Siemens ET 200PA SMART+ AQ 8xI HART Analog Output Module 6DL1165-6TF00-0PH1
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Product Overview
- Key Functions
- Official Specifications
- Frequently Asked Questions
- Compatibility & Ordering Notes
- Hot Selling Models
- Recommended Products
Overview
Siemens • SIMATIC ET 200PA SMART+
6DL1165-6TF00-0PH1 ET 200PA SMART+ AQ 8xI HART Analog Output Module
The AQ 8xI HART PA module provides eight configurable current outputs for process actuators, with HART communication, substitute values, channel diagnostics and long shielded cable support.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6DL1165-6TF00-0PH1 |
| Product Type | Eight-channel HART analog output module |
| Core Function | Controls process actuators and exchanges smart-device data |
| Application or Compatible Series | ET 200PA SMART+ process I/O |
Exact Identification
Match 6DL1165-6TF00-0PH1 character by character and confirm the complete ET 200PA SMART+ AQ 8xI HART Analog Output Module designation.
Interface Arrangement
Confirm the installed supply, ports, field connections and required accessories before wiring the replacement.
Configuration Check
Preserve the approved engineering project, network parameters and application data used by the installed system.
Product Overview
The AQ 8xI HART PA module provides eight configurable current outputs for process actuators, with HART communication, substitute values, channel diagnostics and long shielded cable support.
Channels support unipolar, bipolar and live-zero current output ranges. HART-capable outputs allow supported device communication through the process-I/O station. Supply monitoring, wire-break, short-circuit and overrange or underrange diagnostics support maintenance.
Key Functions
Flexible Current Ranges
Channels support unipolar, bipolar and live-zero current output ranges.
HART Field Communication
HART-capable outputs allow supported device communication through the process-I/O station.
Channel Diagnostics
Supply monitoring, wire-break, short-circuit and overrange or underrange diagnostics support maintenance.
Official Specifications
| Supported Current Ranges | 0 to 10 mA, 0 to 20 mA, -20 to +20 mA and 4 to 20 mA |
|---|---|
| Resolution | 15 bit or 16 bit including sign, depending on range |
| Actuator Connection | Two-wire current output |
| Maximum Resistive Load | 750 Ω |
| Maximum Inductive Load | 10 mH |
| Externally Applied Output Voltage Limit | -0.3 to +36 V |
| Maximum Shielded Cable Length | 1000 m |
| Resistive-Load Settling Time | 1.2 ms at 750 Ω |
| Inductive-Load Settling Time | 0.5 ms |
| Linearity Error | ±0.01 % of output range |
| Temperature Error | ±0.001 %/K of output range |
| Minimum Output Crosstalk Attenuation | 70 dB |
| Repeat Accuracy at 25 °C | ±0.02 % of output range |
| Operational Current Error | ±0.5 % across the full temperature range |
| Basic Current Error at 25 °C | ±0.1 % |
| Substitute Values | Configurable |
| Channel Status Indication | Green LED |
| Maintenance Indication | Yellow MAINT LED |
Frequently Asked Questions
Which current ranges can I configure on 6DL1165-6TF00-0PH1?
Select the supported unipolar, bipolar or 4 to 20 mA range required by each actuator.
Can 6DL1165-6TF00-0PH1 communicate with HART field devices?
Yes; configure HART communication and the corresponding channel parameters in the control-system project.
What output load can 6DL1165-6TF00-0PH1 drive?
Keep a resistive current-output load within 750 Ω and an inductive load within 10 mH.
How far can the shielded output cable run from 6DL1165-6TF00-0PH1?
A shielded output cable may be up to 1000 m under the documented installation conditions.
Which faults can 6DL1165-6TF00-0PH1 diagnose per channel?
The module can report wire-break, short-circuit, range and supply-related diagnostic conditions as configured.
What should I preserve before changing 6DL1165-6TF00-0PH1?
Save every output range, substitute value, HART assignment, diagnostic enable and field-terminal record.
How should I commission replacement outputs on 6DL1165-6TF00-0PH1?
Verify wiring and load first, then test scaling, safe substitute values, HART communication and each actuator response.
Compatibility & Ordering Notes
Compatibility Checklist
- Use only output loads and cable lengths within the documented limits.
- Match each HART device and current range to the configured channel.
- Validate substitute values and safe process response before enabling outputs.