Siemens 6ES7132-4BB01-0AB0 SIMATIC ET 200S 2DO DC24V 0.5A High Feature Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the correct ET 200S terminal base for the two-channel output wiring.
- Keep each output and the module total within their specified current limits.
- Use a load within the 7–600 mA signal-1 range and the stated resistance range.
- Configure the channel diagnostics and required substitute values.
- Maintain correct polarity and the common load-voltage arrangement with the power module.
- Do not parallel outputs for higher current; use redundant-control paralleling only within its specified scope.
6ES7132-4BB01-0AB0 SIMATIC ET 200S 2DO DC24V 0.5A High Feature Module
A two-channel sourcing output module with 0.5 A per output, channel-level short-circuit and wire-break diagnostics, selectable substitute values and isochronous capability.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7132-4BB01-0AB0 |
| Product Type | High Feature digital output module |
| Core Function | Switching two DC loads with channel diagnostics |
| Application | ET 200S electronic-module stations |
Two sourcing outputs
The PNP outputs supply current to the connected DC loads.
Channel diagnostics
Short-circuit and wire-break information is available for each channel.
Defined substitute values
Substitute outputs can be configured as 0 or 1.
Product Overview
6ES7132-4BB01-0AB0 provides two High Feature PNP sourcing outputs for ET 200S, with a 24 V DC load supply from the power module and 0.5 A rated output current per channel.
The module adds per-channel fault diagnostics, green output status indication and a red SF group indicator, with selectable substitute values and isochronous operation support.
Key Functions
Drive the two DC loads
Each sourcing output provides a rated 0.5 A with a total module output-current limit of 1 A.
Identify channel wiring and short-circuit faults
Readable diagnostic information covers wire break and short circuit channel by channel, supported by the SF and output status LEDs.
Select the response in substitute-value operation
The module permits substitute values of 0 or 1 and supports packed addressing and isochronous operation in a compatible station.
Official Specifications
| Rated Load Voltage | 24 V DC from the power module |
|---|---|
| Output Construction | 2 PNP current-sourcing outputs |
| Output-Current Limits | 0.5 A rated per channel; permissible signal-1 range 7–600 mA; total module maximum 1 A |
| Signal-1 Output Voltage | Minimum L+ minus 1 V |
| Signal-0 Residual Current | Maximum 0.3 mA |
| Typical Short-Circuit Response Threshold | 1.5 A |
| Inductive Shutdown-Voltage Limitation | Typically L+ minus 55 to 60 V |
| Permissible Load Resistance | 48–3400 Ω |
| Maximum Lamp Load | 2.5 W |
| Resistive-Load Output Delay | Maximum 100 µs on; 400 µs off |
| Maximum Switching Frequencies | 100 Hz resistive; 2 Hz inductive; 10 Hz lamp load |
| No-Load Current Consumption | Maximum 5 mA per channel from L+; 10 mA from the 3.3 V backplane bus |
| Typical Power Loss | 0.4 W |
| Address Requirement | Maximum 1 byte per module; 2 bits with packing |
| Substitute Output Values | Selectable 0 or 1 |
| Diagnostic and Status Indication | Channel wire-break and short-circuit diagnostics; red SF and green output LEDs |
| Maximum Cable Length | 1000 m shielded; 600 m unshielded |
| Isolation Arrangement and Test | No channel-to-channel isolation; outputs isolated from backplane; 500 V DC test |
| Dimensions and Approximate Weight | 15 × 81 × 52 mm; 40 g |
Frequently Asked Questions
Can I parallel the outputs of 6ES7132-4BB01-0AB0 to increase the load current?
Parallel output operation is not permitted for increasing the current rating.
Can 6ES7132-4BB01-0AB0 be used for redundant control of one load?
Parallel switching for redundant control of a load is supported within the same module.
What should I check if a small load on 6ES7132-4BB01-0AB0 draws less than 7 mA?
The permitted signal-1 current range starts at 7 mA, so the load must satisfy that minimum.
Will 6ES7132-4BB01-0AB0 identify which channel has a broken wire?
Wire-break diagnostics are available channel by channel.
Can I force a defined output level with substitute values on 6ES7132-4BB01-0AB0?
The substitute value can be configured as 0 or 1.
How fast may I switch an inductive load with 6ES7132-4BB01-0AB0?
The maximum switching frequency for an inductive load is 2 Hz.
What should I consider before reversing the supply polarity of 6ES7132-4BB01-0AB0?
Polarity reversal can cause the digital outputs to be connected through, so the correct supply polarity must be maintained.