Siemens 6ED1055-1MD00-0BA1 LOGO! AM2 RTD Temperature Expansion Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the compatible LOGO! base and expansion arrangement.
- Select the correct Pt100 or Pt1000 sensor configuration for both channels.
- Match each sensor connection to the selected two-wire or three-wire arrangement.
- Keep the supply, cabinet temperature and IP20 installation conditions within their limits.
6ED1055-1MD00-0BA1 LOGO! AM2 RTD Temperature Expansion Module
LOGO! AM2 RTD with two Pt100/Pt1000 inputs, two-wire or three-wire connections and a −50 to +200°C measuring range.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ED1055-1MD00-0BA1 |
| Product Type | Resistance-temperature input module |
| Core Function | Pt100 and Pt1000 temperature measurement |
| Application | Compatible LOGO! temperature-control systems |
Two temperature channels
Two analog input channels acquire Pt100 or Pt1000 resistance-temperature signals.
Sensor connection choices
Two-wire and three-wire connections accommodate the stated RTD wiring arrangements.
Compact expansion housing
The 36 mm wide module installs on a 35 mm DIN rail beside the LOGO! system.
Product Overview
6ED1055-1MD00-0BA1 adds two resistance-temperature inputs to a compatible LOGO! controller.
The AM2 RTD accepts Pt100 or Pt1000 sensors using two-wire or three-wire connections and fits a compact two-module-width DIN-rail housing.
Key Functions
Two temperature channels
Two analog input channels acquire Pt100 or Pt1000 resistance-temperature signals.
Sensor connection choices
Two-wire and three-wire connections accommodate the stated RTD wiring arrangements.
Compact expansion housing
The 36 mm wide module installs on a 35 mm DIN rail beside the LOGO! system.
Official Specifications
| Temperature input count | 2 analog RTD channels |
|---|---|
| Sensor types | Pt100 and Pt1000 |
| Sensor wiring | 2-wire or 3-wire |
| Measuring range | −50 to +200°C |
| Nominal supply | 12/24 V DC |
| Permitted supply range | 10.8–28.8 V DC |
| Typical input current | 40 mA |
| Mounting width | 2 module widths; 36 mm |
| Dimensions | 36 × 90 × 53 mm (W × H × D) |
| Rail mounting | 35 mm DIN rail |
| Enclosure protection | IP20 |
| Operating temperature | 0 to +55°C |
| EMC emission classification | EN 55011 Class B |
| Controller equipment standard | EN 61131-2 |
Frequently Asked Questions
Can I connect Pt1000 sensors directly to 6ED1055-1MD00-0BA1?
The module accepts Pt1000 as well as Pt100 resistance-temperature sensors.
Do my RTDs need a three-wire connection to use 6ED1055-1MD00-0BA1?
The module supports either two-wire or three-wire RTD connections.
Can I use a 12 V DC supply for 6ED1055-1MD00-0BA1?
A 12 V DC supply is supported within the permitted 10.8–28.8 V DC range.
Can 6ED1055-1MD00-0BA1 measure a process temperature above +200°C?
The stated measuring range ends at +200°C.
Can a 4–20 mA temperature transmitter connect directly to 6ED1055-1MD00-0BA1?
The input channels accept Pt100 or Pt1000 resistance sensors rather than a 4–20 mA transmitter signal.
How much space should I reserve beside the LOGO! for 6ED1055-1MD00-0BA1?
The module requires 36 mm of rail width.
What supply-current allowance should I include for 6ED1055-1MD00-0BA1?
The typical module input current is 40 mA.