Overview
- Use the module in a supported S5-135U, S5-155U or EU 185U system.
- Keep unused channels unwired and unaddressed.
- Supply configurable input sensors and 1L+ from the same source.
- Respect 4 A per eight outputs and the ventilation-dependent total-load limit.
6ES5482-4UA20 SIMATIC S5 DI/DQ 482 Digital I/O Module
DI/DQ 482 combines fixed and configurable 24 V DC channels, providing 16 to 24 inputs and 8 to 16 outputs within a 32-channel isolated group.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES5482-4UA20 |
| Product Type | Configurable digital I/O module |
| Core Function | Discrete process-signal exchange |
| Application | S5-135U, S5-155U and EU 185U systems |
Configurable middle byte
Eight channels can be assigned individually as inputs or outputs.
24 V DC signals
The output switching range is 5 mA to 0.5 A.
S5 system integration
The 4UA20 version operates without the IP 257 interface.
Product Overview
6ES5482-4UA20 is a SIMATIC S5 DI/DQ 482 module with 16 fixed inputs, eight fixed outputs and eight individually configurable channels. All 32 channels share one isolated group rather than separate input and output potential groups.
The user program determines how the configurable byte is used, allowing the channel allocation to follow the installed process wiring within the supported input and output totals.
Key Functions
Flexible channel allocation
Channels 0.0 to 0.7 are fixed outputs, channels 2.0 to 3.7 are fixed inputs, and channels 1.0 to 1.7 can each operate as an input or output.
Process output switching
The 24 V DC outputs switch resistive and inductive loads within the individual-channel and eight-output group limits.
Program-controlled use
Input access and output assignment determine use of the configurable channels, while an input-designated channel must retain a zero in its output register bit.
Official Specifications
| Input capacity | 16 fixed inputs plus up to 8 configurable inputs |
|---|---|
| Output capacity | 8 fixed outputs plus up to 8 configurable outputs |
| Rated field supply | 24 V DC |
| Input thresholds | Logic 0: −33 to +7 V; logic 1: 13 to 33 V |
| Typical input current | 7 mA |
| Input delay | Typically 0.3 ms; range 0.15 to 0.5 ms |
| Typical input resistance | 3.3 kΩ |
| Maximum unshielded input line | 50 m |
| Output switching current | 5 mA to 0.5 A |
| Output-group total current | Maximum 4 A per 8 outputs |
| Maximum resistive switching frequency | 100 Hz |
| Maximum inductive switching frequency | 2 Hz at 0.3 A; 0.5 Hz at 0.5 A |
| Output fuse | 7 A fast-acting; one fuse per 8 outputs |
| Maximum unshielded output line | 400 m |
| Typical backplane consumption | 80 mA at 5 V |
| Typical field-supply consumption | 220 mA at 24 V |
| Nominal power loss | 8 W |
| Isolation arrangement | One common group for all 32 inputs and outputs |
| Dimensions (W × H × D) | 20 × 255 × 195 mm |
| Approximate weight | 0.4 kg |
Frequently Asked Questions
Can I use 6ES5482-4UA20 with an IP 257 interface?
The 4UA20 version does not provide the IP 257 interface.
Which channels can I change between input and output on 6ES5482-4UA20?
The eight channels addressed as 1.0 to 1.7 can each be assigned as an input or an output.
Are the input and output groups of 6ES5482-4UA20 isolated separately?
All 32 input and output channels form one common isolated group.
What must I do with the output bit when a configurable channel on 6ES5482-4UA20 is an input?
The corresponding output register bit must remain zero when that channel is used as an input.
Can I connect different sensor and 1L+ supplies to 6ES5482-4UA20?
When any configurable channel is used as an input, its sensors and the 1L+ connection must use the same power supply.
How much current can eight outputs of 6ES5482-4UA20 carry together?
An eight-output group has a maximum total switching current of 4 A, subject to the ventilation and temperature conditions.
Can 6ES5482-4UA20 switch a 0.5 A inductive load twice per second?
At 0.5 A the maximum inductive switching frequency is 0.5 Hz, while 2 Hz applies at 0.3 A.