- Apply the 400 V or 690 V motor-current rating appropriate to the actual circuit.
- Allow for the 170 VA coil pickup demand.
- Specify the required auxiliary switch because the basic unit has no instantaneous auxiliary contacts.
- Keep installation within −25 to +60 °C and at or below 2,000 m altitude.
3RT5036-1AN20 SIRIUS 50A 220VAC Power Contactor
A size S2 contactor rated 50 A and 22 kW at 400 V AC-3/AC-3e, with a 220 V AC 50/60 Hz coil and screw terminals.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3RT5036-1AN20 |
| Product Type | AC-operated power contactor |
| Core Function | Motor power-circuit switching |
| Application | Industrial motor starter assemblies |
400 V motor duty
Rated 50 A and 22 kW for AC-3 and AC-3e operation.
220 V AC control
The operating coil accepts 220 V AC at 50 or 60 Hz.
Size S2
Screw terminals and screw or 35 mm DIN-rail mounting support panel integration.
Product Overview
3RT5036-1AN20 switches three-phase motor power circuits using three normally open main contacts. Its AC-3 and AC-3e ratings reach 50 A and 22 kW at 400 V, with a size S2 body for industrial starter assemblies.
The control coil is rated 220 V AC at both 50 and 60 Hz. Main, auxiliary and control connections use screw terminals, while the basic unit has no built-in instantaneous auxiliary NO or NC contacts.
Key Functions
Switch three-phase motor loads
The three main NO contacts carry 50 A at 400 V in AC-3 and AC-3e duty, reducing to 24 A at 690 V.
Operate from an AC control circuit
The coil requires 170 VA apparent pickup power and 15 VA holding power at either 50 or 60 Hz.
Integrate into an S2 starter
The contactor supports side-by-side installation and screw or snap-on mounting on a 35 mm DIN rail.
Official Specifications
| Main-contact arrangement | 3 NO poles; no NC main contact |
|---|---|
| AC-3 and AC-3e rated current | 50 A at 400 V; 24 A at 690 V |
| AC-3 and AC-3e motor power | 15 kW at 230 V; 22 kW at 400 V; 30 kW at 500 V; 22 kW at 690 V |
| AC-1 rated current up to 690 V | 60 A at 40 °C; 55 A at 60 °C |
| Control-coil supply | 220 V AC, 50/60 Hz |
| Coil operating-voltage factor | 0.8–1.1 at 50 Hz; 0.85–1.1 at 60 Hz |
| Coil pickup and holding power | 170 VA pickup; 15 VA holding |
| Built-in instantaneous auxiliary contacts | 0 NO and 0 NC |
| Insulation and surge ratings | 690 V rated insulation voltage; 6 kV rated impulse withstand |
| Mechanical service life | 10 million operating cycles typical |
| Maximum AC-3 and AC-3e switching rate | 800 operations per hour |
| Main-circuit short-circuit fuses | gL/gG 160 A for coordination type 1; gL/gG 80 A for coordination type 2 |
| Main conductor capacity | 2 × 0.75–16 mm² for solid, stranded or fine-stranded conductors |
| Mounting and terminals | Size S2; screw terminals; screw or 35 mm DIN-rail mounting |
| Operating and storage temperatures | Operation: −25 to +60 °C; storage: −55 to +80 °C |
| Maximum installation altitude | 2,000 m above sea level |
| Front protection | IP20; finger-safe for vertical contact from the front |
| Dimensions and net weight | 55 × 112 × 115 mm (W × H × D); 0.84 kg |
Frequently Asked Questions
Can 3RT5036-1AN20 switch a 22 kW motor on a 400 V supply?
The AC-3 and AC-3e motor rating is 22 kW at 400 V with a rated current of 50 A.
Will the same 50 A rating apply to 3RT5036-1AN20 at 690 V?
The AC-3 and AC-3e current rating at 690 V is 24 A.
Can I operate 3RT5036-1AN20 from a 24 V DC control output?
The fitted coil requires a rated supply of 220 V AC at 50 or 60 Hz.
How much transformer capacity does the coil of 3RT5036-1AN20 require at pickup?
The coil has an apparent pickup demand of 170 VA and a holding demand of 15 VA.
Does 3RT5036-1AN20 include an auxiliary NO contact for a holding circuit?
The basic unit has no built-in instantaneous NO or NC auxiliary contacts.
Which gG fuse corresponds to type 2 coordination for 3RT5036-1AN20?
The main-circuit fuse requirement for type 2 coordination is gL/gG 80 A.
How can I secure 3RT5036-1AN20 to the control-panel backplate?
Use screw mounting or snap the contactor onto a 35 mm DIN rail.