Overview
- Choose a supported spring, screw or Fast Connect ET 200S terminal module.
- Match the required M and AUX1 connections to the selected terminal variant.
- Provide the load voltage through the appropriate station power module.
- Do not exceed the 4 A module total or use parallel outputs to increase the rating.
- Account for the approximately 25 µs signal when the load supply is switched through a mechanical contact.
6ES7132-4BD32-0AA0 ET 200S 4DO 24VDC/2A ST Digital Output Module
A four-output 24 V DC PNP module with 2 A per channel, a 4 A total module-current limit and green output-status indication.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7132-4BD32-0AA0 |
| Product Type | Standard digital output electronics module |
| Core Function | Switches field actuator loads |
| Application | ET 200S stations with 15 mm terminal modules |
Four PNP outputs
Current-sourcing channels drive suitable DC loads.
4 A module total
The total current remains limited to 4 A despite the 2 A channel rating.
15 mm electronics
The electronics fit the matching ET 200S terminal-module variants.
Product Overview
6ES7132-4BD32-0AA0 is a four-channel ET 200S digital output electronics module for solenoid valves, DC contactors and indicator lights.
Each output is rated at 2 A, while the module total is limited to 4 A; the load voltage is supplied through the station power module and the field wiring remains on the selected terminal module.
Key Functions
Switching DC actuator loads
Four PNP outputs switch 24 V DC loads with short-circuit protection and a maximum resistive-load switching frequency of 1,000 Hz.
Compact output addressing
The module uses one byte of address space, or four bits when address packing is used, and green LEDs show the output states.
Terminal-module wiring options
Supported 15 mm terminal modules provide spring, screw or Fast Connect wiring options, with auxiliary connections determined by the selected terminal variant.
Official Specifications
| Output Configuration | 4 current-sourcing PNP outputs, 24 V DC |
|---|---|
| Rated Current per Output | 2 A |
| Maximum Total Output Current | 4 A per module |
| Load Current Operating Range | 7 mA–2.4 A per active output |
| Power-module Load Supply | 24 V DC |
| No-load Supply Currents | 10 mA maximum per channel from L+; 10 mA maximum from the 3.3 V backplane |
| Typical Power Loss | 1.6 W |
| Address Allocation | 1 byte per module; 4 bits with packing |
| Short-circuit Threshold | 2.8–7.2 A typical |
| Inductive Shutdown Clamp | Typically L+ minus 55–60 V |
| Minimum On-state Output Voltage | L+ minus 1.0 V |
| Maximum Off-state Residual Current | 0.1 mA |
| Resistive-load Switching Delays | 0→1: 45 µs typical, 50 µs maximum; 1→0: 90 µs typical, 120 µs maximum |
| Maximum Switching Frequencies | 1,000 Hz resistive; 2 Hz inductive at 0.5 H; 10 Hz lamp load |
| Maximum Lamp Load | 10 W |
| Load Resistance Range | 12–3,400 Ω |
| Maximum Cable Lengths | 1,000 m shielded; 600 m unshielded |
| Isolation Test Voltage | 500 V DC between outputs and backplane bus |
| Dimensions (W × H × D) | 15 × 81 × 52 mm |
| Approximate Module Weight | 40 g |
Frequently Asked Questions
Can all four outputs of 6ES7132-4BD32-0AA0 carry 2 A at the same time?
The module total is limited to 4 A, so the four channel loads must be budgeted within that total.
Why could a fast counter detect a pulse when power is applied to 6ES7132-4BD32-0AA0?
Applying the 24 V load supply through a mechanical contact can produce an output signal of about 25 µs.
Which screw-terminal bases can I use with 6ES7132-4BD32-0AA0?
Supported screw-terminal variants include TM-E15S26-A1, TM-E15S24-A1, TM-E15S24-01 and TM-E15S23-01.
Does 6ES7132-4BD32-0AA0 provide diagnostic alarms for individual channels?
The module has output-status LEDs but does not provide a diagnostic function.
How much address space is needed for 6ES7132-4BD32-0AA0 with packing?
Address packing reduces the module allocation from one byte to four bits.
Can I use the AUX1 terminals on every base selected for 6ES7132-4BD32-0AA0?
The available AUX1 and additional ground terminals depend on the selected terminal-module variant.
Can I wire outputs of 6ES7132-4BD32-0AA0 together for a higher-current actuator?
Parallel switching for increased current is not permitted, although redundant load control is supported within the module.