP current-sourcing channels, 24 V DC, 2 A per channel |
|---|---|
| Permissible Supply Voltage | 19.2–28.8 V DC |
| No-load Current Consumption | 60 mA maximum |
| Typical Power Loss | 1 W |
| Maximum Module Output Current | 8 A, subject to mounting position and temperature |
| Horizontal-installation Current Limits | 8 A at 40 °C; 6 A at 50 °C; 4 A at 60 °C |
| Vertical-installation Current Limits | 8 A at 30 °C; 6 A at 40 °C; 4 A at 50 °C |
| Electronic Short-circuit Threshold | 2.8–5.2 A typical |
| Maximum Lamp Load | 10 W per output |
| Load Resistance | 12–3,400 Ω |
| Maximum Off-state Residual Current | 0.1 mA |
| Resistive-load Output Delays | 50 µs maximum for 0→1; 100 µs maximum for 1→0 |
| Maximum Switching Frequencies | 100 Hz resistive; 2 Hz inductive; 10 Hz lamp load |
| Maximum Output Cable Lengths | 1,000 m shielded; 600 m unshielded |
| Output Address Space | 1 byte, plus 1 input byte when QI is enabled |
| Isolation Test Voltage | 707 V DC type test, channels to backplane bus |
| Module Indicators | Green PWR and channel LEDs; green/red DIAG LED |
| Operating Temperature Limits | Horizontal: −30–60 °C; vertical: −30–50 °C; operation below 0 °C from FS08 |
| Dimensions (W × H × D) | 15 × 73 × 58 mm |
| Approximate Weight | 30 g |
Frequently Asked Questions
Which BaseUnit should I select for 6ES7132-6BD20-0BA0?
Use a type A0 BaseUnit and match the actuator wiring arrangement to the required AUX terminals or potential distributor.
Does 6ES7132-6BD20-0BA0 need extra terminals for three-wire actuators?
Three-wire wiring requires a type A0 BaseUnit with AUX terminals or an appropriate potential distributor module.
What does a QI value of zero indicate for 6ES7132-6BD20-0BA0?
A zero quality-status bit indicates a deactivated channel or a module fault, and a channel fault sets the quality status of all channels to zero.
Why is the PWR LED on 6ES7132-6BD20-0BA0 off?
An unlit PWR LED indicates that the load supply voltage L+ is absent.
Can I parallel two outputs of 6ES7132-6BD20-0BA0 to increase the load current?
Parallel outputs must not be used to increase the current rating.
Can 6ES7132-6BD20-0BA0 deliver the full 8 A at 60 °C in horizontal mounting?
The permitted total module current falls to 4 A at 60 °C in horizontal mounting.
Does 6ES7132-6BD20-0BA0 operate as a PWM output module?
The standard module provides digital switching outputs and does not support PWM mode.