Siemens 6EP1336-3BA00 SITOP Modular 24 V DC 20 A Power Supply
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Set the wire jumper for the 120 V or 230 V input range before energizing.
- Keep the continuous output within 20 A and apply the specified high-temperature derating.
- Select constant-current operation or latching shutdown for the downstream circuit.
- Provide 50 mm clearance above and below the DIN-rail-mounted supply.
- Use the specified input and output conductor cross-sections and connect PE.
6EP1336-3BA00 SITOP Modular 24 V DC 20 A Power Supply
A 480 W SITOP modular supply with selectable 120/230 V AC input, 24 V DC at 20 A output and switchable short-circuit behavior.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP1336-3BA00 |
| Product Type | Stabilized industrial power supply |
| Core Function | Converts mains AC to regulated DC power |
| Application | Industrial control and automation cabinets |
Selectable mains range
A wire jumper selects the 120 V or 230 V AC input range.
20 A output
The regulated output is adjustable from 24 V to 28.8 V DC.
Fault behavior selection
Short-circuit operation can use constant-current limiting or latching shutdown.
Product Overview
6EP1336-3BA00 is a SITOP modular stabilized power supply rated at 24 V DC and 20 A, with a typical output power of 480 W.
The input range is selected for the installed 120 V or 230 V AC supply by a wire jumper, while the output potentiometer permits adjustment up to 28.8 V DC for the connected load circuit.
Key Functions
Regulated DC output for cabinet loads
The 24 V output supplies up to 20 A and can be adjusted between 24 V and 28.8 V, with input-to-output isolation and an LED indication for normal operation.
Switchable response to overload
The supply offers a constant-current short-circuit characteristic of approximately 23 A or latching shutdown, with separate yellow overload and red shutdown indications.
Parallel operation and mains buffering
Two units may be operated in parallel for increased output capacity, and the supply bridges a mains interruption for at least 20 ms at 230 V input and rated load.
Official Specifications
| AC Input Ranges | 85–132 V or 176–264 V, selected by wire jumper |
|---|---|
| Line Frequency | 47–63 Hz; nominal 50/60 Hz |
| Rated Input Current | 7.7 A at 120 V AC; 3.5 A at 230 V AC |
| Maximum Inrush Current | 60 A at 25 °C |
| Rated Output | 24 V DC, 20 A; 480 W typical |
| Output Voltage Adjustment | 24–28.8 V DC via potentiometer |
| Residual Ripple | 30 mV typical; 100 mV maximum |
| Output Voltage Peaks | 60 mV typical; 200 mV maximum |
| Mains Buffering Time | At least 20 ms at 230 V AC and rated output current |
| Short-circuit Characteristics | Approximately 23 A constant current or latching shutdown |
| Short-term Short-circuit Boost | 60 A typical for 25 ms during operation |
| Efficiency and Typical Power Loss | 89%; 59 W at rated output |
| Load-step Settling Time | 2 ms typical; 5 ms maximum |
| Enclosure and Electrical Protection | IP20; protection class I; isolated SELV output |
| Operating Temperature | 0–70 °C; 3.5%/K output-current derating above 60 °C |
| Storage and Transport Temperature | −40–85 °C |
| Input Terminals | L, N and PE screw terminals for 0.2–4 mm² conductors |
| Output Terminals | Two + and two − screw terminals for 0.5–4 mm² conductors |
| Dimensions (W × H × D) | 160 × 125 × 125 mm |
| Net Weight | 2.2 kg |
Frequently Asked Questions
Can I connect 6EP1336-3BA00 to either 120 V or 230 V mains without changing a setting?
Select the appropriate input range with the wire jumper before applying the 120 V or 230 V AC supply.
How far can I adjust the DC output of 6EP1336-3BA00?
The output potentiometer adjusts the voltage from 24 V to 28.8 V DC.
Which overload behavior can I select on 6EP1336-3BA00?
Choose either the approximately 23 A constant-current characteristic or latching shutdown.
What do the yellow and red indicators on 6EP1336-3BA00 mean?
The yellow LED indicates overload and the red LED indicates latching shutdown.
Can two units of 6EP1336-3BA00 supply a higher-current load together?
Two power supplies can be connected in parallel for increased output capacity.
How much ventilation clearance is needed around 6EP1336-3BA00?
Leave 50 mm above and below the supply, while adjacent housings may be placed side by side.
Must I reduce the load on 6EP1336-3BA00 above 60 °C?
Reduce the output-current rating by 3.5% per kelvin between 60 °C and 70 °C.