- Provide the required three-pole upstream protection; the unit has no internal fuse.
- Keep the natural-convection clearances at 50 mm above and below.
- Set the selected constant-current or latching-shutdown response to suit the load.
- Use screw-terminal conductor sizes within 0.2–4 mm² for input and output power wiring.
6EP3436-8SB00-0AY0 SITOP PSU8200 Three-Phase 24 V 20 A Power Supply
A 480 W SITOP supply with 400–500 V three-phase input, adjustable 24–28 V output and short-duration overload capacity.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP3436-8SB00-0AY0 |
| Product Type | Stabilized industrial power supply |
| Core Function | Converting mains power into an isolated regulated DC supply |
| Application | Industrial control-cabinet power systems |
Regulate cabinet power
The output is adjustable from 24 to 28 V with a maximum supplied power of 480 W.
Support transient loads
The supply provides 150% rated-current overload capability for up to 5 seconds per minute and a typical 60 A short-circuit boost for 25 ms during operation.
Report and manage output status
A green 24 V OK indicator and relay contact support monitoring, while selectable protection offers constant-current operation or latching shutdown.
Product Overview
6EP3436-8SB00-0AY0 supplies 24 V DC at 20 A from a three-phase mains connection. Its wide input range and isolated regulated output support cabinet loads through normal line and load variations.
The output behavior is selectable for overload handling, and a relay contact reports the 24 V OK state. Two supplies can operate in parallel for increased capacity, while DIN-rail mounting keeps the installation width to 70 mm.
Key Functions
Regulate cabinet power
The output is adjustable from 24 to 28 V with a maximum supplied power of 480 W.
Support transient loads
The supply provides 150% rated-current overload capability for up to 5 seconds per minute and a typical 60 A short-circuit boost for 25 ms during operation.
Report and manage output status
A green 24 V OK indicator and relay contact support monitoring, while selectable protection offers constant-current operation or latching shutdown.
Official Specifications
| Rated AC input | 400–500 V, three-phase |
|---|---|
| Permissible input range | 320–575 V AC |
| Input frequency range | 47–63 Hz |
| Rated input currents | 1.2 A at 400 V; 1.0 A at 500 V |
| Maximum inrush at 25 °C | 16 A |
| Minimum mains buffering | 15 ms at 400 V and rated load |
| DC output rating | 24 V, 20 A, 480 W |
| Output adjustment | 24–28 V; maximum 480 W |
| Maximum output ripple and peaks | 100 mV ripple; 200 mV peaks |
| Overall voltage tolerance | 3% |
| Typical efficiency and power loss | 94%; 31 W at rated output |
| Overload capability | 150% rated current for up to 5 s/min |
| Operational short-circuit boost | 60 A typical for 25 ms |
| Protection characteristic | Approximately 22 A constant current or latching shutdown |
| 24 V OK signaling contact | Normally open relay; 60 V DC / 0.3 A |
| Maximum parallel units for increased power | 2 |
| Protection and electrical class | IP20; Class I; isolated SELV output |
| Operating temperature and derating | −25 to +70 °C; 2%/K derating from +60 to +70 °C |
| Cooling and mounting | Natural convection; EN 60715 35 mm DIN rail |
| Enclosure dimensions and net weight | 70 × 125 × 125 mm; 1.2 kg |
Frequently Asked Questions
Which mains supply is suitable for 6EP3436-8SB00-0AY0?
The supply accepts three-phase 400–500 V AC nominal input within a permissible 320–575 V range.
Can I raise the DC output voltage of 6EP3436-8SB00-0AY0?
The potentiometer adjusts the output from 24 to 28 V within the 480 W power limit.
Can two units of 6EP3436-8SB00-0AY0 be paralleled to increase power?
Up to two supplies can be connected in parallel for increased output capacity.
How much top and bottom clearance does 6EP3436-8SB00-0AY0 need?
Leave 50 mm above and 50 mm below the enclosure.
Can 6EP3436-8SB00-0AY0 supply its full current above 60 °C?
The output requires derating by 2% per kelvin from +60 to +70 °C.
How can a controller monitor the output of 6EP3436-8SB00-0AY0?
A normally open relay contact signals the 24 V OK state and is rated for 60 V DC at 0.3 A.
What upstream protection is required for 6EP3436-8SB00-0AY0?
Use a connected three-pole 6–16 A characteristic-C miniature circuit breaker or one of the specified Siemens circuit-breaker alternatives.