Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
siemens 3ug4512 2br20 sirius phase failure and sequence monitoring relay-0

For SIEMENS

Home >  Products >  For SIEMENS

Siemens 3UG4512-2BR20 SIRIUS Phase Failure and Sequence Monitoring Relay

Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months

  • Overview
  • Hot Selling Models
  • Recommended Products
Overview
SIRIUS 3UG4

3UG4512-2BR20 SIRIUS Phase Failure and Sequence Monitoring Relay

Analog three-phase monitor for 160–690 V AC, with automatic reset, two changeover contacts and removable spring-loaded terminals.

At a Glance

Brand Siemens
Model 3UG4512-2BR20
Product Type Three-phase line monitoring relay
Core Function Phase-loss and phase-sequence detection
Application Three-phase machine supply monitoring

Phase-loss detection

The relay detects failure of a phase in the monitored three-phase supply.

Phase-sequence recognition

The phase-order function enables the control system to react to an incorrect phase sequence.

Automatic reset and contact outputs

Two changeover contacts provide the monitoring output, with auto-RESET specified for this variant.

Product Overview

3UG4512-2BR20 is a SIRIUS line monitoring relay for phase failure and phase sequence on three-phase AC systems. It provides two changeover contacts and uses a spring-loaded connection system with removable terminals.

The relay is intended for the two specified phase-monitoring functions. Its automatic reset, maximum 450 ms response time and slim snap-on housing help integrate phase status into machine control circuits.

Ordering focus: Check the three-phase voltage, required phase-monitoring functions, control-contact load and spring-terminal wiring; compare successor compatibility separately if a replacement is proposed.
Key Functions

Phase-loss detection

The relay detects failure of a phase in the monitored three-phase supply.

Phase-sequence recognition

The phase-order function enables the control system to react to an incorrect phase sequence.

Automatic reset and contact outputs

Two changeover contacts provide the monitoring output, with auto-RESET specified for this variant.

Official Specifications
Monitored supply 3 × 160–690 V AC, 50–60 Hz
Output contacts 2 changeover contacts
Reset mode Automatic reset
Maximum response time 450 ms
Maximum thermal contact current 5 A
AC-15 contact rating 3 A at 250 V or 400 V AC
DC-13 contact rating 1 A at 24 V DC
Minimum switching load 5 mA at 17 V
Output-relay fuse rating 4 A DIAZED fuse link
Rated insulation voltage 690 V, overvoltage category III, pollution degree 3
Rated impulse withstand voltage 6 kV
Relative repeat accuracy 1%
Typical contact endurance 10 million mechanical cycles; 100,000 electrical cycles at AC-15, 230 V
Terminal system Removable spring-loaded terminals
Conductor capacity 2 × 0.25–1.5 mm²; AWG 24–16
Front protection rating IP20
Operating / storage temperature −25 to +60 °C / −40 to +85 °C
Maximum installation altitude 2,000 m above sea level
Dimensions and net weight 22.5 × 94 × 91 mm (W × H × D); 128.19 g
Mounting Snap-on; any mounting position
Frequently Asked Questions

Does 3UG4512-2BR20 detect an incorrect phase order?

Yes; phase-sequence recognition is one of the two specified monitoring functions.

Does 3UG4512-2BR20 also provide under-voltage or phase-asymmetry detection?

No; the listed functions cover phase failure and phase sequence, without under-voltage, over-voltage or asymmetry detection.

Is reset on 3UG4512-2BR20 manual or automatic?

The specified reset function is auto-RESET.

What is the maximum monitoring response time of 3UG4512-2BR20?

The maximum monitoring response time is 450 ms.

How much can an output contact of 3UG4512-2BR20 switch at 400 V AC?

The AC-15 contact rating at 400 V AC is 3 A.

Which terminal style is supplied on 3UG4512-2BR20?

The relay uses removable spring-loaded terminals, with capacity for two 0.25–1.5 mm² conductors at the specified connections.

Is 3UG4512-2BR20 designated for a safety function?

No; the relay is not suitable for a safety function.

Compatibility & Ordering Notes
Before ordering 3UG4512-2BR20: Check the three-phase voltage, required phase-monitoring functions, control-contact load and spring-terminal wiring; compare successor compatibility separately if a replacement is proposed.

Before installation

  • Verify the monitored three-phase supply and the required phase failure/sequence behavior before wiring the control circuit.
  • Size contact loads using the applicable AC-15 or DC-13 rating rather than the thermal-current limit.
  • Use the specified conductor range, terminal arrangement and output-relay fuse protection.
  • Siemens lists 3UG5512-2BR20 as the preferred successor; check its full electrical and mechanical compatibility before substitution.
Hot Selling Models
ET200PRO 6ES7194-4CA50-0AA0
3RV2011-0KA15
7000-13201-2412000
34-1M/S1055 U-51626
70-EX 0525996
1494U-HP1
ABB NLMD-01
3NE4 102
VAA-4E4A-KE5-ZEJQ/E2L-KRO
VMPA2-M1H-J-PI
MGQL12-50
LV429266
SISP b11a1-1.62 24.05-81
MT2834BL
X20BC1083

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop

Evolo Automation is not an authorized distributor unless otherwise specified, representative, or affiliate of the manufacturer of this product. All trademarks and documents are the property of their respective owners and are provided for identification and informational.