Siemens 3UG4512-2BR20 SIRIUS Phase Failure and Sequence Monitoring Relay
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Verify the monitored three-phase supply and the required phase failure/sequence behavior before wiring the control circuit.
- Size contact loads using the applicable AC-15 or DC-13 rating rather than the thermal-current limit.
- Use the specified conductor range, terminal arrangement and output-relay fuse protection.
- Siemens lists 3UG5512-2BR20 as the preferred successor; check its full electrical and mechanical compatibility before substitution.
3UG4512-2BR20 SIRIUS Phase Failure and Sequence Monitoring Relay
Analog three-phase monitor for 160–690 V AC, with automatic reset, two changeover contacts and removable spring-loaded terminals.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3UG4512-2BR20 |
| Product Type | Three-phase line monitoring relay |
| Core Function | Phase-loss and phase-sequence detection |
| Application | Three-phase machine supply monitoring |
Phase-loss detection
The relay detects failure of a phase in the monitored three-phase supply.
Phase-sequence recognition
The phase-order function enables the control system to react to an incorrect phase sequence.
Automatic reset and contact outputs
Two changeover contacts provide the monitoring output, with auto-RESET specified for this variant.
Product Overview
3UG4512-2BR20 is a SIRIUS line monitoring relay for phase failure and phase sequence on three-phase AC systems. It provides two changeover contacts and uses a spring-loaded connection system with removable terminals.
The relay is intended for the two specified phase-monitoring functions. Its automatic reset, maximum 450 ms response time and slim snap-on housing help integrate phase status into machine control circuits.
Key Functions
Phase-loss detection
The relay detects failure of a phase in the monitored three-phase supply.
Phase-sequence recognition
The phase-order function enables the control system to react to an incorrect phase sequence.
Automatic reset and contact outputs
Two changeover contacts provide the monitoring output, with auto-RESET specified for this variant.
Official Specifications
| Monitored supply | 3 × 160–690 V AC, 50–60 Hz |
|---|---|
| Output contacts | 2 changeover contacts |
| Reset mode | Automatic reset |
| Maximum response time | 450 ms |
| Maximum thermal contact current | 5 A |
| AC-15 contact rating | 3 A at 250 V or 400 V AC |
| DC-13 contact rating | 1 A at 24 V DC |
| Minimum switching load | 5 mA at 17 V |
| Output-relay fuse rating | 4 A DIAZED fuse link |
| Rated insulation voltage | 690 V, overvoltage category III, pollution degree 3 |
| Rated impulse withstand voltage | 6 kV |
| Relative repeat accuracy | 1% |
| Typical contact endurance | 10 million mechanical cycles; 100,000 electrical cycles at AC-15, 230 V |
| Terminal system | Removable spring-loaded terminals |
| Conductor capacity | 2 × 0.25–1.5 mm²; AWG 24–16 |
| Front protection rating | IP20 |
| Operating / storage temperature | −25 to +60 °C / −40 to +85 °C |
| Maximum installation altitude | 2,000 m above sea level |
| Dimensions and net weight | 22.5 × 94 × 91 mm (W × H × D); 128.19 g |
| Mounting | Snap-on; any mounting position |
Frequently Asked Questions
Does 3UG4512-2BR20 detect an incorrect phase order?
Yes; phase-sequence recognition is one of the two specified monitoring functions.
Does 3UG4512-2BR20 also provide under-voltage or phase-asymmetry detection?
No; the listed functions cover phase failure and phase sequence, without under-voltage, over-voltage or asymmetry detection.
Is reset on 3UG4512-2BR20 manual or automatic?
The specified reset function is auto-RESET.
What is the maximum monitoring response time of 3UG4512-2BR20?
The maximum monitoring response time is 450 ms.
How much can an output contact of 3UG4512-2BR20 switch at 400 V AC?
The AC-15 contact rating at 400 V AC is 3 A.
Which terminal style is supplied on 3UG4512-2BR20?
The relay uses removable spring-loaded terminals, with capacity for two 0.25–1.5 mm² conductors at the specified connections.
Is 3UG4512-2BR20 designated for a safety function?
No; the relay is not suitable for a safety function.