Overview
SIEMENS SIMATIC ET 200S

6ES7132-4BB01-0AB0 SIMATIC ET 200S 2DO DC24V 0.5A High Feature Module

A two-channel sourcing output module with 0.5 A per output, channel-level short-circuit and wire-break diagnostics, selectable substitute values and isochronous capability.

At a Glance

Brand Siemens
Model 6ES7132-4BB01-0AB0
Product Type High Feature digital output module
Core Function Switching two DC loads with channel diagnostics
Application ET 200S electronic-module stations

Two sourcing outputs

The PNP outputs supply current to the connected DC loads.

Channel diagnostics

Short-circuit and wire-break information is available for each channel.

Defined substitute values

Substitute outputs can be configured as 0 or 1.

Product Overview

6ES7132-4BB01-0AB0 provides two High Feature PNP sourcing outputs for ET 200S, with a 24 V DC load supply from the power module and 0.5 A rated output current per channel.

The module adds per-channel fault diagnostics, green output status indication and a red SF group indicator, with selectable substitute values and isochronous operation support.

Ordering focus: Size both loads within the channel and module limits, preserve the PNP output arrangement and configure diagnostics and substitute values for the application.
Key Functions

Drive the two DC loads

Each sourcing output provides a rated 0.5 A with a total module output-current limit of 1 A.

Identify channel wiring and short-circuit faults

Readable diagnostic information covers wire break and short circuit channel by channel, supported by the SF and output status LEDs.

Select the response in substitute-value operation

The module permits substitute values of 0 or 1 and supports packed addressing and isochronous operation in a compatible station.

Official Specifications
Rated Load Voltage 24 V DC from the power module
Output Construction 2 PNP current-sourcing outputs
Output-Current Limits 0.5 A rated per channel; permissible signal-1 range 7–600 mA; total module maximum 1 A
Signal-1 Output Voltage Minimum L+ minus 1 V
Signal-0 Residual Current Maximum 0.3 mA
Typical Short-Circuit Response Threshold 1.5 A
Inductive Shutdown-Voltage Limitation Typically L+ minus 55 to 60 V
Permissible Load Resistance 48–3400 Ω
Maximum Lamp Load 2.5 W
Resistive-Load Output Delay Maximum 100 µs on; 400 µs off
Maximum Switching Frequencies 100 Hz resistive; 2 Hz inductive; 10 Hz lamp load
No-Load Current Consumption Maximum 5 mA per channel from L+; 10 mA from the 3.3 V backplane bus
Typical Power Loss 0.4 W
Address Requirement Maximum 1 byte per module; 2 bits with packing
Substitute Output Values Selectable 0 or 1
Diagnostic and Status Indication Channel wire-break and short-circuit diagnostics; red SF and green output LEDs
Maximum Cable Length 1000 m shielded; 600 m unshielded
Isolation Arrangement and Test No channel-to-channel isolation; outputs isolated from backplane; 500 V DC test
Dimensions and Approximate Weight 15 × 81 × 52 mm; 40 g
Frequently Asked Questions

Can I parallel the outputs of 6ES7132-4BB01-0AB0 to increase the load current?

Parallel output operation is not permitted for increasing the current rating.

Can 6ES7132-4BB01-0AB0 be used for redundant control of one load?

Parallel switching for redundant control of a load is supported within the same module.

What should I check if a small load on 6ES7132-4BB01-0AB0 draws less than 7 mA?

The permitted signal-1 current range starts at 7 mA, so the load must satisfy that minimum.

Will 6ES7132-4BB01-0AB0 identify which channel has a broken wire?

Wire-break diagnostics are available channel by channel.

Can I force a defined output level with substitute values on 6ES7132-4BB01-0AB0?

The substitute value can be configured as 0 or 1.

How fast may I switch an inductive load with 6ES7132-4BB01-0AB0?

The maximum switching frequency for an inductive load is 2 Hz.

What should I consider before reversing the supply polarity of 6ES7132-4BB01-0AB0?

Polarity reversal can cause the digital outputs to be connected through, so the correct supply polarity must be maintained.

Compatibility & Ordering Notes
Before ordering 6ES7132-4BB01-0AB0: Select the 0.5 A High Feature module and compatible terminal base, calculate both channel loads and total current, and distinguish the five-module manufacturer pack from the required station quantity.

Compatibility Checklist for 6ES7132-4BB01-0AB0

  • Use the correct ET 200S terminal base for the two-channel output wiring.
  • Keep each output and the module total within their specified current limits.
  • Use a load within the 7–600 mA signal-1 range and the stated resistance range.
  • Configure the channel diagnostics and required substitute values.
  • Maintain correct polarity and the common load-voltage arrangement with the power module.
  • Do not parallel outputs for higher current; use redundant-control paralleling only within its specified scope.
Hot Selling Models
LUCB18BL
ABB R115/10 GHV1150001R1
3RG9002-0DC00
ZM-16-PKZ NHI 11-PKZ2
3RG4013-0JB00-PF
SR406 102582 + POPE 8414
A1SY80
3SU1806-0AA00-0AB1
SRC-I 2CO P 8869500000
7000-40041-7321000
7000-13081-6411000
3RV2021-1AA10
efector150 KN0006
6DS1605-8BA
140 DDI35300

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop

Evolo Automation is not an authorized distributor unless otherwise specified, representative, or affiliate of the manufacturer of this product. All trademarks and documents are the property of their respective owners and are provided for identification and informational.