Siemens 6EP1334-2AA01 SITOP smart 24 V 10 A Power Supply
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Match the mains selector position to the incoming voltage and allow the specified inrush current in the feeder design.
- Keep the normal load within the ten-ampere rating and apply the forty-five-degree limit to a twelve-ampere load.
- Provide DIN-rail mounting with fifty-millimetre upper and lower clearances.
- Use the specified terminal conductors and account for the output protection characteristic when coordinating downstream circuits.
6EP1334-2AA01 SITOP smart 24 V 10 A Power Supply
SITOP smart 240 W supply with switch-selected 120/230 V AC input, a ten-ampere rated output and an adjustable 22.8–28 V output setting.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP1334-2AA01 |
| Product Type | Stabilized control power supply |
| Core Function | Isolated AC-to-DC power conversion |
| Application | Higher-current industrial 24 V loads |
Higher-current control supply
The rated output delivers twenty-four volts at ten amperes to the connected control circuit.
Short-duration overload reserve
The supply provides separate startup and in-service overload-current intervals.
Cabinet power integration
Screw terminals, a narrow DIN-rail housing and stated thermal loss support cabinet integration.
Product Overview
6EP1334-2AA01 supplies isolated, stabilized twenty-four-volt DC power for higher-current control circuits.
The DIN-rail unit combines output-current reserve with defined overload, ripple and recovery behavior for cabinet power-system design.
Key Functions
Higher-current control supply
The rated output delivers twenty-four volts at ten amperes to the connected control circuit.
Short-duration overload reserve
The supply provides separate startup and in-service overload-current intervals.
Cabinet power integration
Screw terminals, a narrow DIN-rail housing and stated thermal loss support cabinet integration.
Official Specifications
| Mains input ranges | Switch-selected 120/230 V AC; 85–132 V or 170–264 V |
|---|---|
| Input frequency | 47–63 Hz; nominal 50/60 Hz |
| Rated input current | 4.1 A at 120 V; 2.4 A at 230 V |
| Maximum inrush and duration | 65 A at 25°C; typical duration 3 ms; maximum I²t 3.3 A²s |
| Rated output | 24 V DC; 10 A; 240 W |
| Voltage adjustment | 22.8–28 V |
| Available output-current range | 0–12 A; 12 A up to +45°C |
| Minimum mains buffering | 20 ms at rated load with input 93/187 V |
| Ripple and voltage spikes | Ripple: 50 mV typical, 150 mV maximum; spikes: 150 mV typical, 240 mV maximum |
| Overload during startup | 30 A typical for 100 ms |
| Overload during operation | 33 A typical for 200 ms |
| Current limiting and sustained short circuit | Current-limit response 12.5–13.5 A; typical sustained short-circuit RMS current 16 A |
| Overvoltage threshold | Below 33 V |
| Efficiency and power loss | 90%; typical loss 27 W at rated output |
| Load-step settling | 0.2 ms typical for both 50-to-100% and 100-to-50% resistive load steps |
| Operating and storage ambient | Operation 0 to +60°C with natural convection; storage/transport −40 to +85°C |
| Enclosure and safety class | IP20; Class I; isolated SELV output |
| Screw-terminal conductors | 0.5–2.5 mm²; L, N and PE one each, L+ and M two each |
| Required free space | 50 mm above and below; 0 mm at left and right |
| Dimensions and mounting | 70 × 125 × 125 mm (W × H × D); EN 60715 35 × 7.5/15 mm DIN rail |
Frequently Asked Questions
What switch-on current must the feeder of 6EP1334-2AA01 accommodate?
The maximum inrush current is sixty-five amperes at twenty-five degrees Celsius with a typical duration of three milliseconds.
Will 6EP1334-2AA01 shut off immediately rather than limit current during a short circuit?
The supply uses a constant-current characteristic, with a current-limit response of 12.5–13.5 A and a typical sustained short-circuit RMS current of 16 A.
Can I install 6EP1334-2AA01 with no vertical ventilation gap?
Provide fifty millimetres of free space both above and below the housing.
How are the input and output terminals arranged on 6EP1334-2AA01?
The supply has one screw terminal each for L, N and PE and two each for L+ and M, accepting conductors from 0.5 to 2.5 square millimetres.
Can I screw 6EP1334-2AA01 directly to a wall without a mounting accessory?
This version is specified for the stated thirty-five-millimetre DIN rail and does not support direct wall mounting.
Does 6EP1334-2AA01 provide an NEC Class 2 output?
The supply is not classified as an NEC Class 2 source.
What thermal loss should I include for 6EP1334-2AA01 at rated output?
The typical power loss at rated output is twenty-seven watts.