Siemens 6ES7131-1BH01-0XB0 SIMATIC ET 200L L 16 DI DC 24 V Electronics Block
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the ET 200L terminal block required by the station connection arrangement.
- Keep the two-wire sensor off-state current within the 1.5 mA limit.
- Use the updated device description when selecting 45.45 kbaud.
- Apply the permitted circuit-breaker rating to the sensor-supply groups.
SIEMENS SIMATIC ET 200L
6ES7131-1BH01-0XB0 SIMATIC ET 200L L 16 DI DC 24 V Electronics Block
Read 16 switch and proximity-sensor signals through an ET 200L electronics block with integrated PROFIBUS DP communication and local channel indicators.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7131-1BH01-0XB0 |
| Product Type | Digital input electronics block |
| Core Function | Acquire binary sensor signals |
| Application | PROFIBUS DP distributed I/O |
Binary field sensing
Sixteen 24 V DC inputs read switches and compatible proximity sensors.
PROFIBUS station link
The integrated DP interface exchanges the input data with the master.
Visible station diagnostics
Channel LEDs, a BF bus-fault LED and an ON supply LED support service checks.
Product Overview
6ES7131-1BH01-0XB0 is an ET 200L digital input electronics block with 16 channels arranged in two groups of eight. It connects field switches and proximity sensors to a PROFIBUS DP master through a compact distributed I/O station.
The electronics block provides local input-state indication and PROFIBUS diagnostics, with galvanic isolation between the field channels and the bus interface; channels within the block are not isolated from each other.
Key Functions
Read switches and proximity sensors
The 24 V DC input characteristic supports mechanical switches and compatible two-wire proximity sensors within the permitted off-state current.
Exchange process inputs over PROFIBUS DP
The integrated slave interface supports data rates up to 1.5 Mbaud and FREEZE operation.
Locate station and bus conditions
Green channel LEDs indicate the input signals, while the red BF and green ON LEDs show bus and electronics-supply conditions.
Official Specifications
| Input Arrangement | 16 digital inputs in 2 groups of 8 |
|---|---|
| Electronics and Sensor Supply | 24 V DC with reverse-polarity protection |
| PROFIBUS Data Rates | 9.6, 19.2, 45.45, 93.75, 187.5, 500 and 1500 kbaud |
| PROFIBUS Manufacturer ID | 0014H |
| Input Signal Levels | ON: 13 to 30 V; OFF: −30 to +5 V |
| Typical ON-State Input Current | 5 mA at 24 V DC |
| Input Delay in Both Directions | 2.0 to 4.5 ms |
| Input Characteristic | IEC 1131-2 Type 1 |
| Permitted Two-Wire Sensor OFF Current | Maximum 1.5 mA |
| Electronics Supply Current | Maximum 70 mA |
| No-Load Sensor-Supply Current | Maximum 50 mA per load group |
| Typical Power Dissipation | 2.2 W |
| Power-Failure Withstand Time | At least 20 ms |
| Isolation | Channels isolated from PROFIBUS DP; no isolation between channels |
| Insulation Test Voltage | 500 V DC |
| Maximum Sensor-Cable Length | 600 m unshielded; 1000 m shielded |
| Dimensions | 145 × 60 × 60.5 mm (W × H × D) |
| Approximate Weight | 130 g |
Frequently Asked Questions
Can I connect two-wire proximity sensors to 6ES7131-1BH01-0XB0?
Yes, compatible two-wire proximity sensors can be connected when their closed-circuit current does not exceed 1.5 mA.
Does 6ES7131-1BH01-0XB0 support PROFIBUS station link for mobile equipment?
A voltage from 13 to 30 V is recognized as an ON signal.
Can the DP master freeze the input image of 6ES7131-1BH01-0XB0?
Yes, the electronics block supports PROFIBUS DP FREEZE operation.
What must I change to run 6ES7131-1BH01-0XB0 at 45.45 kbaud?
Use an updated device master file or STEP 7 V4.02 with K4.02.6 or later support for that transmission rate.
Does 6ES7131-1BH01-0XB0 isolate each input from the next one?
No, the channels are isolated from PROFIBUS DP but are not isolated from one another.
Which local indicators should I check when 6ES7131-1BH01-0XB0 stops exchanging data?
Check the red BF LED for a bus fault and the green ON LED for the electronics supply.
How should I protect the sensor-supply terminals of 6ES7131-1BH01-0XB0?
The 1L+, 2L+ and 3L+ sensor-supply terminals may be protected with a maximum 6 A circuit breaker with B or C characteristic.