Overview
- Use with the supported 3VA2 circuit breakers and ETU series 5 or 8.
- Allow the supplied 1.5 m cable route between the function box and the trip unit.
- Configure the installed EFB300 and assign its I/O with powerconfig.
- Use the separate voltage and current ratings for relay contacts and semiconductor outputs.
- Install inside an enclosed fixed switchboard and observe the specified terminal torque.
3VA99870UA10 SENTRON EFB300 External Function Box
An externally powered 24 V DC function box with one digital input, two relay outputs, two semiconductor outputs and a supplied 1.5 m cable.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3VA99870UA10 |
| Product Type | EFB300 external function box |
| Core Function | Adds configurable signaling and ZSI functions |
| Application | 3VA2 circuit breakers with ETU series 5 or 8 |
Configurable signals
One digital input and four outputs connect breaker events to the installation.
Two output technologies
Two relay outputs and two 24 V semiconductor outputs serve different external loads.
Breaker connection
The supplied 1.5 m cable links the EFB300 to the electronic trip unit.
Product Overview
3VA99870UA10 is a SENTRON EFB300 external function box that extends a 3VA2 circuit breaker with programmable I/O, zone-selective interlocking connections and an external ETU supply path.
The box operates from 24 V DC and connects to the electronic trip unit through the included 1.5 m cable; the canonical Siemens order number is 3VA9987-0UA10.
Key Functions
Event-based input and output assignments
One digital input, two relay outputs and two semiconductor outputs can be assigned to the required breaker signals using powerconfig.
Zone-selective interlocking connections
The ZSI interface connects the breaker to the coordinated protection scheme, with separate input and output connections for the interlocking network.
External trip-unit supply and diagnostics
The EFB300 provides an external ETU supply connection and supports device status checks and a local SET-button self-test during commissioning.
Official Specifications
| Rated Control Supply | 24 V DC, ±20% |
|---|---|
| Maximum Current Consumption | 0.16 A |
| Rated Apparent Power | 4 VA |
| Digital Input | 1 input, 24 V DC SELV/PELV |
| Digital Input Thresholds | Signal 1 from 15 V; signal 0 up to 5 V |
| Relay Outputs | 2 outputs; 6 A at 250 V AC or 5 A at 30 V DC |
| Relay Utilization Ratings | AC-12: 6 A at 250 V; AC-15: 3 A at 250 V |
| High-voltage DC Relay Ratings | DC-12: 0.2 A at 250 V; DC-13: 0.1 A at 250 V |
| Semiconductor Outputs | 2 outputs, 24 V DC, 100 mA |
| Breaker Communication Interfaces | 1 |
| ZSI Connection Capacity | Up to 20 connections at the input and 8 at the output |
| Included Connection Cable | 1.5 m |
| Terminal Connection | Removable, pluggable screw-terminal blocks |
| Conductor Cross-section | 0.5–2.5 mm² for solid or prepared finely stranded conductors |
| Screw-terminal Tightening Torque | 0.4–0.5 N·m |
| Enclosure and Pollution Degree | IP20; pollution degree 3 |
| Operating Temperature | −25–60 °C |
| Storage and Transport Temperatures | Storage: −25–70 °C; transport: −25–80 °C |
| Dimensions (W × H × D) | 70 × 116 × 36 mm |
| Net Weight | 242.5 g |
Frequently Asked Questions
Why are the outputs of a newly installed 3VA99870UA10 inactive?
The outputs are deactivated on delivery and must be assigned during commissioning with powerconfig.
How do I add 3VA99870UA10 to the circuit breaker configuration?
Declare the EFB300 as an installed breaker device in powerconfig before assigning the input and output functions.
Where can I check the operating status of 3VA99870UA10?
Open View, Measured Variables, Status Information and EFB Status in powerconfig to inspect the function box status.
Can I use the 100 mA semiconductor output of 3VA99870UA10 like a 6 A relay contact?
The semiconductor outputs are rated for 24 V DC at 100 mA, while the relay contacts have separate AC and DC load ratings.
What voltage must a control signal reach to switch the input of 3VA99870UA10 on?
The digital input recognizes signal 1 from 15 V and signal 0 up to 5 V.
Which cable is included for connecting 3VA99870UA10 to the trip unit?
A 1.5 m connection cable is included for the ETU connection.
How can I run a local commissioning self-test on 3VA99870UA10?
Use the SET button to initiate the function box self-test during commissioning.